TFNET

7

2 - MAINTENANCE

Periodic maintenance of the system

For perfect ef

fi

 ciency of the 

fi

 re detection system, the customer shall provide for a preventive maintenance program. The 

frequency of inspections depends on several factors; it is recommended to perform an inspection on average every 6 months 
(unless speci

fi

 cally required otherwise). Maintenance should be carried out by specialized personnel provided with the necessary 

know-how and equipment to perform adequate maintenance work. It is assumed that the information needed to perform a proper 
maintenance can be provided by the designers and/or manufacturers the 

fi

 re detection system.

The maintenance guidelines are provided in the Italian standard UNI 11224.
The most signi

fi

 cant checks should include at least: 

• 

Functional state of power supply units and accumulators (APS) of the control panel and of the system power supply modules. 

• 

State of the batteries of the self-powered devices (sirens, communicators).

• 

Functional tests of the sensors that make up the system.

• 

Checks about the state of cleanliness of the analysis chambers of the optical sensors.

• Ef

fi

 ciency of the control organs of the control panel and repeaters.

• 

Functional and operational ef

fi

 ciency of the acknowledgement, evacuation and system recovery procedures.

• Ef

fi

 ciency of manual alarm button module.

• Ef

fi

 ciency of optical and acoustic noti

fi

 cation module.

• Ef

fi

 ciency of phone communicators (phone call tests).

• Veri

fi

 cation of system actuations entrusted to input and output interface modules, etc.

• 

Check for correct tightening of the terminals wires.

• 

Final drafting of a test report signed by the maintainer and by the customer for acceptance.

Summary of Contents for TecnoFire TFNET

Page 1: ...by Installation Document version 0 3 FW version 1 0 00 HW version TFNET Setup SW version 5 2 Update date 12 2016 Language English TFNET Communication interface...

Page 2: ...TFNET 2 TFNET TFAXFIRE Systems Compatibility TFA1 298 Ver 1 3 09 TFA2 596 Ver 1 3 09 TFA4 1192 Ver 1 3 09...

Page 3: ...4 INSTALLATION NOTES 4 1 Assembly view 11 4 2 Installation 12 4 3 Connection cables 12 5 USER INTERFACE 5 1 Front panel 13 5 2 LED 13 6 OPERATING MODES OF THE SYSTEM 6 1 Access levels and codes 15 6 2...

Page 4: ...TFNET 4...

Page 5: ...horough knowledge of the product acquired attending specific training courses at the premises of Tecnofire fire systems division of Tecnoalarm S r l Environmental requirements The TFNET communication...

Page 6: ...TFNET 6...

Page 7: ...gnificant checks should include at least Functional state of power supply units and accumulators APS of the control panel and of the system power supply modules State of the batteries of the self powe...

Page 8: ...TFNET 8...

Page 9: ...1999 05 EC class 1 TTE Standards EN 50136 1 1 EN 50136 2 1 Approved for use with TFA1 298 TFA2 596 and TFA4 1192 control panels General speci cations Model TFNET Description Ethernet interface Protoco...

Page 10: ...TFNET 10...

Page 11: ...tor 4 INSTALLATION NOTES Introduction In Italy the installation of this device is regulated by UNI and national standards including DM 37 of 22 Jan 2008 which requires that fire protection systems are...

Page 12: ...ation interface is an expansion device for the TFAXFIRE control panels and is connected to them via the Master and or Slave RS485 BUSES The BUS can be connected in open loop or closed loop mode In the...

Page 13: ...pply status of the device Off Power supply off On Power supply on Green Indicates the status of the connections of the channels SERVER 1 SERVER 2 TECNOALARM TECNOSERVER TECNOALARM SERVICE Off No commu...

Page 14: ...TFNET 14...

Page 15: ...sing the RESET key B Switch the unit operating state manned to Unmanned and vice versa C Manually activate an Evacuation alarm D Access the list of menus reserved to Level 2 Level 3 It is possible to...

Page 16: ...is the selection pointer The pointer can be moved using the arrow keys up or down The choice of the menus can also be done by entering the quick selection number 6 2 Access level 2 The control panel...

Page 17: ...he device is the last device connected on the Bus Of course only if the connection Bus is in open line configuration Identification Normal condition Function JP1 RESET Open Hardware reset JP2 BOOT Ope...

Page 18: ...TFNET 18...

Page 19: ...TFABILMODBUS Note The option numbers not mentioned have not yet been assigned Enabling of software options Enabling of software options can only be performed from the control panel setting menu Repeat...

Page 20: ...TFNET 20...

Page 21: ...ce in the network is identified with the same address of the TFNET 192 168 0 10 Attention before proceeding please be sure to have the file required for the update The file is available from the site...

Page 22: ...change Type Size Open Cancel Exit Reading OK Find device on IP 192 168 0 10 port 10001 Tecnoboot status requested Status BOOT_READY Type PROG GSM Version 0 4 Block dim 1024 mult 4 Address 8010000 808...

Page 23: ...TFNET 23 NOTES...

Page 24: ...842 Via Ciri 38 10099 San Mauro T se Torino Italy Production Unit Strada del Cascinotto 139 54 10156 Torino Italy Tel 39 011 22 35 410 Fax 39 011 27 35 590 info tecno redetection com www tecno redetec...

Reviews: