CWX6B5XAB
Power source
Performance
Input
kW
Running Amps
A
Total cooling capacity (1)
High/Med./Low
kW
Sensible cooling capacity (1)
High/Med./Low
kW
Heating capacity (2)
High/Med./Low
kW
Air circulation
High/Med./Low
m³/h
Features
Controls/Temperature controls
Control unit
Timer
Fan speed
Airflow direction
Water capacity in cooling
High/Med./Low
l/h
Pressure drop on water in cooling (1)
High/Med./Low
kPa
Pressure drop on water in heating (2)
High
kPa
Air Filter
Power noise level
High/Med./Low
dB-A
Water tubing connections
Air clean filter
3-Way valve + By-pass (1/2 gas male, KVS 1,6, 230 NC)
Dimensions & Weight
Dimensions (include panel) Height
mm
Width
mm
Depth
mm
Package dimensions Unit
Height
mm
Width
mm
Depth
mm
Volume
m3
Ceiling panel
Height
mm
Width
mm
Depth
mm
Volume
m3
Weight (include panel) Net
kg
Shipping
kg
Ceiling panel
Net
kg
Shipping
kg
DATA SUBJECT TO CHANGE WITHOUT NOTICE
(1) Air inlet 27°C (D.B.) / 19°C (W.B.); Water inlet 7°C; Water outlet 12°C
(2) Air inlet 20°C; Water inlet 50°C (same water capacity as in conditions (1))
OPERATION LIMITS
Min. water inlet temperature 4°C
Min. air recirculation temperature 5°C
Max. water inlet temperature 60°C
Max. air recirculation temperature 32°C
Max. operating pressure of hydraulic circuit 16 bar
8
0,1
22
26
6
110
965
965
Optional
338
0,238
840
860
860
320
880
30/19/14
30,0
51/44/40
1/2" gas female
Washable, polypropylene, class HB (UL94)
Optional
230 V - 50 Hz
6,0/5,0/4,20
4,70/3,80/3,20
7,70/6,40/5,40
1300/1060/850
0,115
0,5
Microprocessor/ I.C. thermostat
Wireless remote control unit
1030/860/720
ON/OFF 24 hours
3 and Auto
Auto (Remote control)
5