8. Configuration

Connect the device to a computer:

USB:

  Connect the device and the computer using a USB cable. The

device driver is installed automatically if the computer is connected to
the Internet.

XBEE:

  Insert the XBEE stick into the computer. The device driver is

installed automatically if the computer is connected to the Internet. In
order to reset the XBEE settings, short-circuit terminal J8.

RS485:

  Short-circuit   terminal   J8.   Disconnect   the   device   from   the

Modbus network and connect it to the computer using an RS485 USB
adapter. After completing the configuration, open J8 again.

Start the "Digalox Manager" software and connect it to the device. Settings can
then be made on the various tabs and saved in the device.

Please note that the measurement mode selected in “Digalox Manager” is displayed
only until the power supply of the DPM72 is interrupted.

In further operation, the device always shows the first

measurement mode or the one that is selected by the jumpers

J4-J6 (see table “Measurement mode”),

in case of a multi display style additionally the following measuring modes.

Table measurement mode (factory preset, can be changed by software)

Measurement mode

Measurement
input

Display

Measurement

mode selection

1

20 mA (I1) DC scaled

I1

20 mA
%

J1

J12

2

20 mA (I2) DC scaled

I2

20 mA
%

J1

J12

3

4-20 mA (I1) DC scaled

I1

4-20 mA
%

J1

J12

4

4-20 mA (I2) DC scaled

I2

4-20 mA
%

J1

J12

-----

 5 / 8 

-----

Summary of Contents for 103317

Page 1: ...t The device must not be used as the only protective device or protective shutdown The device is not intended to protect persons or facilities against harm Specific devices must be used to guarantee s...

Page 2: ...recorded over a timespan of 36 seconds up to 14 days The timebase as well as the display of the measuring history can be activated by an external switch The measured values remain stored as long as t...

Page 3: ...3 2 1 5 4 Back 1 2 optocoupler switch outputs 2 Jumper pins J1 J12 for activating switching of graphical historic data display min max display auto scaling measurement mode 3 Supply voltage input 4 In...

Page 4: ...sensor with voltage supply 20 mA analogue signal I2low I2high I1high I1low max 100 mA 0 mA 20 mA FF 100 mA 2 20 mA analogue signal max 100 mA 0 mA 20 mA FF 100 mA I2low I2high I1high I1low max 100 mA...

Page 5: ...t the Digalox Manager software and connect it to the device Settings can then be made on the various tabs and saved in the device Please note that the measurement mode selected in Digalox Manager is d...

Page 6: ...interval 2 sec When first opening and closing J1 the current time base is displayed For each subsequent opening and closing the time base changes to the next setting In order to save the setting perm...

Page 7: ...pdate 5 Hz 32 kHz sampling rate Recording of measurement 36 seconds to 14 days 180 internal memory locations Alarm outputs 2 optocoupler outputs max 30 V DC 50 mA Permissible voltage between supply an...

Page 8: ...information TDE Instruments GmbH Gewerbestra e 8 D 71144 Steinenbronn Phone 49 7157 20801 E Mail info tde instruments de Internet www tde instruments de www digalox com 8 8 56 3 83 5 72 0 72 0 77 5 18...