3 - PHYSICAL CHARACTERISTICS
Model
Total cooling capacity
LS
kW
(1)
MS
kW
HS
kW
Sensible cooling capacity
LS
kW
(1)
MS
kW
HS
kW
Pressure drop on water in cooling mode
kPa
(1)
(10 kPa = 1 m W.G.)
Heating capacity
LS
kW
(2)
MS
kW
HS
kW
Pressure drop on water in heating mode
kPa
(2)
(10 kPa = 1 m W.G.)
Air flow rate
LS
m
3
/h
MS
m
3
/h
HS
m
3
/h
Characteristics of fan motor
230 V / 1/ 50 Hz
(3)
W
(4)
A
Maximum power input
W
(with condensate pump)
Maximum current
A
Sound power level
LS
dB(A)
(5)
MS
dB(A)
HS
dB(A)
Sound pressure level (at 2.5 m indoors)
LS
dB(A)
(5)
MS
dB(A)
HS
dB(A)
MW 2
1.4
1.5
2.1
1.3
1.5
1.5
3
2.2
2.4
2.7
2.4
325
370
430
28
0.13
54
0.25
40
45
49
22
27
31
MW 3
2.4
2.6
2.8
1.7
1.9
2.1
5
2.9
3.2
3.5
4.1
325
370
430
28
0.13
54
0.25
40
45
49
22
27
31
MW 4
3.3
3.7
4
2.3
2.7
2.9
11
3.8
4.5
5.1
9
495
630
760
72
0.30
98
0.45
46
51
54
28
33
36
MW 5
4.6
4.9
5.2
3.2
3.5
3.8
17
5.5
6
6.5
13.8
665
760
855
86
0.39
112
0.5
54
57
58
36
39
40
4.1 NOMINAL CONDITIONS
3.1 WEIGHT
Air handler
MW 2
MW 3
MW 4
MW 5
Packed weight (kg)
13
13
17.7
17.7
Net weight (kg)
10
10
13.5
13.5
3.2 DIMENSIONS
MW 2
MW 3
MW 4
MW 5
L
810
810
1000
1000
H
360
360
360
360
P
180
180
205
205
L
P
H
°C
20
15
30
25
3
1
2
117
71
Thickness : 27.5 mm
4 - PERFORMANCES
(1)
Air inlet: 27°C (DB) / 19°C (WB) ; water: inlet at 7°C at high speed, outlet at 12°C
(2)
Air inlet: 20°C; water inlet: 50°C (same flow-rate as under other conditions(1)).
(3)
Max. power consumption (at high speed).
(4)
Max. current consumption (at high speed).
(5)
Without condensate pump accessory.
Note :
Maximum water inlet
temperature: 60°C