3) verify that the instrument or the device are supplied
4) observe the indication led on the device KEY 01: it has to result
green, because if the led results green blinking or red blinking, this
means that on the device it has not been downloaded any valid
configuration and therefore it’s useless to continue.
5) if the les results green, press the button placed on the device.
6) observe the indication led : after having pressed the button, the
led becomes red and therefore, at the end of the data transfer, it
becomes green.
7) now it is possible to disconnect the device.
Instrument supplied and device not supplied
SUPPLY
Instrument supplied from the device
SUPPLY ADAPTER
12 VDC
AC SUPPLY
For additional info, please have a look at the KEY01 instruction
manual.
5 - PROGRAMMABLE PARAMETERS
Here following are described all the parameters available on the
instrument. Some of them could be not present or because they are
depending on the type of instrument or because they are
automatically disabled as unnecessary.
Group “
]
InP”
(parameters relative to the measure input)
0
SSC ÷ FSC
Zero value with V / I
signals
0.Pot
4
100
SSC ÷ 9999
High scale limit input
with V / I signals
FSC
3
0
-1999 ÷ FSC
Low scale limit input
with V / I signals
SSC
2
J
Ptc
4.20
0.10
input C :
J / CrAL / S /
Ir.J / Ir.CA /
Pt1 / 0.50 /
0.60 / 12.60
input E :
J / CrAL / S /
Ir.J / Ir.CA /
Ptc / ntc /
0.50 / 0.60 /
12.60
input I :
0.20 / 4.20
input V :
0.1 /
0.5 / 1.5 /
0.10 / 2.10
Probe type:
J= thermocoupled J
CrAL= termocoupled K
S= thermocoupled S
Ir.J=Infrared Sen. IRS J
Ir.CA= Infrared Sen.
IRS K
Pt1= thermores. Pt100
0.50= 0..50 mV
0.60= 0..60 mV
12.60= 12..60 mV
Ptc= thermistor PTC
KTY81-121
ntc= thermistor NTC
103-AT2
0.20= 0..20 mA
4.20= 4..20 mA
0.1= 0..1 V
0.5=0..5 V
1.5= 1..5 V
0.10= 0..10 V
2.10= 2..10 V
SEnS
1
Note
Def.
Range
Description
Par.
1.000
0.000 ÷ 2.000
Rotation of the
measuring straight line
rot
9
0
-1999 ÷ 9999
Measuring Offset
OFSt
8
1.0
0FF÷ 20.0
sec.
Input digital filter
FiL
7
°C
°C / °F
Temperature unit of
measurement
Unit
6
0
Pt1 / Ptc / ntc:
0 / 1
norm sig.:
0 ÷ 3
Number of decimal
figures
dP
5
Group“
]
Out”
(parameters relative to the outputs)
ALno
ALno / ALnc
ALni / OFF
Functioning of output 2:
see “O1F”
O2F
11
ALno
ALno / ALnc
ALni / OFF
Functioning of output 1:
ALno= Alarm Out nor-
mally opened
ALnc= Alarm Out nor-
mally closed
ALni= Alarm Out nor-
mally closed with rever-
se led func.
O1F
10
Note
Def.
Range
Description
Par.
Group “
]
AL1”
(parameters relative to alarm AL1)
no
no / yES
Alarm AL1 activation in
case of measuring error
AL1i
20
OFF
OFF ÷ 9999
sec.
Activation delay of
alarm AL1
AL1d
19
1
OFF ÷ 9999
Alarm AL1 hysteresis
HAL1
18
9999
AL1L ÷ 9999
High threshold band
alarm AL1 or Maximum
set alarm AL1 for high
or low alarm
AL1H
17
-1999
-1999 ÷ AL1H
Low threshold band
alarm AL1 or Minimum
set alarm AL1 for high
or low alarm
AL1L
16
0
AL1L÷ AL1H
Alarm AL1 threshold
AL1
15
0
0 ÷ 15
Alarm AL1 functioning:
+1 = not activated at
power on
+2 = delayed
+4 = latch
+8 = aknowledged
Ab1
14
LoAb
LoAb / HiAb
LHAb
Alarm AL1 type:
LoAb= Low
HiAb= High
LHAb= Band
AL1t
13
Out1
Out1 / Out2 /
OFF
Output where alarm
AL1 is addressed
OAL1
12
Note
Def.
Range
Description
Par.
Gruppo “
]
AL2”
(parametri relativi all’allarme AL2)
OFF
OFF ÷ 9999
sec.
Activation delay of
alarm AL2
AL2d
28
1
OFF ÷ 9999
Alarm AL2 hysteresis
HAL2
27
9999
AL2L ÷ 9999
High threshold band
alarm AL2 or Maximum
set alarm AL2 for high
or low alarm
AL2H
26
-1999
-1999 ÷ AL2H
Low threshold band
alarm AL2 or Minimum
set alarm AL2 for high
or low alarm
AL2L
25
0
AL2L÷ AL2H
Alarm AL2 threshold
AL2
24
0
0 ÷ 15
Alarm AL2 functioning:
see “AL1”
Ab2
23
LoAb
LoAb / HiAb
LHAb
Alarm AL2 type:
see “AL1”
AL2t
22
Out2
Out1 / Out2 /
OFF
Output where alarm
AL2 is addressed
OAL2
21
Note
Def.
Range
Description
Par.
TECNOLOGIC spa - TLV 38