4-11 Auto-flap Control (Indoor Unit: 4-Way Air Discharge)
Auto flap can control the air flow in 5 steps.
F2 (The flap returns to the original position after release
of standby mode)
(1) When the unit is stopped, the Auto-flap returns to F5 position.
(2) When the airflow direction is set (an optional setting), the auto and Swing settings will be released. To
return the mode to auto-flap control, change the operation mode.
(3) Once Auto-flap is set, the flap position will be input in the memory.
(4) When the operation mode is changed, the unit starts to search flap position. (if a search action for
sensing flap position is not succeeded in one minute, only the swing is operated.)
Operation mode
Cooling/dehumidifying
Fan
Heating
Standby for heating
Automatic setting
Flap position
F1 - F2 - F3 - Swing
F1 - F2 - F3 - F4 - F5 Swing
F1 - F2 - F3 - F4 - F5 Swing
Optional setting
F2
F2
F4
1328_M_I
F1
F5
60°
Heating F1~F5
Cooling F1~F3
F2
F3
F4
The indoor fan speed is automatically set to L and cannot be adjusted to M or H.
When the set temperature is either 18 or 19°C, the set temperature is considered the same
as 20°C.
B range to select the best
operation mode.
Fig. 20
ROOM TEMP
5 MINUTES
3 MINUTES
AREA
A
B
C
OFF
OFF
OFF
OFF
INDOOR FAN
OUTDOOR FAN
COMPRESSOR
T+2°C (T+1°C)
SET TEMP.
T °C
T-2°C (T-1°C)
L
ON
ON
ON
ON
ON
ON
Body sensor
0449_M_S
24