Tecnosystemi TSCE-J1 Owner'S Manual Download Page 8

8

OPERATING FEATURES

HI300  TSCE-J1 Recommended Procedure

NOTE:On Automotive NC Systems leak test with the engine not in operation.

1. The air conditioning or refrigeration system should be charged with sufficient refrigerant to have a gauge 

,pressure of at least 340 kpa(50 psi) when not in operation.At temperatures below 15°C(59°F), leaks may not be 

measurable, since this pressure may not be reached.  

2. Take care not to contaminate the detector probe tip if the part being tested is contaminaled.if the part is 

particularly dirty, or condensate(moisture)is present, it should be wiped off with a dry shop tower or blown off 

with shop air .No cleaners or solvents should be used, since the detector maybe sensitive to their ingredients.

3. Visually trace the entire refrigerant system, and look for signs of air conditioning lubricant leakage,damage,and 

corrosion on all lines, hoses, and components. Each questionable area should be carefully checked with the 

detector probe,as well as all fittings, hoses to line couplings, refrigerant controls, service ports with caps in place, 

brazed or welded areas, and areas around attachment points and hold- downs on lines and components.

4. Always follow the refrigerant system around in a continuous path so that no areas of potential leaks are missed. 

If a leak is found, always continue to test the remainder of the system.

5. At each area checked, the probe should be moved around the location,.at a rate no more than 25 to 50mm/

second(1-2in/second). And no more than 5mm(1/4in) from the surface, completely around the position. Slower 

and closer movement of the probe greatly improves the likelihood. of finding a leak (see fig.6).  

6. An apparent leak shall be verified at least once as floolws:, a)Blow shop air into the area of the suspected leak,if 

nebessary,and repeat the check of the area.ln cases of very large leaks,blowing out the area with shop air often

helps locate the exact position of the leak. b)First move the probe to fresh air and reset. Then hold the probe tip a 

close as possible to the indicated leak source and slowly move around it until the leak is confirmed.

Automotive A/C Systems only- 7. Leak testing of the evaporalor core while in the air conditioning module shall be

accomplished by turning the air conditioning blower on high for a period of 15 seconds minimum,shutting it off, 

then waiting for the retrigerant to accumulate in the case for 10 minutes.

After such time,insert the leak detector probe into the blower resistor block or condensate drain hole,if no water 

is present,or into the closet opening in the heat- ing/ventilation/air conditioning case to the evaporator,such as 

the heater duct or a vent duct.lf the detector alarms,a leak apparently has been found. 

All systems- 8.Following any service to the refrigerant system and any other service which disturbs the refrigerant 

system.A leak test of the repair and of the service parts of the refrigerant system should be done.

Summary of Contents for TSCE-J1

Page 1: ...AUTOMATIC REFRIGERANT LEAK DETECTORTSCE J1 COD 11132033 Owner s Manual Rev 01 2013...

Page 2: ...ral information 3 Features 3 Parts Controls 4 Getting Started 5 Installing Batteries 5 Operating Features 6 Operating Instructions 7 Operating Features 8 Applications 9 Maintenance 9 Specifications 10...

Page 3: ...level 1 to level 7 Unique Tri Color LEDs show a progressive and wide ranging leak size indication communicate the sensitivity level and provide a true voltage indication of battery power level A tact...

Page 4: ...4 PARTS CONTROLS 1 SensingTip 2 TipProtector 3 PowerON OFF 4 ResetButton 5 SensitivityUp 6 SensitivityDown 7 LED Leak Indicators 8 FlexibleProbe B C I...

Page 5: ...ower indicator leftmost LED and a Battery Test function The Constant Power indicator allows the user to see the battery level at all times The LED will remain on whenever the unit is powered on lt may...

Page 6: ...J1 provides seven levels of sensitivity the sensitivity level is indicated on the visual display when either the SENSITVITY OR SENSITIVITY keys are pressed The base beeping tone is also an indication...

Page 7: ...ey This adjustment will not interrupt detection 6 If a full alarm occurs before the leak is pinpointed press the RESET key to reset the circuit to a zero reference as described above OPERATINGTIPS The...

Page 8: ...At each area checked the probe should be moved around the location at a rate no more than 25 to 50mm second 1 2in second And no more than 5mm 1 4in from the surface completely around the position Slo...

Page 9: ...nsing tip clean Prevent dust moisture and grease build up by utilizing the provided tip protector Never use the unit without the protector in place Before using the unit always inspect the tip and pro...

Page 10: ...0 1 oz yr 3gr yr for all Halogen based refrigerant SensingTip Life Approx 20 hours OperatingTemperatur 30 to 125 F 0 to 52 C Battery Life Approximately 30 hours normal use Duty Cycle Continuous no lim...

Reviews: