![Teal SMA SUNNY MULTIGATE XT Installation Manual Download Page 21](http://html.mh-extra.com/html/teal/sma-sunny-multigate-xt/sma-sunny-multigate-xt_installation-manual_827806021.webp)
Installation Manual - TEAL PN 1060147 rev 2.5
21
TEAL Electronics
SMA America, LLC
PIC / RID Label for Multigate A
PIC / RID Label for Multigate B
PIC / RID Label for Multigate C
Designed and Manufactured exclusively for SMA by TEAL Electronics
www
.teal.com - 10350 Sorrento V
alley Road, San Diego, CA 92121 - 858-558-9000
Installation Guide for SMA Multigate XT - Model XT3s - TEAL PN 6900007
FRONT VIEW - DEAD FRONT COVER REMOVED
CABLE DUCT
CLIP (x4)
DIN RAIL GROUND TERMINAL
GROUND TERMINAL TO RECESSED RAIL -
TORQUE
TO 5.7 LB-IN -
CUSTOMER CONNECTION POINTS
5-PORT ETHERNET SWITCH MOUNTED ON RECESSED DIN RAIL -
CUSTOMER
CONNECTION POINTS
24V DC POWER SUPPLY FOR ETHERNET SWITCH
DIN RAIL MOUNTING BRACKETS (x2)
POWER SUPPLY INPUT CIRCUIT BREAKER 1-POLE 10A CB
SMA MULTIGATE MODULES (x3)
RECESSED DIN RAIL GROUND TERMINAL
DIN RAIL MOUNTING BRACKETS ELEVATED 4.9" FROM BACK OF ENCLOSURE
GROUND WIRE (x4)
INPUT TERMINAL BLOCKS
TORQUE TO 5.7 LB-IN
CUSTOMER CONNECTION POINTS
OUTPUT TERMINAL BLOCKS
TORQUE TO 11.5 LB-IN
CUSTOMER CONNECTION POINTS
L1 WIRE (x3)
L2 WIRE (x3)
VARIABLE
DEPTH
CORNER
MOUNTING
KIT (x4)
CUSTOMER
GROUND LANDING
OUTPUT CIRCUIT BREAKER 2-POLE 15A CB (x3)
CABLE DUCT (x2)
Inver
ter
Inver
ter
Communication
SUNNY MUL
TI
GA
TE
Grid
L1 L2
L1 L2
B
Inver
ter
Inver
ter
Communication
SUNNY MUL
TI
GA
TE
Grid
L1 L2
L1 L2
A
Inver
ter
Inver
ter
Communication
SUNNY MUL
TIGA
TE
Grid
L1 L2
L1 L2
C
INPUTS
Field Connections
L1|L2|
A
L1|L2|
B
L1|L2|
C
INPUTS
A
L1|L2|
C
L1|L2|
L1
A | B | C | | PS
L2
A | B | C |
D
N
PS
A|B|C|
D
L1
N
OUTPUTS
OUTPUTS
B
L1|L2|
Factory Connections
- To/Fr
om
Multigate Modules
(TOWARD
MULTIGATES)
L2
W
arning:
- All electrical installations must be done in accordance with the local and National Electrical Code® or ANSI/NFP
A 70. This document
does not replace any local, state, provincial, federal or national laws, regulation or codes applicable to the installation and use of the product. All installations must confor
m with the laws, regulations,
codes and standards applicable in the jurisdiction of installation. - Before connecting the product to the electrical utility grid, contact the local utility company
. This connection must be made by qualified
personnel only
.
- W
iring of the product must be made by qualified personnel only
.
- See diagram for
Customer Connection Points
and torque
specifications of each customer connection point. - See diagram for layout of major components. - Use 75C rated Copper conductors only
, do not use fine stranded
wires. - Use only the provided conduit holes or knock-outs to attach conduits with NEMA 4 fittings only
.
- Seal unused holes with NEMA 4 fittings only
.
- For commissioning and operating instructions, refer to user manual. - Refer to Multigate Manual for LEDs meanings. - Attach safety cover hardware to finger
-tight only
.
Specification T
able:
Model
Voltage Rating
Current Rating
XT3s
240V
AC
36A
Input W
ire Size
Output W
ire Size
#22 to #10A
WG
#20 to #6A
WG
INPUT POWER
CONDUITS
OUTPUT POWER CONDUIT
OUTPUT D
ATA
CONDUIT
∩ ∪
TEAL PN 0610770, rev 1.2
Figure 16: Example of the Multigate XT Door Label.
Figure 15: Example of the PIC/RID
Label supplied with each Multigate.