![TDK-Lambda ZWS300RC Series Instruction Manual Download Page 3](http://html1.mh-extra.com/html/tdk-lambda/zws300rc-series/zws300rc-series_instruction-manual_4251232003.webp)
INSTRUCTION MANUAL
ZWS300RC
Series
TDK-Lambda
<Page>
Note
・
Take note that traces of sheet metal processing be left in our power supplies.
・
When disposing product, follow disposal laws of each municipality.
・
Published EMI (CE, RE) or immunity is the result when measured in our standard measurement conditions and might not
satisfy specification when mounted and wired inside end-user equipment.
Use the product after sufficiently evaluating at actual end-user equipment.
・
When exporting our products, apply for necessary permissions as required by rules and regulations of Foreign Exchange
and Foreign Trade Control Act.
・
Catalogue, contents of the instruction manual may be changed without a prior notice. Refer to latest catalogue or
instruction manual.
・
Reproduction or reprinting the instruction manual or its portion is forbidden without our permission.
LONG-TERM STORAGE METHOD AND LONG-TERM STORAGE PERIOD
・
Please keep the product in carton box.
・
Please do not apply excessive vibration, shock or mechanical stress applied directly to the product.
・
Please keep away from direct sunlight.
・
For long-term storage temperature and humidity, the following conditions shall be used as a guideline :
Temperature range : 5℃
~
30℃
Humidity range : 40%
~
60%RH
Please keep away from the places where temperature and humidity can change drastically.
It can cause condensation on the product or deterioration.
・
For long-term storage period, we recommend to use within 2 years after receiving the product.
There is tendency that the leakage current of an aluminium electrolytic capacitor may increase when stored without using for
a long time. This phenomenon can be improved by applying voltage to the aluminum electrolytic capacitor to reduce the
increased leakage current through the self-recovery effect of the electrolyte. For reference, before using products that have
been stored for a very long time, please warm-up first for 30 minutes or more without taking load.
< Criterion of warm up voltage condition >
(1)Implementation period : 1 year or above after the delivery
(2)Electrical continuity condition
Input voltage : Rating
Load : 0A
Ambient temperature : Normal temperature
Time : 30 minutes or more
3/17