TDE Instruments Digalox DPM72 Instruction Manual Download Page 4

8. Messages on the display

Display

Meaning

Solution

XB timeout S...x

Slave ...x does not respond

Check slave 

configuration

XB tx err S...x

Data transfer problem when sending

to slave ...x

Check 

configuration

XB tx err <ref> 

<status>

Data transfer problem
reference <ref>: 
         255 = None
         254 = Telemetry
         253 = Command
         252 = Slave transfer
status <status>: 
         0x00 = Success
         0x01 = No ACK received
         0x22 = Not connected to network
         0x35 = Encryption error
         0x7A = Invalid host address
         ...

If necessary, 

read the 

transmit 

status 

number in 

the XBEE3

documen-

tation

XB response 

<slavecom_stat> 

S...x

Slave ...x responds with error message
<slavecom_stat>:
         0 = OK
         1 = Uninitialized
         2 = Invalid command
         3 = Invalid status
         4 = Invalid CRC
         5 = Invalid slave
         6 = Invalid interface
         7 = Communication failed
         8 = Buffer overflow
         9 = Invalid address
         10 = Device failure
         11 = Device busy
         12 = Gateway path unavailable
         13 = Gateway target device failed to respond

Check 

configuration

9. Contact details

TDE Instruments GmbH, Gewerbestraße 8, D-71144 Steinenbronn
Phone: +49 7157 20801
E-mail: [email protected]
Internet: www.tde-instruments.de, www.digalox.com

-----

 4 / 4 

-----

Summary of Contents for Digalox DPM72

Page 1: ...he radio interface the devices can also be configured individually The mesh network offers a robust connection that ensures continued operation even if a single radio node fails Each additional node acts as a router increasing the range of the network 2 Specification 2 4 GHz IEEE 802 15 4 mesh network Radio module XB3 24Z8UM J Digi XBee 3 Zigbee 3 0 2 4GHz Micro U FL Ant MMT Antenna connector SMA ...

Page 2: ...ordinator must be assigned to one device The coordinator starts and manages the network There can only be one coordinator and it must be active at all times The other devices should receive the XBEE role Router They can connect to a started network and integrate other devices Using the XBEE remote values tab 4 remote values can be read from other devices In order to display these remote values the...

Page 3: ...tus display The state of the communication is shown on the display Display Description Status Symbol flashes Network is being configured Symbol shines Network connected Crossed out symbol shines Network disconnected C C Coordinator shines XBEE Role Coordinator R R Router shines XBEE Role Router M M Master flashes Device communicates in master mode requesting values from others S S Slave flashes De...

Page 4: ...address If necessary read the transmit status number in the XBEE3 documen tation XB response slavecom_stat S x Slave x responds with error message slavecom_stat 0 OK 1 Uninitialized 2 Invalid command 3 Invalid status 4 Invalid CRC 5 Invalid slave 6 Invalid interface 7 Communication failed 8 Buffer overflow 9 Invalid address 10 Device failure 11 Device busy 12 Gateway path unavailable 13 Gateway ta...

Reviews: