background image

13

2)  Using Outdoor Unit's Gas (Units A & B)

a)  Evacuation

(1) Connect a vacuum pump and a manifold valve

(with pressure gauges) to the service port on the
wide tube service valve for unit A. (Figs. 8-3 )

(2) With the "Lo" knob of the manifold valve open,

run the vacuum pump.  The operation time for
the vacuum pump varies with tubing length and
capacity of the pump.  The following table
shows the amount of time for evacuation:

Note: The rquired time in the above table is

calculated based on the assumption that the
ideal (or target) vacuum condition is around
10 mmHg abs.

(3) With the vacuum pump still running, close the

"Lo"  knob of the manifold valve.  Then stop the
vacuum pump.

Be sure to use a manifold
valve for air purging.  If it is
not available, use a stop valve
for this purpose.  The "Hi"
knob of the manifold valve
must always be kept closed.

CAUTION

!

Required time for evacuation when capacity of 

100 liter/h vacuum pump is  used

If tubing length is 

If tubing length is 

less than 10 m

longer than 10 m

10 min. or more

15 min. or more

L

H

Fig. 8-3

Indoor units

Outdoor unit

Vacuum pump

Unit A

Unit B

Unit C

Manifold
valve

Unit
A

Unit
B

Unit

C

Summary of Contents for DKR8585C

Page 1: ...0M3C5TA MCAV92C5TA CAV92C5TA x 4 DKR8585C For details of its installation refer to the instruction manual of DKR8585C e e h h h h h h e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e e...

Page 2: ...ting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing ln a Ceiling Wall or Floor Make sure the ceiling wall floor is strong e...

Page 3: ...ing length of C 25 g m is longer than 7 5 m No additional charge of compressor oil is required 2 English 1 Selection of Installation Site Maximum Allowable Tubing Length L and Elevation Difference H F...

Page 4: ...e blocks or slab at least 10 cm high above ground level Fig 2 3 The unit must be level and be anchored securely to its base with anchor bolts or the like An unsteady foundation will cause abnormal noi...

Page 5: ...o provide a minimum space of 50 cm between the air discharge outlet and a nearby obstacle The air discharge faces a sidewalk and hot air will be directed toward passersby Figs 2 4 and 2 5 4 English Fi...

Page 6: ...ust be grounded Units A B MCAV92 CAV92 Unit C MCAV KPAV180 5 WARNING AWG American Wire Gauge A Power Supply Line Length m B Inter Line Length m Fuse or Cross Sectional Area Circuit Capacity 3 5 mm2 5...

Page 7: ...2 Air conditioner will not operate Problem 3 Compressor will not start only indoor unit will operate English CAUTION 1 2 4 A 4 5 6 2 4 5 1 8 2 1 Grounding line or or Indoor unit Outdoor unit 1 2 4 B...

Page 8: ...the solid wire to form a loop suitable for the terminal screw 4 Shape the loop wire properly place it on the terminal plate and fix it securely with the removed terminal screw using a screwdriver For...

Page 9: ...be sure to mount it on the copper tube d Make a flare at the end of copper tube with a flare tool Fig 4 3 Use RIGID or equivalent A good flare should have the following characteristics inside surface...

Page 10: ...en up the union connection portion of the indoor unit using a double spanner Fig 7 1 Connect both the wide and narrow tubes of the outdoor unit Fig 7 2 When using the torque wrench be sure to apply th...

Page 11: ...ing nitrogen gas or outdoor unit s gas according to the installation site conditions The respective procedures are described below 1 Using Nitrogen Gas Unit A a Leak test 1 With the service valves on...

Page 12: ...m pump The operation time for the vacuum pump varies with tubing length and capacity of the pump The following table shows the amount of time for evacuation Note The rquired time in the above table is...

Page 13: ...onnet and flare nut on the wide tube service port and fasten the flare nut securely with an adjustable wrench or box wrench Next mount the valve cap and tighten it with a torque wrench the cap needs t...

Page 14: ...ated based on the assumption that the ideal or target vacuum condition is around 10 mmHg abs 3 With the vacuum pump still running close the Lo knob of the manifold valve Then stop the vacuum pump Be s...

Page 15: ...connected to the wide tube service port Then remove the hose 4 Replace the bonnet and flare nut on the wide tube service port and fasten the flare nut securely with an adjustable wrench or box wrench...

Page 16: ...shifts into cooling operation and cool air will start to be felt Cooling operation with the switch at the TEST position is unaffected by the room temperature 4 After stopping the test run turn the op...

Page 17: ...down in cooling operation 1 Connect a low pressure gauge manifold hose to the charge port on the wide tube service valve 2 Lower the stem of the wide tube service valve to position c and purge the air...

Page 18: ...ut prior notice Per garantire un costante miglioramento dei nostri prodotti ci riserviamo di modificarli senza preavviso Par souci d am lioration constante nos produits peuvent tre modifi s sans pr av...

Reviews: