Technibel HKE 189R5I Installation Manual And Operating Instructions Download Page 19

18

GB

6.2.2 - MODULE CC1 CONFIGURATION

• The communication and control module manage the circulator and

the communication interface between the system and the generator.

It is equipped with 2 micro-switches, No. 1 and No. 2.

Micro-switch No. 1

:

In “

ON

” position, the circulator starts automatically if the outdoor

temperature is below 0°C to prevent the hydraulic circuit from

freezing. This position is recommended if the outdoor module is

installed in a location exposed to freezing temperatures (not

recommended).

The factory default setting for this micro-switch is “

OFF

”.

Micro-switch No. 2

:

Must be set to

ON

(activates the water flow safety on the

system).

6.2.3 - SYSTEM PARAMETERISATION

• Make sure that the control unit selector is “

OFF

”.

• Check the parameterisation and adapt it accordingly based on the

type of installation.

The parameters are set on the control box (refer to the system's installation manual).

6.3 - ADDITIONAL HYDRAULIC CIRCUIT VERIFICATIONS

6.3.1 - FORCED CIRCULATOR OPERATION

• In order to conduct the final verifications of the hydraulic circuit, force

the pump to start as follows (installation power ON):

- Set the system control unit to “

OFF

”.

- Press and hold the

button for 5 seconds.

The circulator starts.

The circulator indicator light

flashes.

- Check that the “

H

2

O

” flow indicator is illuminated.

6.3.2 - VERIFICATIONS

• Purging of circuits.

• Hydraulic pressure (2 bar).

• Water flowrate: the unit is equipped with 1/4 SAE pressure taps at the circulator inlet and outlet (see paragraph 2.1.1),

so that the pressure loss can be measured using a hydraulic pressure gauge. Use the circulator curves below to

determine the water flow rate.

In order for the apparatus to work properly, the nominal flow rate must be respected.

6.3.3 - CIRCULATOR CURVES

Micro-switches

No. 1 and No. 2

0

10

20

30

40

50

60

70

80

90

1

1.5

2

2.5

2.8

HKE 369R

1.8

HKE 259R

1.4

HKE 189R

0.9

HKE 489R

2.3

HKE 609R

2.7

HKE 189R / 259R / 369R / 489R / 609R

Circulator SXM 32-55

Water flowrate (m

3

/h)

Manometric

delivery

head

(kPa)

of

the

circulator

Speed 1

Speed 2

Speed 3

0

10

20

30

40

50

60

70

80

90

100

110

120

2

2.5

4

4.5

3

3.5

HKE 709R

3.4

HKE 909R

4.1

HKE 709R / 909R

Circulator SXM 32-80 OEM

Water flowrate (m

3

/h)

Manometric

delivery

head

(kPa)

of

the

circulator

Speed 1

Speed 2

Speed 3

19

GB

7 - MAINTENANCE INSTRUCTIONS

7.1 - GENERAL MAINTENANCE

All equipment must be properly maintained in order to provide optimum performance over time. Faulty maintenance can result in

the cancellation of the product guaranty. Depending on the products, maintenance operations consist in the cleaning of filters (air,

water), internal and external exchangers, casings, and the cleaning and protection of condensate tanks. Treating odours and the

disinfection of room surfaces and volumes also contributes to the cleanliness of the air breathed by users.

Carry out the following operations at least once a year

(the frequency depends on the installation and operating conditions):

- check for leaks on the refrigerating circuit (according to the order of 7th May 2007).

- check for traces of corrosion or oil stains around the refrigerating components,

- inspect the composition and the condition of the coolant and check that it does not contain traces of refrigerating fluid,

- cleaning the exchangers,

- checking the wear parts,

- checking the operating instructions and points,

- check the safety devices,

- de-dusting the electrical equipment cabinet,

- checking that the electrical connections are secure,

- checking the earth connection,

- check the hydraulic circuit (clean the filter, water quality, purge, flowrate, pressure, etc.).

7.2 - HEATER SAFETY

• The unit's heater is equipped with an automatic-reset and a manual-reset safety thermostat.

• These thermostats trip in case of excessive temperature on the heater wall.

• Possible causes:

- Excessively low or inexistent water flowrate.

- Improperly purged water system.

• If the manual thermostat trips, correct the fault then reset the thermostat as follows:

-

Turn off and lock out the unit

.

- Remove the cover.

- The thermostats are located against the heater partition, on the front (see paragraph 2.1.1).

- Press the button in the centre of the manual thermostat.

7.3 - PROTECTION OF HEATER CIRCUITS

• The heater features three heating elements each supplied with 230 V between phases and neutral. Each of these circuits

are protected by a modular circuit breaker (

Q1, Q2, Q3

) located inside the electrical box.

7.4 - CONTROL CIRCUIT PROTECTION

• The indoor unit's control circuit is protected by a modular circuit breaker

Q4

located next to module

CC1

. It is accessible

through the small window on the right-hand side of the unit (without removing the cover panel).

• Before doing any work on the installation, make sure it is switched off and all power supplies locked out.

• Also check that the capacitors are discharged.

• Any work must be carried out by personnel qualified and authorised to work on this type of machine.

• Prior to all maintenance and servicing on the refrigerating circuit, one must first shut down the unit then wait a

few minutes before installing temperature or pressure sensors. Certain equipment, such as the compressor and

piping, may reach temperatures above 100°C and high pressures may lead to serious burns.

IMPORTANT NOTE

6.3.4 - SHUTDOWN FORCED CIRCULATOR OPERATION

• Press and hold the

button for 5 seconds.

The circulator stops.

