TDK-Lambda CUS150M1 Series Instruction Manual Download Page 8

 

- 9 - 

 

TDK-Lambda 

CUS150M1  

Instruction Manual

 

 

 
 

6. Wiring Method 

(1)

 

The output load line and input line shall be separated each other and twisted individually to improve noise. 

(2)

 

Use all lines as thick and short as possible to made lower impedance. 

(3)

 

Noise can be reduced by attaching a capacitor to the load terminals. 

(4)

 

For safety and EMI considerations, connect 

  with the terminal of protective earth of equipment firmly. 

7. External Fuse Rating 

Refer to the following fuse rating when selecting the external fuses that are to be used on input line. Surge current flows when line turns on.   
Have to use slow-blow or time-lag type fuse, not fast-blow fuse. Fuse rating is considered by in-rush current value at line turn-on. Do not 
select the fuse according to input current (RMS.) values under the actual load condition. 

CUS150M1 series: 5A 

 

8. Before concluding that the unit is at fault 

(1)

 

Check if the rated input voltage is connected. 

(2)

 

Check if the wiring of input and output is correct. 

(3)

 

Check if the wire thickness is enough. 

(4)

 

Check if the output current and output wattage dose not over specification. 

(5)

 

Check if the output voltage adjust trimmer (V.ADJ) is properly adjusted. OVP might be triggered and output is shut down. 

(6)

 

Audible noise can be heard when input voltage waveform is not sinusoidal wave. 

(7)

 

Audible noise can be heard during Dynamic-Load operation. 

(8)

 

Ensure that a large capacitor is not connected across the output terminals. Please use within maximum capacitance shown below. 
 

Model CUS150M1-12

CUS150M1-18

CUS150M1-24

CUS150M1-36 CUS150M1-48

Maximum external capacitance 

10000uF 

6000uF 

3000uF 

1000 

400uF 

 

9. Altitude 

CUS150M1 is safety approved for operation at below altitude. 
- Up to 5000m by IEC60950-1 clearance requirement. 
- Up to 4000m by IEC60601-1 clearance requirement. 
Thermal evaluation should be considered for products operating at elevated altitudes above 2000m. 
 

 

Summary of Contents for CUS150M1 Series

Page 1: ...plications which require very high reliability Nuclear related equipment medical equipment traffic control equipment etc it is necessary to provide a fail safe mechanism in the end equipment Do not in...

Page 2: ...nation Mountinghole holediameter 3 5mm Thisholeis notconnectedto ProtectiveEarth of CN1 L ACInputterminalLiveline Fuse inline N AC Input terminal Neutralline Fuse inline Earthterminal Mounting hole ho...

Page 3: ...50M1 4 2 Output Voltage Range Output voltage is set the rated value at shipment V ADJ trimmer VR51 can adjust the output voltage within the range Output voltage range refers to the specification To tu...

Page 4: ...er ripple will becomes larger In this case electrolytic capacitor film capacitor etc might be necessary to use across the load terminal The output ripple cannot be measured accurately if the probe gro...

Page 5: ...set current limit of the withstand voltage test equipment to 20mA The applied voltage must be gradually increased from zero to the testing value and then gradually decreased for shut down When timer i...

Page 6: ...MOUNTING D LOAD LOAD LOAD 20 40 100 100 100 50 100 100 75 60 75 70 50 65 63 55 38 70 50 40 25 5 3 Mounting Method Insert the spacer Max 7mm of height more than 8mm to lift the unit And use all mountin...

Page 7: ...ry from the solder surface If the space is not enough the specification of isolation or withstanding voltage will not be satisfied 3 Protective Earth should be connected to the earth terminal of the e...

Page 8: ...ncluding that the unit is at fault 1 Check if the rated input voltage is connected 2 Check if the wiring of input and output is correct 3 Check if the wire thickness is enough 4 Check if the output cu...

Reviews: