background image

Revision K : December 2009

Page. 7

3055 Del Sol Blvd • San Diego, CA 92154 • 1-800-LAMBDA-4

LZS-A

A500-33  Power  Supply

4.  GUIDE TO APPLICATION

4.1  SAFETY NOTICE

Dangerous voltages exist in this equipment. Observe the usual safety precautions when operating,

wiring, or servicing to reduce the risk of shock or injury.

4.2  INPUT  VOLTAGE

See table 3 on page 4.

4.3  OUTPUT  VOLTAGE

This power supply operates as a constant-voltage source with maximum load ratings as listed on

page 4.  If the load current tries to exceed 110% of the 60°C rating, the output voltage will begin

to decrease, thereby limiting the power delivered to the load.  Upon removal of overload, normal

operation will resume.

When shipped from the factory, the power supply is ready for use with output voltage (Vout) set to

its nominal rating of 24.0V.  Jumpers are in place on TB201 for local voltage sensing.  Where

precise regulation is required directly at the load, remote voltage sensing can be utilized.  This

can be achieved by utilizing the remote sense terminals on TB201 or "D" connector (see Figs.2

and 3).  The output voltage can be increased by turning the Vout adjust potentiometer clockwise.

The output voltage is decreased by turning the Vout adjust potentiometer counter clockwise.

As shown on page 4, LZS-A500 power supplies have both a maximum current rating and a

maximum output power rating (as a function of ambient temperature). Care should be taken to

limit both output current and output power to be within specified limits.  If these limitations are

not adhered to, the internal thermal protection circuit may shut down the power supply's opera-

tion.  For remote voltage sensing, the maximum limits for output power, as given on page 4,

apply at the power supply output terminals, not at the remote sensing point.

When adjusting the output voltage above 24.0V, ensure that there is sufficient OVP margin with

respect to the output voltage, to avoid nuisance tripping.

4.4  OVERVOLTAGE  PROTECTION  CIRCUIT  ADJUSTMENT

The overvoltage protection circuit provides an adjustable means of disabling the DC output if it

should exceed a pre-determined safe value.  When shipped from the factory, the overvoltage

level on each LZS unit is set as given in table 6 on page 5.  If a different OVP threshold is

required, it can be adjusted using the following method:

1. Turn the OVP Adjust potentiometer fully clockwise (at least 10 turns).

2. With the power supply unloaded, set Vout to the OVP threshold desired.  In cases where the

desired OVP threshold exceeds the unit’s adjustment range maximum of 29.4V, a programming

resistor (see figures 4 & 5) will temporarily be needed to provide the higher output voltage to

perform the adjustment. Once adjusted, remove the programming resistor. Alternatively, you may

use an external voltage source to set the OVP threshold as shown in figures 4 & 5.

3. Slowly turn the OVP adjust control counter clockwise while monitoring the output voltage.  Stop

turning the control immediately when the red FAULT indicator lights, indicating an OVP shutdown.

At that point, the OVP threshold is set to the desired value.

4.5  OVERTEMPERATURE AND OVERVOLTAGE SHUTDOWN

LZS-A500 power supplies will automatically shut down if operating conditions cause excessive

internal heating or excessive output voltage.  After the occurrence of an overvoltage shut down,

input power must be interrupted or the remote on/off feature must be toggled to re-establish the

output.  Overtemp shutdown resets itself once the unit has cooled off by approximately 10

°

C.  

4.6  AUXILIARY  CONTROL  AND  ALARM  SIGNALS

LZSa power supplies provide auxiliary control and alarm signals per page 5.  These signals are

accessible via the15-pin, sub miniature "D" connector, located below the output terminals of the

unit.

Summary of Contents for LZS-A500-3

Page 1: ...LZS A500 3 POWER SUPPLY Installation Operation and Maintenance Manual IM L LZSA500 3 3 December 2009 Revision K...

Page 2: ......

Page 3: ...Practices 2 1 1 General safety instructions 2 1 2 Safety Agency Approvals 2 2 RATINGS AND SPECIFICATIONS 4 3 FEATURES 5 4 GUIDE TO APPLICATION 7 4 1 Safety Notice 7 4 2 Input Voltage 7 4 3 Output Volt...

Page 4: ...Therefore screws at the case must not be removed or loosened 7 The output power taken from the power supply must not exceed the rating stated on the power supply label 8 Openings in the product case a...

Page 5: ...cal Fast Transients IEC61000 4 4 2 kV AC Line Criteria A 1 kV I O Line 3m Criteria A Lightning Surge IEC61000 4 5 2 kV line to GND CM Criteria A 1 kV line to line DM Criteria A Conducted RF Common Mod...

Page 6: ...PR 22 Class B Efficiency at max output power 84 typical 110VAC line Output Performance Specifications Units LZS A500 3 Table 4 Voltage Line Regulation 0 1 Voltage Load Regulation 0 1 Ripple and Noise...

Page 7: ...able output via TTL compatible signal connected between pins 6 and 7 of D connector see Fig 9 Signals Isolation Pins 6 and 7 are fully isolated from all other power supply terminals Signal Logic Logic...

Page 8: ...urface mounting position not restricted Maximum allowable penetration into power supply is 1 4 Requires No M4 metric hardware supplied with unit Input and Output Connections Table 11 Input Heavy duty...

Page 9: ...point When adjusting the output voltage above 24 0V ensure that there is sufficient OVP margin with respect to the output voltage to avoid nuisance tripping 4 4 OVERVOLTAGE PROTECTION CIRCUIT ADJUSTM...

Page 10: ...Revision K December 2009 Page 8 LZS A A500 3 3 Power Supply Figure 1 PIN Assignments for TB201 and chassis mounted D connector 5 Figures...

Page 11: ...o CA 92154 1 800 LAMBDA 4 LZS A A500 3 3 Power Supply Revision K December 2009 Page 9 Figure 3 Typical Remote Sense Connection Figure 2 Typical Local Sense Connection LS Local Sense S Remote Sense LS...

Page 12: ...gure 5 Remote Voltage Control with an External Programming Resistor or Voltage Source Remote Sensing Figure 4 Remote Voltage Control with an External Programming Resistor or Voltage Source Local Sensi...

Page 13: ...3055 Del Sol Blvd San Diego CA 92154 1 800 LAMBDA 4 LZS A A500 3 3 Power Supply Revision K December 2009 Page 11 Figure 6 Parallel Operation...

Page 14: ...LZS A A500 3 3 Power Supply Revision K December 2009 Page 12 Figure 7 Series Operation...

Page 15: ...3055 Del Sol Blvd San Diego CA 92154 1 800 LAMBDA 4 LZS A A500 3 3 Power Supply Revision K December 2009 Page 13 Figure 8 Outline Drawing AIR FLOW...

Page 16: ...LZS A A500 3 3 Power Supply Revision K December 2009 Page 14 Figure 9 Remote Output On Off Control Figure 10 Input Good Inverter Good Output Good Signals...

Reviews: