2
Install the Transformer
Select the location between the studs (16" apart) where
the transformer is to be mounted.
Place the transformer between the studs and fasten it to
the studs through the bracket holes with four #8 or
#10 screws (not provided).
STUD
SCREW
BRACKET
C
O
M
X
4
X
3
X
2
X
1
C
O
M
X
4
X
3
X
2
X
1
Install two low voltage wires from the transformer to
the electrical power feed box to which the power feed
canopy will be attached. Run the proper size wire using
the low voltage wire size table.
LOW VOLTAGE WIRES
Insert one low voltage wire into the secondary terminal
marked "COM" and tighten the screw firmly.
Insert the second low voltage wire to the "X2" tap
terminal (default) and tighten the screw firmly.
Measure the voltage at the primary power line coming
into the transformer. If the voltage is not in the range
of 115 - 120 volt, then pick the proper terminal tap
using the "Terminal Tap Table" to reconnect the second
low voltage wire.
Install drywall.
NOTE:
Other wire sizes that comply with electrical
code can be used, but may result in an increased
voltage drop and reduced lamp intensity.
NOTE:
The THHN wire sizes are for 3% drop in
voltage based on 300 watt loads. Lengths are the
distance from the transformer to the system power
feed connector.
TRANSFORMER
WATTAGE
WIRE SIZE
FOR 5 FT
WIRE SIZE
FOR 6-15 FT
WIRE SIZE
FOR 16-20 FT
WIRE SIZE
FOR 21-40 FT
WIRE SIZE
FOR 40-60 FT
WIRE SIZE
FOR 61-90 FT
300 WATT
#6 GA
#4 GA
#1 GA
#1/0 GA
#3/0 GA
#10 GA
LOW VOLTAGE WIRE SIZE TABLE
Connect the 12 Volt Low Voltage
Wires
PRIMARY POWER
LINE VOLTAGE
105 - 109
TERMINAL TAP TABLE
110 - 114
115 - 120
121 - 125
TERMINAL TAP
TO BE USED
X4
X3
X2
X1
1A
1
2
1
2
3
2
2A
4
5
1
2
3