valore indicato

 

(ovvero l’uscita in mA aumenti al valore indicato e la centrale, cui è collegato il rilevatore, indichi 

circa la %LFL indicata). 

Se il valore fosse diverso, sarà necessario eseguire la “

Calibrazione

”. 

Bombola Utilizzata 

Test-Point (TP1-TP2)  Uscita in mA (S) 

% LFL 

Gas Metano al 20%LFL (0,88%v/v) in aria (

20,9% O

2

 circa

)

 

69÷75 mV 

7,2mA (± 0,3) 

20%LFL (± 2) 

Gas Metano al 50%LFL (2,2%v/v) in aria (

20,9% O

2

 circa

)

 

114÷126 mV 

12 mA (± 0,6) 

50%LFL (± 4) 

3) 

Terminata la “

Verifica

”, chiudere la bombola, togliere il TC011 e 

premere il tasto 

F2

 per ripristinare le condi-

zioni di funzionamento normale

. Considerare che l’uscita, tornerà progressivamente a 4 mA. 

AVVERTENZA

Per sicurezza, dopo 5 minuti dall’inserimento del codice, il rilevatore torna in funzionamen-

to 

normale. Si ricorda che durante la verifica si attiveranno i dispositivi d’allarme dell’Unità Centrale. 

“CALIBRAZIONE” (

I Codici disponibili sono due diversi Calibrazione 20% e Calibrazione 50%

questa funzione serve per 

ritarare completamente il rilevatore e va eseguita quando la 

VERIFICA

 non è stata superata.  

AVVERTENZE: 

Durante  la  Calibrazione,  l’uscita  in  mA  diventerà  0mA. 

La  “

Calibrazione

”  va  eseguita  esclusiva-

mente in aria pulita (ambiente senza la presenza di gas infiammabili o altri inquinanti). In base alla bombola di gas 
scelta, va utilizzato solo il corrispondente Codice, in caso di errore la procedura non verrà completata.

 

1.1. 

Se si utilizza la bombola con miscela 

Gas Metano al 20%LIE (0,88%v/v) in aria (20,9% O

2

 circa)

 deve esse-

re eseguito il “

Codice Calibrazione 20%: F2, F2, F2, F1, F2, F1

”. 

1.2. 

Se invece si utilizza la bombola con miscela 

Gas Metano al 50%LIE (2,2%v/v) in aria (20,9% O

2

 circa)

 deve 

essere eseguito il “

Codice Calibrazione 50%: F2, F1, F1, F1, F2, F2, F1

”. 

2. 

Dopo avere eseguito il codice, il Led Verde inizierà a lampeggiare. Attendere che il Led Giallo si accenda fisso. 

3. 

Infilare (tenerlo appoggiato) il TC011 sul porta-

sensore e regolare l’afflusso del Gas, in modo che il flussome-

tro indichi circa 0,3 l/min (

vedi Fig.2

).  

4. 

Attendere circa 3 minuti, poi, quando il Led Verde si accende fisso (e mentre è 

ACCESO fisso

), premere il tasto 

F2

 e tenerlo premuto finché i due Led non rimangono spenti (

AVVERTENZA

: se il  Verde che continua a  lam-

peggiare oltre 5/6 minuti: la calibrazione è fallita. Spegnere e accendere il rilevatore, dopo il preriscaldo, ripete-
re  la  procedura  di  “

Calibrazione

”.  Verificare  che  il  problema  non  dipenda  dal  gas  o  dal  flusso  instabile.  Se  la 

condizione persiste, sarà necessario sostituire il rilevatore e/o inviarlo al fornitore per la riparazione

5. 

Chiudere la bombola e rimuovere il TC011. A questo punto si possono verificare due casi: 

Led Giallo e Verde spenti:

 

la calibrazione è avvenuta correttamente, dopo 8 secondi automaticamente il rilevato-

re si spegne e si riavvia in funzionamento normale

 (

vedi capitolo 

FUNZIONAMENTO “ 

Preriscaldo

). 

Solo Led Giallo  Acceso:

 la calibrazione è fallita. In questo caso, dopo 8 secondi il rilevatore si riavvia automati-

camente  e  dopo  il  preriscaldo,  ripet

ere la procedura di “

Calibrazione

” senza reinserire il “

Codice

”. Se la condizione 

persiste, sarà necessario sostituire il rilevatore e/o inviarlo al fornitore per la riparazione. 

 

EN

 

 GENERAL INFORMATION 

The 

SE182P

 series are gas detectors with a catalytic sensor for flammable gases, are used in gas alarm systems 

for  car  parks,  heating  plants,  and  environments  to  be  protected  from  possible  leaks  of  gases  such  as  Methane, 
LPG,  etc.  Different  models  are  available,  the  only  difference  is  the  calibration  carried  out  for  the  specific  gas.  All 
have  a  three-wire  4÷20mA  linear  output  signal  (

S

)  with  full  scale 

100%  LFL  (Lower  Flammable  Limit)

  of  the 

measured gas 

(

Sensor Linearity up to 50%LFL)

. The instruments comprise of a thermoplastic 

housing, in which the 

elec-

tronic 

circuit  and  the  connection  terminals

  are  mounted

;  the  sensor  is  placed  in  the  yellow  sensor  holder  on  the 

housing cover.

 It is for wall installation and the protection code is IP65.

 

The 

SE182P

 are normally connected to our gas control units. 

NOTES ON THE AVAILABLE MODELS 

SE182PM is to be use in plants powered by Methane (CH

4

), 

is calibrated to detect Methane, a gas lighter than 

air. Its density as to air is 0.55 and its LFL (

Lower Explosive Limit

) is 4.4%v/v 

(%volume

).

 

SE182PG is to be use in plants powered by LPG, 

is calibrated to detect LPG, a gas heavier than air and con-

sists of a mixture of 20÷30% Propane (C

3

H

8

) and 80÷70% Butane (C

4

H

10

). Propane density as to air is 1.56 while 

Butane' is 2.05. The LFL is 1.7%v/v for Propane and 1.4%v/v for Butane. Standard calibration to LPG is carried out 
for Butane gas. 

TS282PB (Unleaded Gasoline/Petrol) 

is calibrated to detect Gasoline vapours heavier than air and highly flam-

mable. Its density as to air about 2.8 and its LFL (

Lower Explosive Limit

) is about 1.2%v/v 

(%volume

).

 

OPERATIONAL DESCRIPTION 

The  catalytic  sensor  is  not  sensitive  to  humidity  and  temperature  variations.  The  calibration  is  performed  for  the 
specific gas to be detected; but it can contemporaneously detect any other flammable gas or solvents that should 
be present in the same environment. 
On the PCB (printed circuit board placed inside the housing cover) there are two F1 e F2 keys, using for the Test 
and Calibration routine, protected by a code, and 2 LEDs shows the operating conditions: 

Green LED "ON": 

 

normal operating condition. 

Yellow LED "FAULT": 

 

the sensor should be faulty, disconnected, out of scale or expired. 

Preheating

: when the detector is powered, a pre-heating time of about 60 seconds begins, indicated by the flash-

ing of the yellow "FAULT" LED and during this time the output remains at 4 mA. 

After this period, the green LED “

ON

” illuminates to indicate normal functioning. After this period the unit is able to 

detect gas even if it attains the optimum stability conditions after about 48 hours continual functioning. 

Summary of Contents for SE182PB

Page 1: ... jusqu a 50 LFL LII Limite del Sensore Sensor limits Limite échelle 100 LFL LII Sensore Sensor Capteur Catalitico Catalityc Catalytiques Preriscaldo Preheating Préchauffage 30 secondi seconds secondes Tempo di risposta T50 Response time T50 Temps de résponse T50 30 secondi seconds secondes Precisione Accuracy Precision 10 Deriva a lungo termine in aria pulita Long time drift in pure air Dérive à l...

