background image

2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

10

the sensor in question. A remote sensor should read 1080 

to 1090 ohms at room temperature. The built-in sensor 

should read 108 to 109 ohms at room temperature. If any 

of the temperatures are still reading slightly high or low, you 

can add in a temperature offset (calibration) using Ubiquity 

or TCS Insight. In Ubiquity, you can edit the calibration off

-

set for each temperature input (room, discharge, outdoor 

air, etc.) on the controller's programming page. For exam

-

ple, if the room temperature is reading 2 degrees high, you 

would subtract 2 from the existing offset in the room tem

-

perature calibration offset field and submit the page. In TCS 

Insight, the process is similar. Refer to the Calibrate Using 

TCS Insight Tech Bulletin # 1019 for details. As a last resort 

and only when directed to do so by TCS technical support, 

you may be able to use the on-board adjustment pots. 

Refer to the Thermostat Sensor Calibration Tech Bulletin # 

1005 for details.

Outputs Will Not Shut Off

First check the room temperature and the setpoints and 

determine whether the output should be on. There are 

delays and minimum on and off times for the fan and 

heating and cooling stages. Also, check the service 

status menus to verify that the outputs are on. Turning 

the system to "off" will instantly turn all outputs off. The 

thermostat can be reset by pressing the system switch 

button and the service status button simultaneously.

Analog Output Not Working Properly

Check wiring. A separate transformer should be used for 

the SZ1063 and SZ1064, and a separate transformer 

should be used for the motor(s). Check to make sure 

that the analog output is programmed correctly.
Check the Monitoring screens. The Mod Out Screens 

will tell you what the SZ1063 and SZ1064 is trying to put 

out. Compare this with the actual position on the heating 

or cooling device.

Output Operation is not Correct

Check programmed parameters, in particular "Reverse" 

and "Direct" acting selections and "Heat" or "Cool" 

selections for the analog outputs, and "Offset"and 

"Differential" selections and "Delay Times" for the relay 

outputs. Check wiring.

LED Description                                 

Six LEDs on the face allow the occupant to view the cur

-

rent operating status of the thermostat.

Rev:0113

C3587_REV2

OCCUPIED

This LED will be lit whenever the unit is operating in the 

occupied mode.

HEATING

This LED will be lit when any heat output is operating.

COOLING

This LED will be lit when any cool output is operating. 

DATA / PROGRAM

This LED will be lit when the thermostat is within the 

programming or clock setup menus. It will blink when the 

unit is being accessed by a PC.

SERVICE

This LED will be lit when DI2 is closed.

FAN

This LED will be lit when the fan output is closed.

Limiting Occupant Access                  

SETPOINT ADJUSTMENT
The occupant may temporarily change the occupied 

heating and cooling set/- 5°F by factory default. 

This setpoint change will remain until the end of the cur

-

rent occupied period, at which time the program reverts 

to the setpoints defined in programming. To change the 

range of adjustment allowed, see programming step #22. 

OVERRIDE
The occupant has the ability to put the unit into occupied 

mode by pressing the override button on the front. By 

factory default, the unit will remain in the occupied mode 

for 180 minutes. This value may be changed from 0 to 

255 minutes in programming step #23.  

SETTING CLOCK & SCHEDULE
The ability to set the clock and schedule is allowed by 

factory default. An access code may be required as set 

in programming step # 49.

PROGRAMMING
The ability to program control parameters is allowed by 

factory default. An access code may be required as set 

in programming step # 49.

User’s Guide                                     

Inside the hinged door of the thermostat is the 

Superstat

TM

 User's Guide. This guide is designed to 

assist the installer in explaining to the end user how 

to operate their new thermostat, as well as serve as a 

handy future reference for the end user.

We recommend that the installer fill out the appropriate 

pages and explain to the user how the thermostat oper

-

ates, what settings may be changed, and how the time 

clock schedules are used.

T1

T2

T3

1  

2

1  2  3  4  5

adjust display contrast

Summary of Contents for SZ1063

Page 1: ...64 only Local and remote override capability External time clock and override options Auxiliary output for heat cool or time clock SZ1064 only Contents Description 1 Features 1 Mounting 1 Wiring 2 Setup 3 Programming 3 Setting Clock Schedule 6 Sequence of Operation 6 Checkout Troubleshooting 8 LED Description 9 Limiting Occupant Access 10 User Guide 10 Mounting The SZ1063 and 64 are designed for w...

Page 2: ...om mon return paths When the Superstat is used as a stand alone thermostat without communications the unit transformer may be used to power it To do this install a jumper between the R and 24 terminals The 24 terminal must then be connected to the common side of the unit trans former Black 1 For communication wiring use twisted shielded 18 AWG Must be run separately 2 Dry momentary contct Must not...

Page 3: ...e information on programming through the PC consult your TCS software manual PROGRAMMING THROUGH THE KEYPAD To access the programming screens press the program setup button Screens A thru F are monitoring screens program setup ENTER ACCESS 000 CODE 9 OVERRIDE ON 178 MINUTES F program setup MOD OUT 1 00 MOD OUT 2 00 E program setup program setup PIPE TEMP D 150F DI3 OPEN OFF AUX RELAY C program set...

Page 4: ...two occupied periods SZ1064 only Schedule Announcement Screen Announces the next screen SZ1064 only Copy Schedule Screen Choose to use the same schedule that was used for the previous day If so the next screen does not appear SZ1064 only Occupied Times Screen Set the hours and minutes of start and end times for up to two occupied periods SZ1064 only Occupied Times Screen Set the hours and minutes ...

Page 5: ...step 42 2 Pipe Fan Coil Enable Screen Choose YESifusingatwo pipesystem Otherwisechoose NO If NO is selected and skip to step 42 and it is assumed to be a four pipe system Digital Aquastat Input Screen Choose whether DI1 will be normally open N O or nor mally closed N C for cooling The next screen is skipped Analog Aquastat Input Screen If an analogaquastatisselected choosethechangeover setpoint to...

Page 6: ...enabled using the software the override also activates in occupied mode and takes the thermostat into unoccupied mode In either case you are able to view the time remain ing in the override period both within the software and by using the service button to scroll through the status screens If the occupant desires to return the thermostat to unoccupied or occupied operation depending on how the ove...

Page 7: ...ng a temperature sensor select ANALOG in step 31 and place a changeover set point in step 33 When the temperature is greater than this setpoint it is assumed hot water is available and heating is done When the temperature is less than this setpoint it is assumed cold water is available and cooling is done When using a two pipe system to do both heating and cooling only AO2 is used When using a two...

Page 8: ...er than zero you anticipate that the residual heat or cooling in the duct will bring the temperature back to setpoint In most cases a first stage is set to zero The differential value is the difference between the on and off points Using an offset value greater than or equal to the proportional band of an analog output will allow the relay to come on after full modulation is achieved Strip heat fo...

Page 9: ...n after 30 seconds 8 Press the warmer button until the cooling setpoint is greater than the current temperature by one degree The cooling stage will sequence off The fan will turn off 2 minutes afterwards 9 For a heating or cooling analog output Take note of the room and discharge air temperatures If the analog output is set for Cooling press the Cooler button until the cooling setpoint is less th...

Page 10: ... acting selections and Heat or Cool selections for the analog outputs and Offset and Differential selections and Delay Times for the relay outputs Check wiring LED Description Six LEDs on the face allow the occupant to view the cur rent operating status of the thermostat Rev 0113 C3587_REV2 OCCUPIED This LED will be lit whenever the unit is operating in the occupied mode HEATING This LED will be l...

Reviews: