OUTDOOR UNIT:
GRV92R5TA-
COOLING
Indoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
performance at
Rating conditions
Running Amps.
A
0,12
0,28
4,3
4,7
Power input
Kw
0,027
0,063
0,963
1,040
Full load conditions
Running Amps.
A
0,12
0,28
5,1
5,5
Power input
Kw
0,027
0,063
1,140
1,230
Rating Conditions:
Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions: Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
HEATING
Indoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
performance at
Rating conditions
Running Amps.
A
0,12
0,28
4,3
4,7
Power input
Kw
0,027
0,063
0,973
1,050
Full load conditions
Running Amps.
A
0,12
0,28
4,8
5,2
Power input
Kw
0,027
0,063
1,080
1,170
Rating Conditions:
Indoor Air Temperature 20°C D.B.
Outdoor Air Temperature 7°C D.B. / 6°C W.B.
Full Load Conditions: Indoor Air Temperature 27°C D.B.
Outdoor Air Temperature 24°C D.B. / 18°C W.B.
NOTE: Data referred to indoor unit
MCAV92R5TA-
model.
For other indoor unit models there could be some differences.
Outdoor unit
230V 1-Phase 50 Hz
Outdoor unit
230V 1-Phase 50 Hz
23