Explanation:
The “Ice Forming Detection” will be done by two algorithms –
1. In Dynamic Temp Detection, the ice formation will be detected by
(i) Compare the OCT with a Deicing Dynamic Temperature Threshold, and
(ii) Detect the drop in ICT which accompany the ice formation.
2. The Static Temp Detection will be done by comparing the OCT with a Deicing Static Temperature
Threshold.
The Deicing Data Record is used to determine the time delay between two deicing cycles. In general, the
time delay will be increased if the last deicing cycle can be completed quickly.
TLD > TST
AND
SCT > SCD
DDT = OCT - TempD
DTF = 1
IFAN/OFAN
speed change
Reset SCT cnt to 0
DTF = 0
DDT and DTF information
to main algorithm
Reset TLD cnt to 0
DTF = 0
Yes
Yes
No
Yes
No
1st COMP start,
OR deice complete
No
27