APPLICATION
:
Single Line Progressive
OP1
- Pump
IP1
- Cycle switch
IP2
- Low Level or Remote Test switch
Single Line Injector with automatic vent valve
OP1
- Pump
IP1
- Pressure switch
IP2
- Low Level or Remote Test switch
Dual Line with automatic reversing valve
OP1
- Pump
IP1
- Cycle switch
IP2
- Low Level or Remote Test switch
Single Line Injector with electric vent valve
OP1
- Pump
OP2
- Electric vent valve
IP1
- Pressure switch
IP2
- Low Level or Remote Test switch
OPTION 0 - (DSW3 switch 5 ON)
This option modifies the base program to allow
OP1 pulse interval
(pulsing option selected via
DSW2) to be set between 1 - 15 sec using switches 1 - 4. Selecting OPTION 0 disables the
DOSAGES feature.
OPTION 1 - (DSW3 switch 6 ON)
This option modifies the base program so that the Pump On Time will
terminate on IP1
activation or when the number of IP1 activations (doses) = the number preset on DSW3 (n = 1-
15).
OPTION 2 - (DSW3 switch 7 ON)
This option modifies the base program to use a Remote Test switch input in place of the Low
Level switch input. The Remote Test switch connected to IP2 mimics the TEST switch on the
front panel.
OPTION 3 - (DSW3 switch 8 ON)
This option modifies the base program to cancel the FAULT alarm function ie.
Ignore IP1
.