Setup
Note: If using remote sensor(s), the calibration may need
to be adjusted. See “Checkout and Troubleshooting”
section.
TEMPERATURE SENSOR SELECTION
The dipswitches in the cover (shown above) must be set
when using remote room, and/or pipe temp sensors.
Use the following guide to determine the dipswitch
settings for your application.
Using built-in room sensor only.
(This is the default setting.)
Using built-in room sensor with
pipe sensor only. (SZ1064 only)
Using remote room sensor only.
Using remote room sensor with
pipe sensor only. (SZ1064 only)
Once the dipswitches have been
set and you have confirmed that
the sensors are reading correctly,
secure the cover to the base with
the two set screws located at the top right and the left
side to prevent
tampering.
Programming
The SZ1063 and SZ1064 may be programmed through
the keypad on the face, or with a PC.
If programming with a PC, the following must be set
through the face prior to programming:
• Address (step #18)
• Baud rate (step #19)
• Temperature scale (step #20)
For more information on programming through the PC,
consult your TCS software manual.
PROGRAMMING THROUGH THE KEYPAD
To access the programming screens, press the program
setup button. Screens A thru F are monitoring screens
program
setup
program
setup
BRANCH TO CLOCK/
10.
SCH. MENU?
YES
ENTER ACCESS
000
CODE
9.
NO
OVERRIDE ON
178 MINUTES
F.
program
setup
MOD OUT 1 00%
MOD OUT 2 00%
E.
program
setup
program
setup
PIPE TEMP:
D.
150F
DI3 OPEN
OFF
AUX RELAY
C.
program
setup
program
setup
DI2 OPEN
DI1 OPEN
B.
program
setup
A.
WED FAN:MED
3:27 PM
82F
1 2 3 4 5
Main Monitoring Screen
. Press the
program setup button to access the follow-
ing screens. (Day and date not shown on
SZ1063)
Digital Input 1 & 2 Status Screen.
Shows the status of DI1& DI2.
Digital Input 3 Status & Auxiliary
Relay Output Screen.
Shows the
status of DI3. Shows the status of the
auxiliary relay output. This can be either
a timeclock output, a stage of heat or a
stage of cool. (Aux. output on SZ1064
only)
Pipe Temperature Screen.
Shows
the pipe temperature if a pipe tem-
perature sensor is used. (SZ1064 only)
Modulating Output 1 & 2 Status
Screen.
Shows the percentage of mod-
ulating output 1 (heat) & output 2 (cool).
Override Status Screen.
Shows the
status of the first and second stages of
heating.
high
Occupied
Heating
Cooling
Data / Program
Service
COOLER
WARMER
Fan
fan
medium
fan
low
fan
fan
off
program
setup
OVERRIDE