Page 2: ...ocedere alla Re golazione del 4mA come indicato avanti in VERIFICA FUNZIONAMENTO Funzionamento Normale deve essere acceso il solo Led Verde ON Guasti in caso di guasto del sensore l uscita S va a 0 mA FAULT Il segnale sarà poi interpretato dalla centrale e segnalato come una situazione di guasto Il Led Giallo si accende ogni 4 secondi con il Led Verde acceso per avvisare che il Sensore ha superato...

Page 3: ... Ossigeno circa Gas Metano al 50 LFL 2 2 v v in aria 20 9 Ossigeno circa I sensori Catalitici non possono assolutamente funzionare in carenza d ossigeno È possibile usare sia bombole monouso con valvola d erogazione sia ricaricabili ad alta pressione con riduttore di pressione Inoltre è necessario il kit di calibrazione Tecnocontrol mod TC011 per gas non corrosivi TEST ELETTRICO Codice Test F2 F2 ...

Page 4: ...icamente il rilevato re si spegne e si riavvia in funzionamento normale vedi capitolo FUNZIONAMENTO Preriscaldo Solo Led Giallo Acceso la calibrazione è fallita In questo caso dopo 8 secondi il rilevatore si riavvia automati camente e dopo il preriscaldo ripetere la procedura di Calibrazione senza reinserire il Codice Se la condizione persiste sarà necessario sostituire il rilevatore e o inviarlo ...

Page 5: ... pole non reversible and plug in terminals For con nections and distance see also the specific instructions of the control unit to which the detector must be connect ed We recommend using a shielded 3 wire cable with the shield connected to the earth on the control unit side The maximum distance from the control unit to which the detectors can be connected depends on the power supply See Table 1 N...

Page 6: ...iplied by 1 55 K Butane see Table 2 would become 31 LFL 8 96 mA If instead e g to check the SE182PG a cylinder with a 0 28 v v Butane Air mixture corresponding to 20 LFL Butane is used the code must not be used and the result will be 20 LFL 7 2 mA 1 With the keys perform the Cal Check Code Wait until the Yellow Led starts to flash the green one remain fix 2 Insert the TC011 over the sensor holder ...

Page 7: ...ever ma peut détecter en même temps d autres gaz combustibles présent dans la pièce Sur le circuit situé à l intérieur du couvercle du boîtier se trouvent les touches de codage F1 et F2 pour les opéra tions de vérification et calibrage et 2 LED indiquant les conditions de fonctionnement Led Vert ON fonctionnement normal Led Jaune FAULT capteur en panne ou déconnecté ou saturé ou échu Préchauffage ...

Page 8: ...Les autres substances causant une perte tempo raire de sensibilité sont les halogènes l hydrogène sulfuré le chlore les hydrocarbures chlorés trichloréthylène ou tétrachlorures de carbone Après une brève période en air propre le capteur reprend son fonctionnement normal VERIFICATIONS PERIODIQUES Remarque Important les opérations suivantes doivent être exécutées seulement par personnel expert et fo...

Page 9: ...VERTISSEMENT Durant l opération d étalonnage l appareil porte la sortie S à 0mA L étalonnage doit être exé cuté en air propre exclusivement milieu sans la présence de gaz inflammables ou autres En fonction du cylindre choisi seul le code correspondant doit être utilisé En cas d erreur la procédure ne sera pas effectuée 1 1 Si la bouteille est utilisée avec un mélange de Methane à 20 LII 0 88 v v e...

Page 10: ...s heavy gas densité par rapport à l air gaz léger gaz lourd 3 Valore in di volume del 20 LFL del gas rilevato Value in volume of 20 LFL of the gas detected Valeur en du volume correspondant à 20 de la LII du gaz détecté 4 Coefficiente di sensibilità riferito al gas Metano Gain with respect to Methane Coefficient de sensibilité par rapport au gaz methane Tabella 3 Table 3 Tableau 3 SE182P Uscita Ou...

Reviews: