TECALEMIT TC100D2 Manual Download Page 5

 

 

 

TC100D2-V6 0 MANUAL Apr 08 A4 (reflowed).docx 

 

Page 5 of 6 

APPLICATION

:  

Single Line Progressive 

 

 

 

OP1 

 

- Pump 

 

 

 

IP1 

 

- Cycle switch  

 

 

 

IP2 

 

- Low Level or Remote Test switch 

 

 

 

Single Line Injector with automatic vent valve 

 

 

 

OP1 

 

- Pump 

 

 

 

IP1 

 

- Pressure switch 

 

 

 

IP2 

 

- Low Level or Remote Test switch 

 

 

 

Dual Line with automatic reversing valve

 

 

 

 

OP1 

 

- Pump 

 

 

 

IP1 

 

- Cycle switch 

 

 

 

IP2 

 

- Low Level or Remote Test switch 

 

 

 

Single Line Injector with electric vent valve

 

 

 

 

OP1 

 

- Pump 

 

 

 

OP2 

 

- Electric vent valve  

 

 

 

IP1 

 

- Pressure switch 

 

 

 

IP2 

 

- Low Level or Remote Test switch 

 

OPTION 0  -  (DSW3 switch 5 ON)

 

 
This option modifies the base program to allow

 OP1 pulse interval

 (pulsing option selected via 

DSW2) to be set between 1 - 15 sec using switches 1 - 4.  Selecting OPTION 0 disables the 
DOSAGES feature. 
 

   OPTION 1  -  (DSW3 switch 6 ON)

 

 
This  option  modifies  the  base  program  so  that  the  Pump  On  Time  will 

terminate  on  IP1

 

activation or when the number of IP1 activations (doses) = the number preset on DSW3 (n = 1-
15). 
 

   OPTION 2  -  (DSW3 switch 7 ON)

 

 
This option modifies the base program to use a Remote Test switch input in place of the Low 
Level switch input. The Remote Test switch connected to IP2 mimics the TEST switch on the 
front panel. 
 

   OPTION 3  -  (DSW3 switch 8 ON)

 

 
This option modifies the base program to cancel the FAULT alarm function ie. 

Ignore IP1

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 