ST-707 Rotations Control
Any comments concerning the program should be reported to the
boiler's manufacturer.
Each controller should be set individually for personal needs,
depending on the type of fuel used for burning as well as the type of the
boiler. The TECH company shall not be liable for any incorrect settings of
the controller.
II.
Functions of the regulator
This chapter describes the functions of the regulator, the method of
changing the settings as well as navigation in the menu which is made
using the
pulse generator
(knob). The boiler's operational parameters
are displayed on the main screen of the controller. The user selects the
operation mode and a number of settings of the boiler according to their
own needs.
After activation of the controller the name of the manufacturer of
the boiler as well as the version of the program are displayed on the
graphic display. A message with language selection appears after a few
seconds. In this function, the user may change the language version.
II.1. Basic definitions
Ignition
– this cycle begins at the moment of activation in the menu of
the
ignition
function controller and when the choice is approved (the
following message will appear on the display:
"PID: IGNITION"
) and
lasts until the time when the flue gas temperature reaches the value of at
least 60
o
C (preset
ignition threshold
), provided that this temperature
does not fall below this value for 30 seconds (preset
ignition time
).
Operation –
after completion of ignition the regulator switches to the
operation cycle and the following message is shown on the display:
"PID: OPERATION"
. This is the basic functioning condition of the
- 7 -