9
(*)
Weight for model with pump and tank.
(**) If the water volume of the system is below the minimum, a buffer tank must be installed.
(***) If the water volume of the system is above the maximum, an additional expansion vessel is required.
(****) Starting current accounting for the electronic starter (current limiter).
- Cooling capacity: outside air temperature 35°C, water temperature 12°C - 7°C.
- Heating capacity: outside air temperature 7°C (dry bulb) and 6.2°C (wet bulb) water temperature 40°C - 45°C.
- Sound pressure level measured in compliance with the standards ISO 3741 - ISO 3744 and EN 29614-1
- Sound pressure measured at a distance of 10 metres and 1.5 metres from the ground in free field conditions (fan end).
- The maximum power consumption is the power consumption of the mains power supply required for the unit to operate.
- The maximum input current is the current level at which the internal protective devices of the unit are tripped. It is the maximum
allowable current per unit. This value must never be exceeded and must be used to size the line.
PhrF model
23
27
32
40
46
60
77
85
Power supply
V-Ph-Hz
400-3N-50
Cooling capacity (EN 14511)
kW
19.55
23.68
27.99
34.84
39.46
54.27
69.25
75.41
EER (EN 14511)
2.61
2.83
3.09
2.94
3
2.89
2.88
2.7
Cold power consumption (EN 14511)
kW
7.49
8.38
9.06
11.86
13.14
18.8
24.05
27.93
Heating capacity (EN 14511)
kW
22.57
26.83
30.80
38.67
44.07
59.12
75.67
83.97
COP (EN 14511)
3
3.2
3.24
3.23
3.27
3.11
3.17
3.08
Hot power consumption (EN 14511)
kW
7.52
8.38
9.52
11.97
13.47
18.98
23.87
27.23
Maximum power consumption
kW
13.60
14.50
18.30
21.80
22.40
27
32.30
39.40
Maximum input current
A
21.7
24
28.6
35.2
36.4
48
57
69
Starting current ****
A
68
103
87
108
108
117
136
154
Number of compressors / circuit
1 / 1
1 / 1
1 / 1
1 / 1
1 / 1
2 / 1
2 / 1
2 / 1
Refrigerant charge
kg
4.23
5.80
7.50
7.80
10.80
12.80
16.30
16.30
Low / high pressure switch
bar
2 / 42
2 / 42
2 / 42
2 / 42
2 / 42
2 / 42
2 / 42
2 / 42
Number of axial fans
4
4
2
2
2
4
4
4
Air flow rate
m
3
/h
9,990
9,307
16,276
16,276
15,776
24,930
24,354
24,354
Water flow rate, cold only
L/h
3,373
4,094
4,833
6,021
6,823
9,202
11,782
12,831
Heat pump water flow rate
L/h
3,949
4,670
5,396
6,756
7,769
10,303
13,244
14,579
Diameter of hydraulic couplings
Inch
1.25
1.25
1.25
1.25
1.25
2
2
2
Water headloss (cold only)
kPa
51
49
40
41
43
56
55
64
Water headloss (heating)
kPa
69
62
49
50
54
60
59
71
Pressure head available (cold only)
kPa
123
116
143
130
119
138
128
114
Pressure head available (heating)
kPa
97
95
128
113
99
130
110
100
Water capacity excluding option
Litres
4
4
5.5
5.5
5.5
7
11
12
Expansion vessel
Litres
5
5
8
8
8
8
8
8
Tank capacity
Litres
50
50
125
125
125
125
125
125
Height
mm
1,300
1,300
1,485
1,485
1,485
1,735
1,735
1,735
Length
mm
1,565
1,565
1,990
1,990
1,990
2,091
2,091
2,091
Depth
mm
600
600
950
950
950
1,183
1,183
1,183
Sound power
dB(A)
71
72
73
73
75
81
81
81
Sound pressure at 10 metres
dB(A)
43
44
45
45
47
53
53
53
Weight packed *
kg
283
295
406
466
495
660
702
792
Net weight (excluding packaging) *
kg
268
280
384
444
473
648
690
780
Minimum water capacity of system **
Litres
105
125
140
175
205
270
345
380
Maximum water capacity of system ***
Litres
145
145
231
231
231
231
231
231