IMPORTANT!
Please read before installation

This air conditioning system meets strict safety and operating
standards.
For the installer or service person, it is important  to install
or service the system so that it operates safely and efficiently.

For safe installation and trouble-free operation,
you must:

• Carefully read this instruction booklet before beginning.
• Follow each installation or repair step exactly as shown.
• Observe all local, state and national electrical  codes.
• Pay close attention to all warning and caution notices

given in this manual.

•The unit must be supplied with a dedicated electrical line.

This symbol refers to a hazard or unsafe practice which
can result in severe personal injury or death.

This symbol refers to a hazard or unsafe practice which
can result in personal injury or product or property damage.

If necessary, get help
These instructions are all you need for most installation
sites and maintenance conditions.
If you require help for a special problem, contact our
sale/service outlet or your certified dealer for additional
instructions.

In case of improper installation
The manufacturer shall in no way be responsible for improper
installation or maintenance service, including failure to follow
the instructions in this document.

SPECIAL PRECAUTIONS

• During installation, connect before the refrigerant system

and then the wiring one; proceed in the reverse orden
when removing the units.

When wiring

ELECTRICAL SHOCK CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH. ONLY A
QUALIFIED, EXPERIENCED ELECTRICIANS
SHOULD ATTEMPT TO WIRE THIS SYSTEM.

• Do not supply power to the unit until all wiring and tubing

are completed or reconnected and checked, to ensure
the grounding.

• Highly dangerous electrical voltages are used in this

system. Carefully refer to the wiring diagram and these
instructions when wiring.
Improper connections and inadequate grounding can
cause accidental injury and death.

• Ground the unit following local electrical codes.
• The Yellow/Green wire cannot be used for any connection

different from the ground connection.

• Connect all wiring tightly. Loose wiring may cause

overheating at connection points and a possible fire
hazard.

• Do not allow wiring to touch the refrigerant tubing,

compressor, or any moving parts of the fan.

• Do not use multi-core cable when wiring the power supply

and control lines. Use separate cables for each type of line.

When transporting
Be careful when picking up and moving the indoor and
outdoor units. Get a partner to help, and bend your knees
when lifting to reduce strain on your back. Sharp edges or
thin aluminium fins on the air conditioner can cut your fingers.

When installing...
... In a ceiling or wall
Make sure the ceiling/wall is strong enough to hold the unit-
weight. It may be necessary to build a strong wooden or
metal frame to provide added support.

... In a room
Properly insulate any tubing run inside a room to prevent
"sweating", which can cause dripping and water damage to
walls and floors.

... In moist or uneven locations
Use a raised concrete base to provide a solid level
foundation for the outdoor unit.
This prevents damage and abnormal vibrations.

... In area with strong winds
Securely anchor the outdoor unit down with bolts and a
metal frame. Provide a suitable air baffle.

... In a snowy area (for heat pump-type systems)
Install the outdoor unit on a raised platform that is higher than
drifting snow. Provide snow vents.

When connecting refrigerant tubing
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of

the flare and union tubes before connecting them;  screw
by hand and  then tighten the nut with a torque wrench
for a leak-free connection.

• Check carefully for leaks before starting the test run.

NOTE:
Depending on the system type, liquid and gas lines may
be either narrow or wide. Therefore, to avoid confusion, the
refrigerant tubing for your particular model is specified as
narrow tube for liquid, wide tube for gas.

When servicing
• Turn the power OFF at the main power board  before

opening the unit to check or repair electrical parts and
wiring.

• Keep your fingers and clothing away from any moving

parts.

• Clean up the site after the work, remembering to check

that no metal scraps or bits of wiring have been left inside
the unit being serviced.

• Ventilate the room during the installation or testing the

refrigeration system; make sure that, after the installation,
no gas leaks are present, because this could produce
toxic gas and dangerous if in contact with flames or heat-
sources.

WARNING

CAUTION

WARNING

EG

Summary of Contents for CA10FICR5

Page 1: ...ked as it satisfies Directives Low voltage no 2006 95 EC Standard EN60335 2 40 2003 incl Corr 2006 A11 2004 A12 2005 A13 2012 A1 2006 A2 2009 con EN 60335 1 2002 A11 2004 A1 2004 A12 2006 A2 2006 A13...

Page 2: ...olt pitch 820 Ceiling opening 820 Ceiling opening 377 Panel center 757 Suspention bolt pitch 368 25 9 X Air intake grille Air outlet Refrigerant liquid line use the tube connector Refrigerant gas line...

Page 3: ...ing to touch the refrigerant tubing compressor or any moving parts of the fan Do not use multi core cable when wiring the power supply and control lines Use separate cables for each type of line When...

Page 4: ...ation and maintenance as well as unrestricted air flow around the unit Installation site selection Outdoor unit AVOID Heat sources exhaust fans Direct sunlight Damp humid or uneven locations To make h...

Page 5: ...esto prodotto marcato in quanto conforme alle Direttive Bassa Tensione n 2006 95 CE Standard EN60335 2 40 2003 incl Corr 2006 A11 2004 A12 2005 A13 2012 A1 2006 A2 2009 with EN 60335 1 2002 A11 2004 A...

Page 6: ...lt pitch 820 Ceiling opening 820 Ceiling opening 377 Panel center 757 Suspention bolt pitch 368 25 9 X Air intake grille Air outlet Refrigerant liquid line use the tube connector Refrigerant gas line...

Page 7: ...on i tubi refrigeranti il compressore o le parti mobili del ventilatore Nel collegare l alimentazione e le linee di controllo non usare cavi a pi conduttori Usare cavi separati per ciascun tipo di lin...

Page 8: ...zione e spazi minimi di manutenzione intorno all unit Scelta del luogo di installazione unit esterna EVITARE La vicinanza a fonti di calore o ad aree interessate da espulsioni di aria calda L esposizi...

Page 9: ...st marqu puisque il est conforme aux Directives Basse Tension n 2006 95 CE Standard EN60335 2 40 2003 incl Corr 2006 A11 2004 A12 2005 A13 2012 A1 2006 A2 2009 with EN 60335 1 2002 A11 2004 A1 2004 A1...

Page 10: ...olt pitch 820 Ceiling opening 820 Ceiling opening 377 Panel center 757 Suspention bolt pitch 368 25 9 X Air intake grille Air outlet Refrigerant liquid line use the tube connector Refrigerant gas line...

Page 11: ...endie Il ne faut en aucun cas laisser les c bles toucher la tuyauterie du r frig rant le compresseur ou toute pi ce mobile N utilisez pas de c ble multiconducteur pour le c blage des lignes d alimenta...

Page 12: ...permettre aussi bien un bon fonctionnement qu une maintenance ais e ainsi qu une circulation d air libre autour de l appareil Choix de l emplacement d installation Appareil ext rieur EVITEZ Les sourc...

Page 13: ...Produkt ist mit Zeichen gekennzeichnet weil es den folgenden Richtlinien entspricht Niederspannungsrichtilinie 2006 95 EG Standard EN60335 2 40 2003 incl Corr 2006 A11 2004 A12 2005 A13 2012 A1 2006 A...

Page 14: ...ch 820 Ceiling opening 820 Ceiling opening 377 Panel center 757 Suspention bolt pitch 368 25 9 X Air intake grille Air outlet Refrigerant liquid line use the tube connector Refrigerant gas line D 12 7...

Page 15: ...ittelrohre den Kompressor oder die beweglichen Teile des Ventilators ber hrt Verwenden Sie keine Mehraderkabel f r die Verdrahtung der Stromversorgung und Steuerleitungen Benutzen Sie separate Kabel f...

Page 16: ...tz sowohl f r Betrieb und Wartung als auch f r ungehinderten Luftstrom vorhanden ist Wahl des Installationsortes Au enger t VERMEIDEN SIE W rmequellen Sauggebl se Direkte Sonneneinstrahlung Feuchte lu...

Page 17: ...ONFORMIDAD Este Producto est marcado porque responde a las Directivas Baja Tensi n n 2006 95 CE Standard EN60335 2 40 2003 incl Corr 2006 A11 2004 A12 2005 A13 2012 A1 2006 A2 2009 with EN 60335 1 200...

Page 18: ...olt pitch 820 Ceiling opening 820 Ceiling opening 377 Panel center 757 Suspention bolt pitch 368 25 9 X Air intake grille Air outlet Refrigerant liquid line use the tube connector Refrigerant gas line...

Page 19: ...n contacte con el tubo de refrigerante compresor o parte m viles del ventilador No use cable coaxial para cablear las l neas de potencia y las de control Use cables separados para cada una de las l n...

Page 20: ...acios m nimos necesarios para la manutenci n D nde instalar la unidad exterior EVITAR Zonas expuestas a fuentes de calor y corrientes de aire caliente Exposici n directa al sol Zonas h medas o con rie...

Page 21: ...ato dei raccordi nella posizione pi appropriata per i collegamenti Collocare in sede l unit utilizzando dadi e rondelle per fissarla sulle aste di sospensione figura 03 Verificare che l unit sia a liv...

Page 22: ...nsi n 1 y el agujero a realizar en el falso techo figura 01 Para las varillas de suspensi n utilizar varilla roscada de 8 o 10 mm Ver la cotas en la tabla mostrada al lado figura 02 Colocar en su siti...

Page 23: ...raccorder un tube en PVC rigide 4 diam tre interne 18 mm bien isol et fixez le l unit au moyen d un tube flexible 2 en PVC ou en gomme fixez avec colliers d installation 3 Le branchement doit tre bie...

Page 24: ...unit au moment de brancher la ligne de drainage La ligne ne doit pas rester suspendue sans support Serrez la contre un mur une structure ou autre support 6 le plus pr s possible de l unit N installez...

Page 25: ...renouvellement de l air Le moteur de ventilateur suppl mentaire pour la prise d air ext rieure doit poss der une alimentation lectrique distincte et pouvoir tre command l aide d un interrupteur bipola...

Page 26: ...sicher da der Deckel richtig eingepa t ist ziehen Sie dann die Schrauben an Colocar el cable el ctrico y concitarlo al tablero de bornes v ase esquema de conexiones Bloquear el cable a la abrazadera C...

Page 27: ...cho C I EG F D E Use rawl plug suitable to the ceiling consistence and four M10 threaded bars of suitable lenght not supplied Reperire sul mercato dei tasselli adatti alla consistenza del soffitto e q...

Page 28: ...u faux plafond pour l entretien Abnehmbare Tafel zum Wartungszweck vorbereiten Colocar un panel amovible de modo que facilite las operaciones de mantenimiento H The unit is supplied of PVC hose from t...

Page 29: ...Predisporre il cavo elettrico per il collegamento alla morsettiera e collegarlo Vedere schema per l allacciamento Bloccare il cavo al fissacavo Accertarsi che i terminali dei cavi elettrici siano ben...

Page 30: ...roblemas en el funcionamiento del acondicionador con riesgo le incendio Al cerrar la caja de los componentes el ctricos controlar que los cables no sobresalgar y que no se queden atrapados entre la ta...

Page 31: ...mit 5 Liter Wasser auff llen Die Einheit in Gang setzen in dem man den einwandfreien Betrieb der Kondensatwasserbeseitigungspumpe berpr f Remover el filtro del aire y verter en el interior de la cubet...

Page 32: ...upteur bipolaire ON OFF avec fusible de s curit Pour viter des probl mes de fonctionnement et bruit l arriv e d air neuf doit repr senter peu pr s 10 du d bit d air total Ouvrir le trous pr coup q fix...

Page 33: ...una distanza di apertura dei contatti che consenta la disconnessione completa nelle condizioni della categoria di sovratensione III Le dispositif de sectionnement de la ligne doit avoir une distance...

Page 34: ...nt le conducteur de terre si le c ble d alimentation est tir accidentellement C ble de raccordement B BLINDE C ble lectrique bipolaire blind la section et la longueur du c ble lectrique recommand sont...

Page 35: ...iseur ne pas installer la t l commande aux endroits suivants En plein soleil Derri re un rideau ou tout autre endroit o elle serait cach e A plus de 8 m tres du climatiseur Pr s de la sortie d air du...

Page 36: ...Placer la t l commande dans la position d sir e V rifier que la commande distance peut tre utilis e dans cette position Fixer le support au mur avec deux vis et accrocher la telecommande POSITION AN E...

Page 37: ...Schraubenziehen in die Seitenschlitze auf demselben Deckel hineinsteckt Das Empf ngerkabel nicht in der N he von Starkstromleitungen gleiten lassen weder zusammen mit andere elektrischen Leitungen in...

Page 38: ...lectrique Ne pas fournir d nergie lectrique au syst me ni essayer de mettre en marche l unit avant que les conduites frigorifiques et l installation lectrique ne soient compl t es Wenn vorgesehen den...

Page 39: ...per abilitare il ripristino effettivo delle impostazioni iniziali Al riavvio l unit interna ricomincia a funzionare con le impostazioni di fabbrica Pour remettre z ro les r glages de d faut vous deve...

Page 40: ...significa recuperar todo el gas refrigerante en la Unidad Exterior sin perder la carga del Sistema Se utiliza cuando hay que recolocar el acondicionador y despu s de una reparaci n del circuito de ref...

Page 41: ...a bo te composants lectriques Sortir le pont c bles l vateur de pression Den Deckel der Elektroteiledose entfernen Die Druckerhebungsverbindungsdrahtgruppe herausziehen Remover la tapa de la caja de l...

Page 42: ...r du ventilateur Vitesses du ventilateur disponibles Moyenne Haute Tr s haute M H HH Max pression statique peu pr s 7 mm H Standard Einheit wie geliefert Verf gbare Ventilatorgeschwindigkeiten Niedrig...

Page 43: ...CB soit plac s comme repr sent Einheit A Uberpr fen Sie da der Schalter SW1 PCB wie in Abbildung eingestellt ist Unidad A Controlar que el interruptor SW1 PCB est configurados como en figura I EG F D...

Page 44: ...nt appuyer en m me temps sur les boutons FAN et I FEEL pendant plus de 5 secondes et les rel cher en dirigent la t l commande vers l unit int rieure Si les r glages sont corrects il y aura un signal a...

Page 45: ...ATION est allum Apr s 3 minutes de fonctionnement Si le r glage est correcte l unit change en REFROIDISSEMENT et s arr te Temp rature 32 C Le syst me est pr t pour le fonctionnement Si il y a une erre...

Page 46: ...commencera fonctionner avec le nouveau adresse l Schalten Sie den Strom der Inneneinheit ab l Entfernen Sie die Batterien von die Fernbedienung l Stellen Sie die Schalter auf sehen Sie die Tabelle l...

Page 47: ...FF 4 OFF 5 ON 6 ON SW3 1 ON 2 OFF 3 1 OFF 2 ON 3 OFF 4 OFF 5 ON 6 ON SW3 1 OFF 2 ON 4 1 ON 2 ON 3 OFF 4 OFF 5 ON 6 ON SW3 1 ON 2 ON REMOTE CONTROL UNIT TELECOMANDO TELECOMMANDE FERNBEDIENUNG MANDO A D...

Page 48: ...S A C Printed in italy Z I Route d partementale 28 01600 Reyrieux France T l 33 4 74 00 92 92 Fax 33 4 74 00 42 00 Technibel is a trademark of NIBE ENERGY SYSTEM FRANCE...

Reviews: