Commissioning
Proline Promass F 500 EtherNet/IP
138
Parameter
Prerequisite
Description
User interface /
Selection / User
entry
Factory setting
Failure mode
One of the following options is
selected in the
Assign current
output
• Mass flow
• Volume flow
• Corrected volume flow
• Target mass flow
• Carrier mass flow
• Density
• Reference density
• Concentration
• Temperature
• Carrier pipe temperature
• Electronic temperature
• Oscillation frequency 0
• Oscillation amplitude 0
• Frequency fluctuation 0
• Oscillation damping 0
• Oscillation damping
fluctuation 0
• Signal asymmetry
• Exciter current 0
One of the following options is
selected in the
Current span
parameter (→ 137):
• 4...20 mA NAMUR
• 4...20 mA US
• 4...20 mA
• 0...20 mA
Define output behavior in
alarm condition.
• Min.
• Max.
• Last valid value
• Actual value
• Defined value
Max.
Failure current
The
Defined value
option is
selected in the
Failure mode
parameter.
Enter current output value in
alarm condition.
0 to 22.5 mA
22.5 mA
*
Visibility depends on order options or device settings