- 21 -
TDK-Lambda
EZA11K series
Quick Manual / Practical(I)
Parameter
Function
Operation mode
Symbol
Name
LBV
Limit of Battery
Volts for
Discharging
Set the battery discharge lower
limit voltage of the battery over
discharge protection function
-Manual grid CV
-Manual grid CV with battery CC.
-Automatic grid CV
-Automatic grid CV with battery
CC.
DLD
Deviation of
Volts for
Warning of
Discharging
Lower Limit
Set the warning voltage to
inform you that the battery is
almost fully discharged. When
Battery Volt<LBV+DLD,
Warning signal is outputted.(Set
1 in Bit10 of CST)
-Manual grid CV
-Manual grid CV with battery CC.
-Automatic grid CV
-Automatic grid CV with battery
CC
DCD
Deviation of
Volts for
Cancel
Warning of
Discharging
Lower Limit
When Battery Volt
>LBV+DLD+DCD, Warning
signal is canceled. (Set 0 in
Bit10 of CST)
-Manual grid CV
-Manual grid CV with battery CC.
-Automatic grid CV
-Automatic grid CV with battery
CC.
*Deadzone: Converter is held in equilibrium operation that no operations neither generation
(Charge) nor regeneration (Discharge).