 -4- 

TDK-Lambda 

RDS Series (110VDC Input) 

Instruction Manual

 

 

5. How to Wiring for the Terminal 

Please be careful when wiring the input line. Improper connection would cause damage to power supply. 

·

 

Each terminal wiring must be held under the condition without no input. 

·

 

When applying Protection Ground, use the terminal with the symbol ‘ ’ or use fixing screw to the (sheet-metal) chassis. 

·

 

When wiring, please separate between input & output line to improve immunity of switching noise. 

·

 

When using Remote Sensing or Remote ON/OFF function, please prepare twisted pair or shield wire for sensing or ON/OFF 

signal line, and ensure to separate from the output (load) line. 

·

 

Current rating is 25A maximum for the each terminal, but ensure to operate within rated specification of each output. 

 

 

Basic Connection (Local Sensing)

 

 

 

 

               

How to use Remote Sensing 

CS to +V, and –S to -V terminal   

 

 

 

1) Remove the short piece (originally attached). 

by using the short piece (sheet metal) 

 

 

 

2) CS & +V terminal by wiring. 

(Short piece is attached when shipping.)   

 

 

 

3) Connect -S & -V terminal by wiring. 

   

 

 

 

 

 

 

  * Note) Output shuts down when sensing line is open 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
                           

   * The short-piece is also connected between CNT and TOG terminals originally when shipping. 

 
 
 

   

   [ Pre-Caution ]      Insulation Classification and Safety Conformability 

 
                     Although withstand voltage is 2kVAC (1minute) between Input and Output / between Input and Chassis (Protective Earth) 
                     for this product, insulation classification is different for each point as shown below.. 

 
                                   

Between Input and Output - - - - - - - - - - - - - - - - - - - - - -  Reinforced Isolation

 

                                   

Between Input and Chassis (Protective Earth) - - - - - - - - - - - - Basic Isolation

 

 
                    Please connect AC/DC PSU (or transformer and rectifier) which has Reinforced or Double Isolation to the input terminal 
                     of this product when using original AC input which is greater than 115V. 
 
                    Furthermore, please refer Isolation and Withstand Voltage test method in the section 6-12 and 6-13 later. 

 
 
 
 
 

 

 

 

 

Load 

 

 

 

 

 

Load 

 

Summary of Contents for RDS Series

Page 1: ...instruction manual before switching on Input voltage Output current power Ambient temperature humidity should be kept within specifications otherwise the product will be damaged Do not operate and sto...

Page 2: ...ion 5 6 5 OCP Over Current Protection 5 6 5 OTP Over Temperature Protection 5 6 7 Remote Sensing Function S S terminals 5 6 8 Remote Control ON OFF Function 5 6 9 Output Ripple Noise Voltage 6 6 10 Se...

Page 3: ...ut Voltage Rated Input Voltage Output Power Type Products Series Name 2 Block Diagram Note For the 5V output model Rectifier is Synchronous type and LVP function is built in Abbreviation Symbol OCP Ov...

Page 4: ...bout 5 6V at open mode It changes 0V when turning off input 4 For 5V output model OCP method is constant current limit with latch shutdown by LVP It can be reset as the 2 above Furthermore for 12 15 a...

Page 5: ...t S to V and S to V terminal 1 Remove the short piece originally attached by using the short piece sheet metal 2 Connect S V terminal by wiring Short piece is attached when shipping 3 Connect S V term...

Page 6: ...own OCP operates if output current exceeds the rated output current of the unit approximately at 120 typ Then if output decrease to 2V approximately the output will be shut down by LVP inside After LV...

Page 7: ...aximum forward current rating more than output load current And maximum reveres voltage must withstand each power supply output voltage 6 11 Parallel Operation The RDS50 110 can be used for Back up Op...

Page 8: ...nting Method etc 7 1 Mounting Directions Mounting directions are as the picture shown below Standard mounting is A However the mounting as B C is also available Do not mount using D E method Use RDS a...

Page 9: ...ct the fuse according to input average current values under the actual load condition RDS unit has same rating fuse inside Vin Line RDS50 110 F3 2AL 10 Before Thinking that the Unit is Failure 1 Check...

Page 10: ...by this handbook indicates compliance with the Low Voltage Directive and RoHS Directive UKCA MARKING UKCA Marking when applied to a product or packing material for a product covered by this handbook i...

Reviews: