7) Forcede mode
means of the OPERATION button on the front panel. The operation modes can be selected
pressing the button in a cyclic way (OFF
Ö
COOL
Ö
HEAT
Ö
OFF…). The settings are:
COOLING mode
SET POINT temperature = 25°C
FAN SPEED = HIGH
HEATING mode
SET POINT temperature = 21°C
FAN SPEED = HIGH
See also paragraph 15 for additional details.
8) Protection operations in Cool and Dry Mode
8.1 Freeze-up
This protection prevents ice formation on the indoor coil heat exchanger. The protection is activated by
the indoor coil temperature (ICT sensor) and only after 6 minutes of compressor operation. This
protection acts in 2 levels:
LEVEL 1
INDOOR FAN SPEED: ANY (as selected from remote controller)
COMPRESSOR: ON
OUTDOOR FAN: cycling (30 seconds ON
B
30 seconds OFF).
DRAIN PUMP: operates according to paragraph 17
LEVEL 2
INDOOR FAN SPEED: ANY (as selected from remote controller)
COMPRESSOR: OFF for at least 6 minutes and until ICT
≥
8°C
OUTDOOR FAN: OFF for at least 6 minutes and until ICT
≥
8°C
DRAIN PUMP: always ON ( stops when exiting the protection)
The system exit this protection routine when ICT temperature rises above 8°C.
18