TCS BRE2-EB Product Information Download Page 3

 

02/2013

 

TCS TürControlSysteme AG, TCS Hotline Germany:  [email protected]

 

Subject to technical changes. 

FAX: +49 (0) 41 94/ 9 88 129 

 

PI_bre2eb_uk  1 A 

 

Programming options 

 

manually 

additional options with PC / con

figo™  

Switch time of the output: 0.5 to 128 s 
factory setting 1s 
 
Switching functions of the output: 

  calling the 

device‘s serial number 

  floor call, front-door door call and internal  

  call to the serial number 

  door release with serial number,  

  start of a voice connection and  
  control function of a serial number  
 
Function of the input: 

  as closing contact to create any 

  TCS:BUS protocol 

Switch time of the output: 

  up to 30 min or unlimited



  pull-in delay up to 30 min 

Switching functions of the output:  

  start of a voice connection at the front-door station 

  reset at the end of a voice connection 

  second serial number 

  control functions and front-door calls of 10 further serial

  numbers 
switch ON / OFF function, switch ON / OVER function 
linkage of several relay switch functions 
setting a programming lock 
Function of the input: 

  as opener to create any TCS:BUS protocol

 

open the device’s output 

 
 
 

Connecting the lines 

 

Connection lines 

per terminal

 

TCS:BUS, input terminals:  0.12 ... 0.5 mm

2

 (diameter: 0.4 ... 0.8 mm) possible 

output terminals: 

0.5   ... 1.5 mm

2

 (diameter: 0.8 ... 1.4 mm) possible 

Connect the lines according to the following connection schemata 
 

!

 

When using 3-wire technique, remove the jumper (see device overview)! 

 
 

TCS:BUS terminals, input terminals 

output terminal 

 

 

 
 
 

Important note for commissioning 

During the transport, the relay can be exposed to impacts. Thus, the contact can be 
moved into working position (K1-K2 closed). 

 

!

 

When starting the commissioning, connect the TCS:BUS to the relay and the  
TCS:BUS to the power supply to move the contact into rest position. 

 

 
 
 
 



Summary of Contents for BRE2-EB

Page 1: ...tors between heavy and low current lines within shared cable ducts use of standard communication lines e g J Y St Y with 0 8 mm diameter existing lines modernisation with deviating cross sections can be used in compliance with the loop resistance Attention The ingress of liquids or electronically conductive parts can cause short circuits fire or an electronic shock Thus provide water or other liqu...

Page 2: ...E2 EB is suitable to execute switching and detection functions in TCS BUS sys tems To be built in into flush mounted sockets Suitable for 3 wire connection a b and P 2 wire connection with max of 3 pieces BRE2 EB within the TCS BUS sys tem Short description Basic functions output potential free for switching functions to trigger the switch time by pressing bell buttons of any front door station fl...

Page 3: ...voice connection second serial number control functions and front door calls of 10 further serial numbers switch ON OFF function switch ON OVER function linkage of several relay switch functions setting a programming lock Function of the input as opener to create any TCS BUS protocol open the device s output Connecting the lines Connection lines per terminal TCS BUS input terminals 0 12 0 5 mm2 di...

Page 4: ... blinks for 30 s press as long as Prog2 tone light switch tone and ring tone sound at the front door station release shortly LED press is ON output is allocated to a bell button Programming mode of the system is switched OFF Delete the allocation to a bell button shortly LED press blinks press until the delete tone sounds release shortly LED press is ON Programming mode of the system is switched O...

Page 5: ... release the LED lights up press door opener or press floor push button or free BUS actions by entry via Service Device TCSK 01 press until the release LED lights up shortly LED OFF execute required BUS action input is allocated to BUS actions Reload factory setting2 switch time of the output 1 s input sends door release protocol AS 0 BRE2 press until release the LED is ON press until the LED rele...

Page 6: ...ormation on disposal The adjoining symbol shows that the device has to be disposed separately from domestic waste The material used are recycable Please do help protecting our environment and dispose the device via a collection point for electronic scrap Dispose the parts of the packaging in collecting tanks for cardboard and paper resp plastics ...

Page 7: ...ct to technical changes FAX 49 0 41 94 9 88 129 PI_bre2eb_uk 1 A Warranty We offer a simplified processing in case of warranty for electricians Please note our conditions of sale and delivery download from www tcsag de down loads trade information Please contact the TCS HOTLINE ...

Page 8: ... Subject to technical changes FAX 49 0 41 94 9 88 129 PI_bre2eb_uk 1 A Service Please send your questions and inquiries to hotline tcsag de Headquarters TCS TürControlSysteme AG Geschwister Scholl Str 7 39307 Genthin Phone 49 0 3933 879910 FAX 49 0 3933 879911 www tcsag de ...