![Technibel CHGV 50 Technical Instructions Download Page 4](http://html1.mh-extra.com/html/technibel/chgv-50/chgv-50_technical-instructions_1067644004.webp)
4
3 - TECHNICAL CHARACTERISTICS
CHGV 50
CHGV 64
CHGV 72
CHGV 80
kW
47.60
62
67
78
kW
20.60
26.40
28.80
29.40
( E E R )
2.31
2.35
2.33
2.65
kW
25
32
36
36.6
A
42.80
56.30
60.40
64.80
A
38.70
47.70
54
55.50
A
170
185
225
225
mm
2
16
16
25
25
m
3
/ h
8.21
10.66
11.52
13.43
L / s
2.28
2.96
3.20
3.73
k P a
220
160
180
90
Electrical supply cable section
Nominal water flow
Available pressure
Model
Heating capacity
Nominal power consumption *
Effictuiveness heating *
Rated total input amperage
Total Max. power consumption **
Total Max. current consumption **
Starting current
(*)
Gross value without hydraulic pump.
(**)
In the operating range.
•
Power supply:
400V (±10%) / 3 Ph + N Earth / 50Hz
•
Nominal operating conditions:
- water inlet temperature
: + 12°C
- water outlet temperature
: +
7°C
- outdoor dry bulb temperature (dry) : + 35°C
•
Operating limits (pure water):
- temperature of inlet air to condenser : - 10°C to + 45°C
- water outlet temperature
: + 4°C to + 20°C
•
Water system pressure
: 1.5 to 3 bar.
Consult us for any special climatic conditions departing significantly from the nominal conditions.