OUTDOOR UNIT:
GRV122R5TA-
COOLING
Indoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
performance at
Rating conditions
Running Amps.
A
0,13
0,28
5,79
6,2
Power input
Kw
0,031
0,063
1,206
1,300
Full load conditions
Running Amps.
A
0,13
0,28
6,79
7,2
Power input
Kw
0,031
0,063
1,426
1,520
Rating Conditions:
Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions: Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
HEATING
Indoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
performance at
Rating conditions
Running Amps.
A
0,13
0,28
6,19
6,6
Power input
Kw
0,031
0,063
1,306
1,400
Full load conditions
Running Amps.
A
0,13
0,28
6,89
7,3
Power input
Kw
0,031
0,063
1,346
1,440
Rating Conditions:
Indoor Air Temperature 20°C D.B.
Outdoor Air Temperature 7°C D.B. / 6°C W.B.
Full Load Conditions: Indoor Air Temperature 27°C D.B.
Outdoor Air Temperature 24°C D.B. / 18°C W.B.
NOTE: Data referred to indoor unit
MCAV122R5TA- model.
For other indoor unit models there could be some differences.
Outdoor unit
230V 1-Phase 50 Hz
Outdoor unit
230V 1-Phase 50 Hz
24