1 Introduction 

This document provides operating, maintenance and installation 
instructions. This unit measures and displays the characteristics 
of Single Phase Two Wire (1P2W), Three Phase Three Wire 
(3P3W) and Three Phase Four Wire (3P4W) networks. The 
measuring parameters include Voltage (V), Current (A), 
Frequency (Hz), Power (kW/KVA/KVAr), Power Factor (PF), 
Imported, Exported and Total Energy (kWh/kVArh).The unit also 
measures Maximum Demand Current and Power, this is 
measured over preset periods of up to 60 minutes. 

It also comes with a complete comms capability with built in 
Pulse and RS485 Modbus RTU outputs, configuration is 
password protected. 

This unit is 10(100)A direct connected. Configuration is password 
protected. 

1.1 Unit Characteristics 

The DRS-100-3P can measure and display: 

• Phase to Neutral Voltage and THD% (Total

Harmonic Distortion) of all Phases

• Line Frequency
• Current, Maximum Demand Current and Current

THD% of all Phases

• Power, Maximum Power Demand and Power Factor
• Imported, Exported & Total Active Energy
• Imported, Exported & Total Reactive Energy

The unit has a Password-Protected set up menu for: 

• Changing the Password
• System Configuration - 1P2W, 3P3W, 3P4W.
• Demand Interval Time
• Reset for Demand Measurements
• Pulsed Output Duration

1.2 RS485 Serial 

– Modbus RTU 

RS485 serial port with Modbus RTU protocol to provide a means 
of remotely monitoring and controlling the Unit. Set-up screens 
are provided for setting up the RS485 port. Refers to section 4.8. 

1.3 Pulse output 

Two pulsed outputs that can be set for active (kWh) or reactive 
(kVArh) energy. 

2 Start Up Screens 

The first screen lights up all 
display segments and can be used 
as a display check. 

The second screen indicates the 
firmware installed in the unit and 
its build number. 

Please note: Values may vary from 
the numbers shown here. 

The interface performs a self-test 
and indicates the result if the test 
passes. 

*After a short delay, the screen will display active energy
measurements.

3 Measurements 

The buttons operate as follows: 

Selects the Voltage and Current display screens. In 
Set-

up Mode, this is the “Left” or “Back” button. 

Select the Frequency and Power factor display 
screens. In Set-

up Mode, this is the “Up” button. 

Select the Power display screens. 
In Set-

up Mode, this is the “Down” button. 

Select the Energy display screens. In Set-up mode, 
this is the “Enter” or “Right” button. 

3.1 Voltage and Current 

Each successive press of the 

 button selects a new 

parameter: 

Phase to neutral voltages. 

Phase to Line voltages 

Current on each phase. 

Voltage THD% per phase 

Current THD% per each phase. 

3.2 Frequency and Power Factor and Demand 

Each successive press of the 

 button selects a new range: 

Frequency and Power 

Factor (total). 

Power Factor of each phase. 

Maximum Current 

Demand. 

Maximum Power Demand. 

3.3 Power 

Each successive press of the 

 button select a new range: 

Instantaneous Active 

Power in kW. 

Instantaneous Reactive Power in 

kVAr. 

Instantaneous Volt-Amps in KVA. 

Total kW, kVArh, kVA. 

3.4 Energy Measurements 

Each successive press of the

 

 button selects a new range: 

Total active energy in kWh. 

Total reactive energy in kVArh. 

Imported active energy in kWh. 

Exported active energy in kWh. 

Imported reactive energy in kVArh. 

Exported reactive energy in kVArh. 

Please note the register is 9999999.9 display over two lines. 

Warnings  

During  normal  operation,  voltages  hazardous  to  life
may be present at some of the terminals of this unit. 

At voltages below that specified in the Range of Use
the  meter  may  shut  down.    However,  voltages
hazardous to life may still be present at some of the
terminals of this unit.

Installation  and  servicing  should  be  performed  only
by  qualified,  properly  trained  personnel  abiding  by
local regulations.

Ensure  all  supplies  are  de-energised  before
attempting connection or other procedures.

Terminals  should  not  be  user  accessible  after
installation and external installation provisions must
be  sufficient  to  prevent  hazards  under  fault
conditions.

This  unit  is  not  intended  to  function  as  part  of  a
system providing the sole means of fault protection -
good  engineering  practice  dictates  that  any  critical
function be protected by at least two independent and
diverse means.

The  unit  does  not  have  internal  fuses  therefore
external fuses must be used for protection and safety
under fault conditions.

Never  open-circuit  the  secondary  winding  of  an
energized current transformer.

This product should only be operated with the CT
secondary connections earthed.

If this equipment is used in a manner not specified by
the  manufacturer,  protection  provided  by  the
equipment may be impaired.

Caution: Risk of 
Electric Shock

 

User Manual 

DRS-100-3P 

DIN Rail Energy Meter for Direct Connected 

Three Phase Electrical Systems up to  

100 Amps 