background image

IST-2138.PM02.01/B

 

Istruzione / User’s Manual / Manuel d’utilisation 

Pag.11/11

 

 

 

 

 

190

65 

83 

105 

70 

Ø42 

107 

Fig. 1 –

 

Dimensioni /

 Size / Dimensions 

Imbocco Femmina ¾” Gas Conico UNI 6125 

”¾” UNI 6125 Female Gas Conical Thread 

Entrée femelle ¾” Gaz Conique UNI 6125

 

 

12-24V

 

mA

 

1

 

2

 

3

 

4

 

ON

 

OFF

 

SET

 

Dip Switch

 

 

TP1   TP2

 

Fig. 2 -

 

Schema di collegamento / Wiring diagram / Schéma 

AL2

 

AL3

 

AL

1

 

FAUL

T

 

1

 2

 3

 

5

 
4

 

6

 7

 8

 

F1 F2 

Scheda Uscite Relé 

Relays Output Board 

Sortie sur Realis

 

12÷24Vdc 

Alimentazione 

Power Supply 

Alimentation

 

Centrale rivelazione gas 

Gas Central Unit 

Centrale de détection

 

RL

-

 

+

 

Uscita in 4÷20 mA 

4÷20 mA Output 

Sortie en 4÷20 mA

 

Test Uscita  

Output Test 

Sortie Test 

40÷200mV

 

mV

 

 

Alimentazione 

/ Power Supply / Alimentation

 

100

300

400

500

50

0

5

200

Vdc

RL=Resistenza di carico 

/ Load resistor / Resistance de charge

RL

Ohm

Fig.4 -

 

Alimentazione / Resistenza di Carico 4÷20mA 

Power supply / Load resistance diagram 4÷20mA 

Alimentation / Résistance de charge 4÷20mA

 

600

0

10

15

 

20

 

25

28

650

10,8

24

Area di funzionamento 
Allowable oparating region 

350

700

800

 

0,3 L/min

 

Fig. 3 -

 Tester di calibrazione 

/ Calibration Tester / Kit de Calibration 

 

 

TECNOCONTROL S.r.l. Via Miglioli 47 SEGRATE ( MI ) 

 Tel: 02/26 92 28 90   Fax: 02/21 33 734

 

 

Summary of Contents for SE138PB

Page 1: ...arico Load Charge MAX 24V 1A SPST Uscita in Corrente Current Output Sortie en mA Resistenza di carico load resistor résistance de charge 4 20 mA lineare Linear linéaire 50 ohm 12Vdc 10 500 ohm 24Vdc 10 Campo di misura Standard Range Champ de mesure 0 100 LIE LEL Limite Scala Limits Limite échelle 100 LIE LEL Vita media in aria pulita Average Life in fresh air Vie moyenne en air pur 5 anni years an...

Page 2: ...are anche altri gas o solventi infiammabili se presenti nello stesso locale Nota i LED sono non sono visibili quando la custodia è chiusa Preriscaldo quando il trasmettitore è alimentato inizia la fase di preriscaldo del sensore segnalata dal lampeggio del LED giallo FAULT Dopo circa 60 secondi il LED giallo si spegne e si accende il verde ON che indica il nor male funzionamento Dopo questo tempo ...

Page 3: ...l senso re alle condizioni ambientali eseguire se necessario la Regolazione dello Zero vedi Verifiche e Calibrazione AVVERTENZE La vita utile del sensore in aria pulita è mediamente 5 anni Al termine di questo periodo indicato dallo strumen to con un lampeggio del Led Giallo ogni 4 secondi è necessario sostituire la Cartuccia Sensore Verifiche Periodiche si consiglia di eseguire ogni anno la verif...

Page 4: ...ndo la miscela di gas sopra indicata la corretta ri sposta al gas e può essere eseguita dopo la Calibrazione o dopo l installazione ma va eseguita soprattutto duran te le manutenzioni periodiche in quanto è l unico metodo per controllare l effettivo funzionamento del rilevatore Infilare il TC011 sul portasensore regolare il riduttore della Bombola in modo che il flussometro indichi circa 0 3 l min...

Page 5: ...LED activate green LED off FAULT relays activate and 0mA output signal this signal different kind of faults 1 The Dip Switch set up is wrong please verify see Table 2 and 3 2 The Cartridge Sensor is not working please replace with new one 3 If a new Cartridge Sensor is installed or it is not correctly connected or a not com patible one is mounted Please check the Cartridge connections and compatib...

Page 6: ...o the lighting of the LEDs it corresponds the activation of the relevant relays relay FAULT with the yellow LED relay ALARM1 with the 1st red LED relay ALARM2 with the 2nd red LED relay ALARM3 with the 3rd red LED At the end all the LEDs will remain lighted for around 5 seconds and then the detector returns at the conditions of normal operation It is advisable to perform this opera tion every 12 m...

Page 7: ...ALARM 2 1 led rouge ALARM 1 relais d alarme ALARM 1 Led vert ON fonctionnement normal Led jaune FAULT capteur en panne ou déconnecté ou saturé ou échu Touches F1 et F2 pour les opérations de vérification et calibrage En outre un signal de sortie est disponible S 4 20mA linéaire avec fin d échelle à 100 LIE du gaz d étalonnage Cette sortie peut être utilisée pour se raccorder sur une installation c...

Page 8: ... de sûreté des installations Montage en Fig 1 sont indiquées les dimensions Le détecteur doit être monté en position verticale avec le capteur tourné vers le bas Positionnement du SE138PM il doit être fixé à environ 20 30 cm du plafond le gaz méthane étant plus léger que l air Positionnement du SE138PG il doit être fixé à environ 20 30 cm du plancher le gaz GPL étant plus lourd que l air Positionn...

Page 9: ...es Après avoir inséré le Code du Zéro comme confirmation de l opération 1 clignotement de la 1ère led rouge et la sortie deviendra 4 0 mA Nous conseillons d exécuter cette opération après l installation ou après le changement de la Cartouche Cap teur et chaque semestre en fonction des conditions ambiantes Considérer que le SE138P est doté d un suiveur de zéro sophistiqué qui toutes les heures refa...

Page 10: ...12 30 60 30 OFF ON ON Risevato Reserved Réservé Risevato Reserved Réservé ON ON ON Risevato Reserved Réservé Risevato Reserved Réservé Tabella 3 Table 3 Tableau 3 S1 SET Dip Switch Contatti Relé Allarme Relays contacts SPST TECNOCONTROL S r l Via Miglioli 47 SEGRATE MI Tel 02 26 92 28 90 Fax 02 21 33 734 Contact de Relais I Dip Switch vanno posizionati prima d alimentare l apparecchio Dip Switch s...

Page 11: ...Centrale rivelazione gas Gas Central Unit Centrale de détection RL Uscita in 4 20 mA 4 20 mA Output Sortie en 4 20 mA Test Uscita Output Test Sortie Test 40 200mV mV Alimentazione Power Supply Alimentation 100 300 400 500 50 0 5 200 Vdc RL Resistenza di carico Load resistor Resistance de charge RL Ohm Fig 4 Alimentazione Resistenza di Carico 4 20mA Power supply Load resistance diagram 4 20mA Alime...

Reviews: