2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

1

SZ1063/SZ1064

Modulating Fan Coil 

Thermostats

Product Manual           

Description                                        

The SZ1064 is a microprocessor based programmable 

modulating fan coil thermostat and the SZ1063 is a non-

programmable modulating fan coil thermostat.

Features                                            

•  Stand-alone or network operation 

•  No battery backup required

•  Minimum on/off times for HVAC equipment protection

•  32-character LCD display

•  Six status LEDs 

•  Remote room sensing capability

•  User setpoint adjustment limits

•  Three speed fan

•  System and fan switching with access lockouts

•  External input for setback or aquastat changeover

•  Access to programming may be locked out or limited 

with the use of an access code

•  Fahrenheit or Celsius temperature display

•  Control for two or four pipe systems

•  7-day programmable time clock

•  Optional pipe sensor inputs for changeover (SZ1064 

only)

•  Adjustable delay on start-up and power-up for soft 

starts

•  Smart recovery (SZ1064 only)

•  Local and remote override capability

•  External time clock and override options

•  Auxiliary output for heat, cool or time clock (SZ1064 

only)

Contents                                            

Description

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1

Features

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1

Mounting 

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1

Wiring

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2

Setup

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3

Programming

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3

Setting Clock & Schedule

. . . . . . . . . . . . . . . . . . . . . . .

6

Sequence of Operation

  . . . . . . . . . . . . . . . . . . . . . . . .

6

Checkout & Troubleshooting

  . . . . . . . . . . . . . . . . . . . . 8

LED Description

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Limiting Occupant Access

  . . . . . . . . . . . . . . . . . . . . . . 10

User Guide

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Mounting                                          

The SZ1063 and 64 are designed for wall mounting 

using two #6 sheet metal screws, either over a horizon

-

tally installed 2" x 4" junction box, or directly to block or 

drywall.
For best results, the thermostat should be mounted on 

an interior wall which reflects normal room environment, 

at a height of approximately five feet from the floor. 

Avoid areas exposed to direct sunlight, unusual heat 

or cool sources, open doors and windows, unventilated 

locations and hot or cold air from diffusers.

If using a remote room sensor, it should be mounted in 

the manner described above. The thermostat may then 

be mounted in an area which is accessible for adjusting 

its settings.

Caution:  Remove power from thermostat prior to 

mounting.

        Communicating Thermostats

        Communicating Thermostats

SZ1063 has been discontinued January 2013

Summary of Contents for SZ1063

Page 1: ...64 only Local and remote override capability External time clock and override options Auxiliary output for heat cool or time clock SZ1064 only Contents Description 1 Features 1 Mounting 1 Wiring 2 Setup 3 Programming 3 Setting Clock Schedule 6 Sequence of Operation 6 Checkout Troubleshooting 8 LED Description 9 Limiting Occupant Access 10 User Guide 10 Mounting The SZ1063 and 64 are designed for w...

Page 2: ...om mon return paths When the Superstat is used as a stand alone thermostat without communications the unit transformer may be used to power it To do this install a jumper between the R and 24 terminals The 24 terminal must then be connected to the common side of the unit trans former Black 1 For communication wiring use twisted shielded 18 AWG Must be run separately 2 Dry momentary contct Must not...

Page 3: ...e information on programming through the PC consult your TCS software manual PROGRAMMING THROUGH THE KEYPAD To access the programming screens press the program setup button Screens A thru F are monitoring screens program setup ENTER ACCESS 000 CODE 9 OVERRIDE ON 178 MINUTES F program setup MOD OUT 1 00 MOD OUT 2 00 E program setup program setup PIPE TEMP D 150F DI3 OPEN OFF AUX RELAY C program set...

Page 4: ...two occupied periods SZ1064 only Schedule Announcement Screen Announces the next screen SZ1064 only Copy Schedule Screen Choose to use the same schedule that was used for the previous day If so the next screen does not appear SZ1064 only Occupied Times Screen Set the hours and minutes of start and end times for up to two occupied periods SZ1064 only Occupied Times Screen Set the hours and minutes ...

Page 5: ...step 42 2 Pipe Fan Coil Enable Screen Choose YESifusingatwo pipesystem Otherwisechoose NO If NO is selected and skip to step 42 and it is assumed to be a four pipe system Digital Aquastat Input Screen Choose whether DI1 will be normally open N O or nor mally closed N C for cooling The next screen is skipped Analog Aquastat Input Screen If an analogaquastatisselected choosethechangeover setpoint to...

Page 6: ...enabled using the software the override also activates in occupied mode and takes the thermostat into unoccupied mode In either case you are able to view the time remain ing in the override period both within the software and by using the service button to scroll through the status screens If the occupant desires to return the thermostat to unoccupied or occupied operation depending on how the ove...

Page 7: ...ng a temperature sensor select ANALOG in step 31 and place a changeover set point in step 33 When the temperature is greater than this setpoint it is assumed hot water is available and heating is done When the temperature is less than this setpoint it is assumed cold water is available and cooling is done When using a two pipe system to do both heating and cooling only AO2 is used When using a two...

Page 8: ...er than zero you anticipate that the residual heat or cooling in the duct will bring the temperature back to setpoint In most cases a first stage is set to zero The differential value is the difference between the on and off points Using an offset value greater than or equal to the proportional band of an analog output will allow the relay to come on after full modulation is achieved Strip heat fo...

Page 9: ...n after 30 seconds 8 Press the warmer button until the cooling setpoint is greater than the current temperature by one degree The cooling stage will sequence off The fan will turn off 2 minutes afterwards 9 For a heating or cooling analog output Take note of the room and discharge air temperatures If the analog output is set for Cooling press the Cooler button until the cooling setpoint is less th...

Page 10: ... acting selections and Heat or Cool selections for the analog outputs and Offset and Differential selections and Delay Times for the relay outputs Check wiring LED Description Six LEDs on the face allow the occupant to view the cur rent operating status of the thermostat Rev 0113 C3587_REV2 OCCUPIED This LED will be lit whenever the unit is operating in the occupied mode HEATING This LED will be l...

Reviews: