3055 Del Sol Blvd • San Diego, CA 92154 • 1-800-LAMBDA-4
THR4-SSERIES POWER SYSTEM
Revision A4 : August, 2009
Page. 23
Controller Settings
Battery Boost Start Modes
Current Delay
The amount of time the start current must be
exceeded before the test will start. (Minutes)
0 minutes 0 minutes 0 minutes
Start Current
The value at which the current autoboost test will
start. (Amps)
40 Amps 40 Amps 40 Amps
AC Fail Mode
Enables or disables the AC fail based autoboost test.
When enabled the boost feature will automatically
start if an AC failure lasted longer than the AC fail
duration
Disabled
Disabled
Disabled
AC Fail Duration
The length of time (H:M:S) the AC failure must last
to trigger the autoboost feature
0:15:00
0:15:00
0:15:00
DC Drop Voltage The voltage the batteries must drop below during
the AC failure to trigger the autoboost feature (Volts)
44 Vdc
Battery Discharge Test
Battery Discharge Test Enables or Disables the battery discharge test feature Disabled
Disabled
Disabled
Duration
Sets the length of time (H:M:S) that the battery
discharge test will run.
1:00:00
1:00:00
1:00:00
Alarm Voltage
Sets the voltage at which an alarm will be generated
if the battery voltage falls below it during the Battery
Discharge Test.
11.25 V
22.5 V
45 V
Abort Voltage
The voltage at which the battery discharge test will
abort at when the system voltage drop below this
point.
10.75V
21.5V
43 V
Thermal Comp
Enabling this value will take thermal compensation
Adjust
effects into account during the test. Disabling this
value will disable Thermal Compensation effects
Disabled
Disabled
Disabled
during the test. Both Thermal Compensation, and
T Comp BDT have to be Enabled for thermal comp.
effects to take place during BDT.
Password
User/Admin 1001/5001 1001/5001 1001/5001
System
Description
12V
24V
48V
36V
Parameters
Nominal Nominal
Nominal Nominal
Table 10
* - Requires LVD & proper shunt
** - Requires LVD