4) Compressor motor does not operate.
5) Outdoor fan does not operate.
No
Yes
Does compressor motor magnetic
contactor (52C) actuate ?
Replace the compressor
motor magnetic contactor.
Check resistance of compressor
motor winding.
Replace the compressor.
NG
0461_M_I
No
Yes
No
Yes
Is fan motor capacitor normal ?
No
Is there voltage output of
P.C.B. Ass’y for fan motor ?
Yes
Check resistance of fan motor
winding.
NG
Replace the fan motor.
Replace the relays.
Replace the capacitor.
Replace P.C.B. Ass’y
in the outdoor unit.
Are auxiliary relays (1Y, 2Y)
normal ?
0462_M_I
44