15. Wiring Method

(1)The output load line and input line should be separated. 
(2)Use all lines as thick and short as possible to make lower impedance. When attach the battery or large capacitance 

capacitor to the line, please attach them 1.5M apart from converter terminal. The lines shall be twisted or use 
shielded wire to improve noise sensitivity. 

(3)Noise can be reduced by attaching a capacitor to the load terminals.
(4) For safety and EMI considerations connect      terminal to the mounting set ground terminal by thick wire
( 5 )If  lighting  s u r g e   protection  is  required,  please  place  it  in  front  of  the  converter.  There  is  no  protection  against 

lighting surge inside the converter.

15-1.  Inserting contact into housing

(1)Do not apply any pulling force to crimped part and insert contact straightly to housing.
(2)Insert contact into housing, without stopping, to its furthest extent.
(3)Check secure locking on each insertion by pulling wire softly in order to check that contact does not come off 

housing. Besides, check whether there is the backlash in the direction of insertion axis.

15-2.  Mating and Un-mating connector

Hold receptacle housing securely and insert into header straight against to headed post until click sounds. Hold all 
wire securely and fix receptacle housing by fingers so as to unplug and then withdraw it on the mating axis.

 

15-3.  Routing of Wire

Routing wire so as not to apply external force to connector except force such as extent that bend the wire slightly, 

considering an enough length to route and fixing of wire.

16

 External Fuse Rating

Refer to following fuse rating when selecting external fuses that are to be used on input line.
Surge current flows when line turn on.
Do not select the fuse with input current values under the actual load condition.

HVDC (DC400V)

: 

70A Fast Blow type

LVDC (DC300V)

:

 

 70A Fast Blow type

23/24

Summary of Contents for EZA11K Series

Page 1: ...not attempt repair by yourself as it is dangerous for the user Do not operate and store these products in environments where condensation occurs due to moisture and humidity It might lead fire and ele...

Page 2: ...ltage to the output Especially applying reverse voltage or overvoltage more than the rated voltage to the output might cause failure electric shock or fire Do not use in special environment such as pl...

Page 3: ...sitive at generation and negative at regeneration Note When attach the battery or large capacitance capacitor please use the line over 1 5M to connect the device to the converter terminal Bi direction...

Page 4: ...N External Signal Connector Refer to 10 System Interface section SW DIP Switch Refer to 9 User Interface section RS 485 Serial Interface Connector Refer to 10 System Interface section Battery Connecti...

Page 5: ...ections for input output and connector terminals Route input line and output line separately to avoid noise interference Connect protective earth grounding to the terminal of this power supply Use the...

Page 6: ...r the initialize process the converter will be in waiting mode Power conversion operation will start when the operation command is sent The internal FANs are rotated during any power conversion operat...

Page 7: ...s when battery voltage level reaches the target voltage level Refer to 7 Battery Protection Grid bus ramp up mode can be selected for charged up capacitor Max 15000 F of grid side from 0V and or for o...

Page 8: ...e and over discharge protection that stops charging and discharging process when battery voltage level reaches the target voltage level Refer to 7 Battery Protection Grid bus ramp up mode can be selec...

Page 9: ...e The converter is necessary the pre charged voltage at battery side and grid side See illustration below The converter cannot startup when the pre charged voltage is not enough 9 24 Generation Charge...

Page 10: ...The rotary switch functions as the RS 485 address setting for this converter The interface address is composed of 7 bits and can be set within the range 0x00 0x7E range Rotary switch is used to set th...

Page 11: ...al PG is outputted Pin 3 becomes short to SG during Converter Operation Power Conversion 10 1 3 Converter Operation Stop Command STOP By shorting this signal to SG the converter can be forcibly stoppe...

Page 12: ...ut 2ms typ Chattering removal time 16ms No Voltage Contact Input When use semiconductor SW ON voltage should be 0 3V maximum Converter can be forcibly stopped by pin 5 short to SG Converter shuts down...

Page 13: ...termediate RS 485 connectors Due to this feature RS 485 bus can be extended simply by connecting interface cables between converters when connecting multiple converters to the host devices Depending o...

Page 14: ...Alert is detected external signal connector ALM signal is triggered open When this happens during power conversion process power conversion stops and the external signal connector PG becomes open Heav...

Page 15: ...verter Stop Command External Signal When Converter Stop Command of the External Signal Connector is detected the Converter Stop Alarm is triggered 11 2 9 Fan Lock If internal FAN rotation speed reduce...

Page 16: ...r Voltage Alarm is triggered Detect threshold level is fixed 11 2 14 System Alert When Abnormality is detected in this converter System Alarm will be triggered Alarm due to System Alert is not covered...

Page 17: ...ollow below indications 1 Please set same output voltage 2 Please use same size and same length of output wires 3 Please use same size and same length of input wire for each separate converter 12 8 Dy...

Page 18: ...voltage must be gradually increased from zero to testing value and then gradually decreased to zero When timer is used the unit may be damaged by high rate of change of voltage at turn on off Ramp the...

Page 19: ...1min 50mA Must connect short all pins of RS 485 and CN Notes This product has ceramic capacitor between primary circuit and chassis and between secondary circuit and chassis Some withstand voltage tes...

Page 20: ...6mm Converter Side View 20 24 Warning When installing EZA11K load the body on the chassis base side Don t load of the body only by the side brackets for rack mount That would damage the bracket and c...

Page 21: ...ng type converter This converter has ventilating holes on the front and rear side panel Keep these two areas freely as much as possible 2 The maximum allowable penetration of mounting screws is 6mm In...

Page 22: ...ltage V HVDC Voltage V Output Voltage V Output Current A Output Current A Output Voltage V Output Current A Output Current A 14 Output Derating 14 1 LVDC Voltage vs LVDC Current Derating 14 2 HVDC Vol...

Page 23: ...ousing 2 Insert contact into housing without stopping to its furthest extent 3 Check secure locking on each insertion by pulling wire softly in order to check that contact does not come off housing Be...

Page 24: ...ssis of converter abnormally hot The output might shut down by OTP operation Please re start after allowing time for the unit to cool down sufficiently 7 Check if the output current and output wattage...

Reviews: