Installation and Maintenance
Service Manual
9. Maintenance
9.1 Error Code
1. Malfunction display requirement
When there are several malfunctions, they will be displayed circularly.
2. Malfunction display method
(1) Hardware malfunction: immediate display; refer to “error code list”;
(2) Operation state: immediate display; refer to “error code list”;
(3) Other malfunctions: it is displayed after the compressor stops for 200s; refer to “error code list”.
Note: when the compressor is restarted, the malfunction display delay time (200s) is cleared.
3. Malfunction display control
The indicator lamp and dual 8 nixie tube displays shall be synchronized. That is when the indicator lamp blinks, the dual 8 nixie
tube displays the corresponding malfunction code.
4. Display control viaremote controller
Enter display control: press light button successively for 4 times within 3s to display the corresponding malfunction code;
Exit display control: pressing light button successively for 4 times within 3s or after display is shown for 5min, the display will
terminate.
Error Code List
Malfunction Name
Malfunction types
Dual-8
Nixie Tube
Indicator Display
Operation
indicator
Cooling
indicator
Heating
indicator
Fault in input power zero
Hardware malfunction
U8
blink 17 times
Jumper cap malfunction protection
Hardware malfunction
C5
blink 15 times
No feedback of indoor fan motor
Hardware malfunction
H6
blink 11 times
Indoor ambient sensor open or short circuit
Hardware malfunction
F1
blink once
Indoor tube sensor open or short circuit
Hardware malfunction
F2
blink twice
Inlet tube sensor malfunction
Hardware malfunction
b5
blink 19 times
Outlet tube sensor malfunction
Hardware malfunction
b7
blink 22 times
IPM sensor circuit malfunction
Hardware malfunction
P7
blink 18 times
Outdoor ambient sensor open or short circuit
Hardware malfunction
F3
blink 3 times
Inlet pipe temperature sensor of outdoor
condenser is open-circuit/short circuit(commercial
air con)
Hardware malfunction
A5
Outdoor tube sensor open or short circuit
Hardware malfunction
F4
blink 4 times
outlet pipe temperature sensor of outdoor
condenser is open-circuit/short circuit(commercial
air con)
Hardware malfunction
A7
Exhaust sensor open or short circuit
Hardware malfunction
F5
blink 5 times
Communication failure between indoor unit and
outdoor unit
Hardware malfunction
E6
blink 6 times
Compressor phase current detection circuit
malfunction
Hardware malfunction
U1
blink 12 times
Compressor demagnetization protection
It can be displayed
through remote
controller within 200s
and displayed directly
after 200s
HE
blink 14 times
PN voltage drop protection
U3
blink 20 times
IPM high temperature protection
P8
blink 19 times
Refrigerant-lacking or blockage protection
F0
blink 10 times
Capacitor charge malfunction
Hardware malfunction
PU
blink 17 times
Refrigerant system high pressure protection
Hardware malfunction
E1
blink once
system low-pressure protection (reserved)
Hardware malfunction
E3
blink 3 times
Compressor over load protection
It can be displayed
through remote
controller within 200s
and displayed directly
after 200s
H3
blink 3 times
Fault in matching
Hardware malfunction
LP
blink 19 times
Loading EEPROM malfunction
Hardware malfunction
EE
blink 15 times
AC current detect circuit malfunction
Hardware malfunction
U5
blink 13 times
Outdoor DC fan motor malfunction
Hardware malfunction
L3
blink 23 times
Mode conflict
operation status
E7
blink 7 times