Menu Outputs
22
After selecting the type (such as
SPEED CTRL
, since a solar pump shall run speed-controlled at
output 1 later on) all available parameter lines are faded in.
OUTPUT STATUS:
TYPE: SPEED CTRL
DESIGNATOR
GROUP: General
DES:
-------
MODE: Wave packet
(This line is suppressed in
SWITCH OUTP
)
DELAY: 0 Sec
Rise-delay time
RUN-ON: 0 Sec
After-running time
In the next step the name (designator)
Solar pump 1
is to be assigned to the output 1. As in the pa-
rameterizing of the sensors superset "designator groups" and a sequential index until 9 (e.g.
Solar
pump 4
) were specified. Most suggestions like
Solar pump 1
are to be found in
General
. In order to
proceed quickly from one designator to the next, the key (x10) must be pressed at the same time.
The waveform can be selected via the parameter "
MODE
" of the speed control. While usual commer-
cial pumps are controlled by wave packets (fast switching on/off of the motor), ventilated motors need
a phase control (such as a light dimmer).
NOTICE:
The menu allows a choice between wave packet and phase angle however in the standard
version the output of waveform "phase angle" is not possible. Special versions on request.
“
DELAY
”
permits the setting of an adjustable rise-delay time.
Via “
RUN-ON
” the cutoff-delay time of the output can be determined.
If after the entrance the TYPE
MIXER
has been selected, the following indication appears:
OUTPUT STATUS:
TYPE: MIXER
DESIGNATOR
GROUP: General
DES:
-------
RUNTIME: 2.5 min
With “
RUN TIME
” the total running time of the mixer motor has to be fixed.
Where there are stability problems in the mixer control circuit, the mixer running time can be in-
creased or reduced to lengthen or shorted the pulses or pauses. This has no influence on the remain-
ing running time, as this is always loaded with 20 minutes upon a direction change or enable.
WARNING:
The factory setting of the total running time of the motor is 0 seconds! Thus the mixer is not con-
trolled. Unfortunately it is not possible for reasons due to the programming technique to preset anoth-
er value in the factory setting. Therefore this parameter must be entered while setting the mixer out-
put.
The submenu option “
OUTPUT STATUS
“ represents a special characteristic. Here a list of all func-
tions and messages (including status) controlling the output is put down. By this it is easier to under-
stand at the system, why a pump is being controlled right now or not. In addition, it is possible to enter
the corresponding functions out of the output status in order to check the function status there (see
function modules).
If an output is controlled by multiple functions, the output switches ON, if at least one function is active
(OR – function)!
The outputs (manual and automatic) are controlled only 30 sec. after the starting up of the
control unit.