10. TROUBLESHOOTING
CHECK BEFORE AND AFTER «TROUBLESHOOTING»
(A)
Check power supply wiring.
• Check the power supply wires are correctly connected.
(B)
Check power supply.
• Check that voltage is in specified range (±10% of the rating).
• Check that power is being supplied.
• WARNING: If the following troubleshooting must be done with power supplied,
be careful not to touch any uninsulated live part that can cause ELECTRIC SHOCK.
A CIRCUIT BREAKER TRIPS OR FUSE BLOWS.
• When circuit breaker is set to ON, it trips in a few moments. Resetting is not possible.
• Measure insulation resistance. There is a possibility of ground fault.
If resistance value is 1 Mohm or less, insulation is defective.
B CIRCUIT BREAKER TRIPS IN SEVERAL MINUTES AFTER TURNING AIR CONDITIONER ON.
1 • There is the possibility of short circuit.
18
Summary of Contents for 39.7718.916
Page 8: ...3 REFRIGERANT FLOW DATA 3 1 Refrigerant Flow Diagram 8...
Page 21: ...E SOME PARTS OF THE AIR CONDITIONER DO NOT OPERATE 21...
Page 22: ...F AIR CONDITIONER OPERATES BUT ABNORMALITIES ARE OBSERVED 22...
Page 23: ...23...
Page 24: ...G POOR COOLING OR HEATING 24...
Page 25: ...H EXCESSIVE COOLING OR HEATING I A SENSOR IS DEFECTIVE 25...
Page 26: ...11 CHECKING ELECTRICAL COMPONENTS 26...
Page 27: ...27...