![TDK-Lambda ZWS300RC Series Instruction Manual Download Page 12](http://html1.mh-extra.com/html/tdk-lambda/zws300rc-series/zws300rc-series_instruction-manual_4251232012.webp)
INSTRUCTION MANUAL
ZWS300RC
Series
TDK-Lambda
<Page>
6-12.
Connecting method of Buffer module ZBM-AC (Option “/BM”)
By connecting our ZBM-AC to CN2, the Hold up time of ZWS300RC can be extended.
Derating the output power of ZWS300RC by 10W per ZBM-AC connection.
The ZBM-AC that can be connected to ZWS300RC is as follows.
When using multiple ZBM-AC units, the maximum number of /S option is one unit.
It is necessary to use harness with withstand voltage of 400V or higher and equivalent to AWG16.
Please be careful about insulation of harness, because CN2 is on the primary side. An optional harness (sold
separately) for connection is available.
For details on how to use ZBM-AC and precautions, refer to the ZBM-AC instruction manual.
■
ZBM-AC connectable quantity
■
ZBM-AC connection example
■
Output power vs. Hold up time characteristics
ZWS300C Input Voltage : 200VAC, Ta=25℃, Initial state of capacitor capacity
12/17
0
50
100
150
200
250
300
100
1000
10000
O
ut
pu
t P
ow
er
(
W
)
Buffer Time (msec)
1 UNIT
2 UNITS
3 UNITS
4 UNITS
ZWS300RC
ZBM-AC
or
ZBM-AC/S
ZBM-AC
The following connections are not possible
ZWS300RC
ZWS300RC
ZBM-AC
• • • M
aximum
4 units
Input Voltage
85-170VAC or 120-240VDC
170-265VAC or 240-370VDC
Maximum number of units
1 unit
4 units
Output Power of
ZWS300RC-24/BM
Buffer Time (msec)
1 UNIT
2 UNITS
3 UNITS
4 UNITS
300 W
Do not use
Do not use
Do not use
Do not use
290 W
217
Do not use
Do not use
Do not use
280 W
225
412
Do not use
Do not use
270 W
235
450
625
Do not use
260 W
245
470
705
860
240 W
261
493
723
950
180 W
358
665
963
1270
120 W
541
995
1415
1900
60 W
1041
1920
2810
3580
30 W
1972
3510
4950
6300
CN2
CN2
CN2