The circulator indicator light

and the “

H

2

O

” flow rate light do out.

6.4 - OPERATION

• Installation power is ON.

• Start the system in the desired operating mode using the control box button (consult the system control manual and the

control box user's guide).

Summary of Contents for HKE 189R5I

Page 1: ...GB INSTALLATION MANUAL Pub Inverter split air to water heat pump Indoor unit HKE 189R5I HKE 259R57I HKE 369R57I HKE 489R57I HKE 609R57I HKE 709R7I HKE 909R7I...

Page 2: ...icking up and moving the indoor and outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminium fins on the air conditioner can cut...

Page 3: ...iating maintenance or servicing on the installation check that its power supply is disconnected and locked out 1 4 USE OF EQUIPMENT This device is designed for heating buildings This appliance is not...

Page 4: ...12 Flow detector 13 Water inlet connection 14 Water outlet connection 15 Filling drainage of the water system 16 Safety valve drain connection 17 Flare gas connector 18 Flare liquid connector 19 Elect...

Page 5: ...t board 12 Transformer 2 1 2 ELECTRICAL BOX Hydraulic filter 3 4 FF for HKE 189R and 259R 1 FF for HKE 369R 489R and 609R 1 1 4 for HKE 709R and 909R Outside temperature sensor Installed in a box with...

Page 6: ...ection 3 4 male 3 4 male 1 male 1 1 4 male 1 1 4 male 3 Water circuit fill drain 1 2 male 1 2 male 1 2 male 1 2 male 1 2 male 4 Safety valve connection and drainage 5 Gas refrigerant connection 1 2 fl...

Page 7: ...the unit remove the retaining screws 1 on each side and 1 on top 1 Slide the cover upward 2 until the bottom edge of the covers is aligned with the lower part of the rear support then pull it towards...

Page 8: ...nected on the 2 zone module thus doing away with the need to install the control unit in zone 1 Wall mounting the unit must not be installed in corners on shelves or behind curtains near sources or he...

Page 9: ...er the value indicated on the unit s identification plate for split systems refer to the installation instructions as the charge must consider the length of the connecting lines 4 In case of leakage d...

Page 10: ...supplied 4 2 3 SAFETY VALVE CONNECTION The unit is equipped with a safety valve that opens if the pressure in the hydraulic system exceeds 3 bar A flexible hose 4 not supplied can be connected to the...

Page 11: ...cable between the indoor unit and the outdoor unit Shielding Screws not supplied Metal clamp not supplied screwed to the terminal strip s support plate Grounding of the cable shielding SPW W706 906 N...

Page 12: ...nstallation is connected Single phase Rsce Three phase Rsce Such that Sc Three phase short circuit power of the network Sc where Unominal nominal voltage between phases Z impedence of the network at t...

Page 13: ...Indoor unit HKE Power supply amperages and cable sizes The sections are given as an indication only They have to be verified and adapted if necessary according to the installation conditions and the s...

Page 14: ...ength 25 meters To be connected to the heating board A1 Note This sensor must be located outside in a location that is representative of the temperature to be measured on a wall facing North North wes...

Page 15: ...NNECTION DIAGRAM Route the control cables on the right side of the board Pass the pilot wire 230 V on the left side of the board 1 2 CN1 230V CN2 CN3 CN4 CN8 CN7 CN6 CN5 3 5 4 3 2 1 4 3 2 1 4 5 3 2 1...

Page 16: ...f the indoor unit 5 ACCESSORIES 5 1 WATER CONNECTION HOSES Length 1 m insulated female 3 4 code 70600054 for HKE 189R and 259R 1 code 70600055 for HKE 369R 489R and 609R 1 1 4 code 70600027 for HKE 70...

Page 17: ...good condition of the apparatus No tools or other foreign objects inside the apparatus 6 2 CONFIGURATION AND PARAMETERISATION 6 2 1 AUTO ADDRESSING OF INDOOR AND OUTDOOR UNITS Set the control unit se...

Page 18: ...ications of the hydraulic circuit force the pump to start as follows installation power ON Set the system control unit to OFF Press and hold the button for 5 seconds The circulator starts The circulat...

Page 19: ...rate Improperly purged water system If the manual thermostat trips correct the fault then reset the thermostat as follows Turn off and lock out the unit Remove the cover The thermostats are located ag...

Page 20: ...lacement with other than genuine parts all modifications of the refrigerating circuit all replacement of refrigerant by a fluid other than that indicated on the manufacturer s plate all use of the uni...

Page 21: ...H2 H3 E1 E2 T T 230V A1 A2 KM2 A1 A2 KM3 A1 A2 KA1 R3 Q4 1 2 3 4 KM3 Q3 Q2 Q1 KM2 PE XA F1 CX6 F2 E1 CX5 4 CX3 2 P BUS CX1 A1 A2 KA2 S1 S2 S3 11 KA1 12 14 J1 11 KA2 12 14 S4 S5 S6 TR A1 M1 1 2 3 4 KM...

Page 22: ...vent freezing of drainage water in cold weather regions t l o b r o h c n a e h t r o f 4 3 2 1 4 1 1 g i F o t r e f e R dimensions 0 1 M s t l o b r o h c n a h t i w t e e f e h t r o h c n a o t e...

Page 23: ...ginning You must ensure that installation complies with all relevant rules and regulations 8 To prevent malfunction of the air conditioner caused by electrical noise care must be taken when wiring as...

Page 24: ...24...

Page 25: ...25...

Page 26: ...26...

Page 27: ...polarenergi no P boks 117 9450 Hamnvik...

Reviews: