![Tecnosystemi TOTAL AIR 200P EVO PLUS User Manual Download Page 21](http://html1.mh-extra.com/html/tecnosystemi/total-air-200p-evo-plus/total-air-200p-evo-plus_user-manual_1072140021.webp)
21
Accessories for
Air Conditioning
Ventilation
Solutions
Air Curtains and
Accessories
Accessories
For Heating
Instruments &
Tools
Multi - Zone
Air Control System
TECHNICAL FEATURES
FREE - COOLING
When outdoor air conditions are good, namely, with an indoor summer temperature that is cooler
than the outside, the internal By-Pass damper must be switched manually. It automatically enters
into operation and excludes the cross-flow recuperator, so as not to reduce the comfortable
features of outdoor air and to reduce energy consumption for ventilation In winter, the logic is
reversed and the Free-Cooling feature is activated when the outdoor air temperature is higher
than the recovery temperature of the stale air in the various rooms.
In any case, if the outside temperature deviates too much from the desired indoor temperature,
the Free-Cooling mode is not activates; therefore, the mitigating passage is carried out through
the exchanger, whose aim is to provide comfort.
FREE - COOLING
EXTERNAL AIR
ASPIRATION
TREATED
AIR OUTFLOW
CODE
TOTAL AIR 200P/Y
TOTAL AIR 300P/Y
VOLTAGE 50 Hz [V]
1 ~ 230
1 ~ 230
MAXIMUM MOTOR POWER [W]
200
200
MOTOR CURRENT [A]
1.94
1.94
MAXIMUM FLOW [m³/h]
200
300
NOISE at 3 meters [dB(A)]
38
40
CHASSIS MATERIAL
electro-galvanized sheet
electro-galvanized sheet
INSULATION
closed-cell polyethylene,
10 mm
closed-cell polyethylene,
10 mm
FILTERS: SUPPLY/RETURN
G4
G4
DUCT DIAMETER [mm]
Ø 150 - 200
Ø 150 - 200
EFFICIENCY
92 %
90 %
RECUPERATOR TYPE