TDE Instruments Digalox DPM72 Instruction Manual Download Page 2

4. Configuration

To configure a device, plug the XBEE stick into the computer. The driver of the stick 
is installed automatically if the computer is connected to the Internet.

If   the   XBEE   connection   settings   of   the   device   should   be   reset,   short-circuit 
connector J8 and open it again. This switches the device to configuration mode. The 
display (if present) shows "XBEE: Config", the measurement function is deactivated.

The device can be configured using the "Digalox

®

 Manager" software. In particular, 

the XBEE connection settings “Network ID” and “Link key” should be changed on 
the   General   tab   so   that   they   differ   from   the   default   settings.   Afterwards,   the 
measuring function is active. “Network ID” and “Link key” must be the same for all 
devices of a network.

The   XBEE   role   "Coordinator"   must   be   assigned   to   one   device.   The   coordinator 
starts and manages the network. There can only be one coordinator and it must be 
active at all times. The other devices should receive the XBEE role "Router". They 
can connect to a started network and integrate other devices.

Using   the   XBEE   remote   values   tab,   4   remote   values   can   be   read   from   other 
devices. In order to display these remote values, they must be selected as value 
types of display values on the display values tab.

For devices with a display, all values that are to be transmitted must also be visible 
on the display. Devices without a display provide the first four display values. By 
setting jumpers J4-J6, other display values are provided accordingly.

5. Source value addresses

Address

Data type

Description

0x0000

int8

Chosen display value index

0x0001

int8

(0) DC or (1) AC measurement active

0x8000-0x8003

int64

Display value 1-4 as int64

0xC000-0xC003

float32

Display value 1-4 as float32

-----

 2 / 4 

-----

Summary of Contents for Digalox DPM72

Page 1: ...he radio interface the devices can also be configured individually The mesh network offers a robust connection that ensures continued operation even if a single radio node fails Each additional node acts as a router increasing the range of the network 2 Specification 2 4 GHz IEEE 802 15 4 mesh network Radio module XB3 24Z8UM J Digi XBee 3 Zigbee 3 0 2 4GHz Micro U FL Ant MMT Antenna connector SMA ...

Page 2: ...ordinator must be assigned to one device The coordinator starts and manages the network There can only be one coordinator and it must be active at all times The other devices should receive the XBEE role Router They can connect to a started network and integrate other devices Using the XBEE remote values tab 4 remote values can be read from other devices In order to display these remote values the...

Page 3: ...tus display The state of the communication is shown on the display Display Description Status Symbol flashes Network is being configured Symbol shines Network connected Crossed out symbol shines Network disconnected C C Coordinator shines XBEE Role Coordinator R R Router shines XBEE Role Router M M Master flashes Device communicates in master mode requesting values from others S S Slave flashes De...

Page 4: ...address If necessary read the transmit status number in the XBEE3 documen tation XB response slavecom_stat S x Slave x responds with error message slavecom_stat 0 OK 1 Uninitialized 2 Invalid command 3 Invalid status 4 Invalid CRC 5 Invalid slave 6 Invalid interface 7 Communication failed 8 Buffer overflow 9 Invalid address 10 Device failure 11 Device busy 12 Gateway path unavailable 13 Gateway ta...