• If tripped:

-

Turn off and lock out the unit.

- Correct the fault.

- Reset the circuit breaker.

Note:

The opening of circuit breaker

Q4

disconnects only the control part. In the event of maintenance / servicing, all circuits

must be disconnected by opening the main circuit breaker.

7.5 - TROUBLESHOOTING RECOMMENDATIONS

• All maintenance and servicing operations on the refrigerating circuit must be conducted in accordance with standard trade

practices and safety rules: recovery of the refrigerant, inert shielded (nitrogen) brazing, etc…

• All brazing operations must be conducted by qualified welders.

• For equipment charged with R 410 A, refer to the specific instructions in paragraph 4.1 and in the outdoor unit's manual.

• This unit is equipped with pressurised equipment, for example piping.

Use only genuine parts listed in the spare parts list for replacing defective refrigeration components.

• Pipes may only be replaced by copper tubing in compliance with standard NF EN 12735-1.

• Leak detection, in the case of pressure testing:

- Never use oxygen or dry air, as the risk of fire or explosion is present.

- Use dehydrated nitrogen or a nitrogen and refrigerant mix indicated on the manufacturer's plate.

- For units equipped with pressure gauges, the test pressure must not exceed the gauges' maximum allowable pressure

rating.

• All part replacement with other than genuine parts, all modifications of the refrigerating circuit, all replacement of refrigerant

by a fluid other than that indicated on the manufacturer's plate, all use of the unit outside the application limits defined in the

documentation, shall result in the cancellation of PED EC marking compliance which shall fall under the liability of the

individual who carried out these modifications.

• The technical information, relative to the safety requirements of the various applicable directives, is indicated on the

manufacturer's plate of the unit and mentioned on the 1

st

page of this manual.

8 - WIRING DIAGRAM

A1

Heating control PCB

A2

Indoor unit PCB

CC1

Communication and control module

E1

Water pressostat

F1

Automatic - heater safety thermostat

F2

Manual - heater safety thermostat

J1

Water flow switch

KA1

Heater fault relay

KA2

Water flow relay

KM1

R1 contactor

KM2

R2 contactor

KM3

R3 contactor

KM4

M1 contactor

M1

Water circulator pump

Q1

R1 circuit breaker

Q2

R2 circuit breaker

Q3

R3 circuit breaker

Q4

Control circuit breaker

R1

Support heating element

R2

Support heating element

R3

Support heating element

S1

Water inlet temperature sensor (system)

S2

Water outlet temperature sensor

S3

Outdoor air temperature sensor

S4

Heat pump exchanger temperature sensor (E2)

S5

Liquid line temperature sensor (E1)

S6

Water return temperature sensor (Heat pump) (TA)

TR

Indoor unit board power supply transformer

Symbols of the components

BU

Blue

BK

Black

PK

Pink

RD

Red

WT

White

Colours of the wires

Summary of Contents for HKE 189R5I

Page 1: ...GB INSTALLATION MANUAL Pub Inverter split air to water heat pump Indoor unit HKE 189R5I HKE 259R57I HKE 369R57I HKE 489R57I HKE 609R57I HKE 709R7I HKE 909R7I...

Page 2: ...icking up and moving the indoor and outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminium fins on the air conditioner can cut...

Page 3: ...iating maintenance or servicing on the installation check that its power supply is disconnected and locked out 1 4 USE OF EQUIPMENT This device is designed for heating buildings This appliance is not...

Page 4: ...12 Flow detector 13 Water inlet connection 14 Water outlet connection 15 Filling drainage of the water system 16 Safety valve drain connection 17 Flare gas connector 18 Flare liquid connector 19 Elect...

Page 5: ...t board 12 Transformer 2 1 2 ELECTRICAL BOX Hydraulic filter 3 4 FF for HKE 189R and 259R 1 FF for HKE 369R 489R and 609R 1 1 4 for HKE 709R and 909R Outside temperature sensor Installed in a box with...

Page 6: ...ection 3 4 male 3 4 male 1 male 1 1 4 male 1 1 4 male 3 Water circuit fill drain 1 2 male 1 2 male 1 2 male 1 2 male 1 2 male 4 Safety valve connection and drainage 5 Gas refrigerant connection 1 2 fl...

Page 7: ...the unit remove the retaining screws 1 on each side and 1 on top 1 Slide the cover upward 2 until the bottom edge of the covers is aligned with the lower part of the rear support then pull it towards...

Page 8: ...nected on the 2 zone module thus doing away with the need to install the control unit in zone 1 Wall mounting the unit must not be installed in corners on shelves or behind curtains near sources or he...

Page 9: ...er the value indicated on the unit s identification plate for split systems refer to the installation instructions as the charge must consider the length of the connecting lines 4 In case of leakage d...

Page 10: ...supplied 4 2 3 SAFETY VALVE CONNECTION The unit is equipped with a safety valve that opens if the pressure in the hydraulic system exceeds 3 bar A flexible hose 4 not supplied can be connected to the...

Page 11: ...cable between the indoor unit and the outdoor unit Shielding Screws not supplied Metal clamp not supplied screwed to the terminal strip s support plate Grounding of the cable shielding SPW W706 906 N...

Page 12: ...nstallation is connected Single phase Rsce Three phase Rsce Such that Sc Three phase short circuit power of the network Sc where Unominal nominal voltage between phases Z impedence of the network at t...

Page 13: ...Indoor unit HKE Power supply amperages and cable sizes The sections are given as an indication only They have to be verified and adapted if necessary according to the installation conditions and the s...

Page 14: ...ength 25 meters To be connected to the heating board A1 Note This sensor must be located outside in a location that is representative of the temperature to be measured on a wall facing North North wes...

Page 15: ...NNECTION DIAGRAM Route the control cables on the right side of the board Pass the pilot wire 230 V on the left side of the board 1 2 CN1 230V CN2 CN3 CN4 CN8 CN7 CN6 CN5 3 5 4 3 2 1 4 3 2 1 4 5 3 2 1...

Page 16: ...f the indoor unit 5 ACCESSORIES 5 1 WATER CONNECTION HOSES Length 1 m insulated female 3 4 code 70600054 for HKE 189R and 259R 1 code 70600055 for HKE 369R 489R and 609R 1 1 4 code 70600027 for HKE 70...

Page 17: ...good condition of the apparatus No tools or other foreign objects inside the apparatus 6 2 CONFIGURATION AND PARAMETERISATION 6 2 1 AUTO ADDRESSING OF INDOOR AND OUTDOOR UNITS Set the control unit se...

Page 18: ...ications of the hydraulic circuit force the pump to start as follows installation power ON Set the system control unit to OFF Press and hold the button for 5 seconds The circulator starts The circulat...

Page 19: ...rate Improperly purged water system If the manual thermostat trips correct the fault then reset the thermostat as follows Turn off and lock out the unit Remove the cover The thermostats are located ag...

Page 20: ...lacement with other than genuine parts all modifications of the refrigerating circuit all replacement of refrigerant by a fluid other than that indicated on the manufacturer s plate all use of the uni...

Page 21: ...H2 H3 E1 E2 T T 230V A1 A2 KM2 A1 A2 KM3 A1 A2 KA1 R3 Q4 1 2 3 4 KM3 Q3 Q2 Q1 KM2 PE XA F1 CX6 F2 E1 CX5 4 CX3 2 P BUS CX1 A1 A2 KA2 S1 S2 S3 11 KA1 12 14 J1 11 KA2 12 14 S4 S5 S6 TR A1 M1 1 2 3 4 KM...

Page 22: ...vent freezing of drainage water in cold weather regions t l o b r o h c n a e h t r o f 4 3 2 1 4 1 1 g i F o t r e f e R dimensions 0 1 M s t l o b r o h c n a h t i w t e e f e h t r o h c n a o t e...

Page 23: ...ginning You must ensure that installation complies with all relevant rules and regulations 8 To prevent malfunction of the air conditioner caused by electrical noise care must be taken when wiring as...

Page 24: ...24...

Page 25: ...25...

Page 26: ...26...

Page 27: ...polarenergi no P boks 117 9450 Hamnvik...

Reviews: