4 Set Up 

To enter set-up mode, press the 

 button for 3 seconds, until 

the password screen appears.

 

Setting up is password protected 
so you must enter the correct 
password (default ‘1000’) before 
processing. 

If an incorrect password is 
entered, the display will show: 

PASS Err 

Once the correct password is entered, hold 

 for 1 second to 

enter the setup menu. 

To exit the setup menu, press 

 repeatedly until the 

measurement screen is restored. 

4.1 Set-up Entry Methods 

Some menu items, such as password and Modbus address, 
require a four-digit number entry while others, such as supply 
system, require selection from a number of menu options. 

CT ratio is not required. This product is directly connected. 

4.1.1 Menu Option Selection 

1. Use the 

 and

 buttons to scroll through the different 

options of the set up menu.

2. Press

 to confirm your selection. 

3. If an item flashes, then it can be adjusted by the

 and 

 buttons. 

4. Having selected an option from the current layer, press
to confirm your selection. The SET indicator will appear.

5. Having completed a parameter setting, press

 to return to 

a higher menu level. The SET indicator will be removed and you 

will be able to use the 

 and 

 buttons for further menu 

selection. 

6. On completion of all setting-up, press

 repeatedly until 

the measurement screen is restored.

4.1.2 Number Entry Procedure

 

When setting up the unit, some screens require the entering of a 
number. In particular, on entry to the setting up section, a 
password must be entered. Digits are set individually, from left to 
right. The procedure is as follows: 

1. The current digit to be set flashes and then can be adjusted

using the 

 and 

 buttons. 

2. Press

 to confirm each digit setting. The SET indicator 

appears after the last digit has been set. 

3. After setting the last digit, press

 to exit the number 

setting routine. The SET indicator will be removed. 

4.2 Communication 

There is a RS485 port can be used for communication using 
Modbus RTU protocol. For Modbus RTU, parameters are 
selected from Front panel. 

4.2.1 RS485 Address 

From the set-up menu, use 

and 

 buttons to select the 

address ID. 

Press 

 button to enter the 

selection routine. The current 
setting will be flashing. 

Use 

 and 

buttons to choose Modbus 
address (001 to 247). 

On completion of the entry procedure, press 

 button to 

confirm the setting and press 

 button to return the main set-

up menu. 

4.2.2 Baud Rate 

From the set-up menu, use 

and 

 buttons to select the 

Baud Rate option. 

Press 

 to enter the selection 

routine. The current setting will 
flash. 

Use 

 and 

buttons to 

choose Baud rate 2.4k. 4.8k, 9.6k, 
19.2k, 38.4k 

On completion of the entry procedure, press 

 to confirm the 

setting and press 

 to return to the main set up menu. 

4.2.3 Parity 

From the set-up menu, use 

and 

 buttons to select the 

parity option. 

Press 

 to enter the selection 

routine. The current setting will 
flash. 

Use 

 and 

 buttons to 

choose parity (EVEN / 
ODD / NONE (default)). 

On completion of the entry procedure, press 

 to confirm the 

setting and press 

 to return to the main set up menu. 

4.2.4 Stop bits 

From the set-up menu, use 

and 

 buttons to select the 

stop bit option. 

Press 

 to enter the selection 

routine. The current setting will 
flash. 

Use 

 and 

buttons to choose stop bit (2 or 1). 

On completion of the entry procedure, press 

 to confirm the 

setting and press 

 to return to the main set up menu. 

4.3 Pulse Output 

This option allows you to configure the pulse output. The output 
can be set to provide a pulse for a defined amount of energy 
active or reactive. Use this section to set up the relay pulse 
output

—Units: kWh, kVArh. 

From the set-up menu, use 

and 

 buttons to select the 

Pulse output option. 

Press 

 to enter the selection 

routine. The unit symbol will flash. 

Use 

 and 

 buttons to 

choose kWh or kVArh. 

On completion of the entry procedure, press 

 to confirm the 

setting and press 

 to return to the main set up menu. 

4.3.1 Pulse rate 

 You can configure the pulse output to relate to a defined amount 
of imported or exported energy. This can also be set to use with 
active energy (kWh) or reactive energy (kVarh). 

Please note there are limitations that need to be factored in when 
setting the pulsed output. This is based upon the relay output 
only being able to pulse 2 times in one second. 

Pulse settings: 1 pulse per 0.01(10W) / 0.1(100W) / 1 (1kWh) 
/10(10kWh) / 100(100kWh) /1000 (1000kWh). 

DFT= Default. Set as 1 (1kWh) 

From the set-up menu, use 

and 

 buttons to select the 

Pulse Rate option. 

Press 

 to enter the selection 

routine. The current setting will 
flash. 0.01/0.1/1/10/100kWh/ 
kVArh per pulse. 

Use 

 and 

 buttons to choose pulse rate. On 

completion of the entry procedure, press 

 to confirm the 

setting and press 

 to return to the main set up menu. 

4.3.2 Pulse Duration (DIT) 

The energy monitored can be active or reactive and the pulse 
width can be selected as 200, 100 or 60ms (Default). 

From the set-up menu, use 

and 

 buttons to select the 

Pulse width option. 

Press 

 to enter the selection 

routine. The current setting will 
flash. 

Use 

 and 

 buttons to choose pulse width. On 

completion of the entry procedure press 

 to confirm the 

setting and press 

 to return to the main set up menu. 

4.4 Light Period (LP) 

The light period is a programmable time (in minutes) that 
determines how long the display backlight remains on for before 
this goes into standby. 

From the set-up menu, use the 

 and 

 buttons to select 

the reset option. 

Press 

 to enter the selection 

routine. The dIt will flash. The 
options are 0/10/30/60/120 
minutes. 

Press 

 to confirm the setting and press 

 to return to 

the main set up menu. 