background image

3. Take note of the current temperature and other input 

readings. If the SZ1145 will be used only for monitor-
ing, and the readings appear to be correct, you are 
done.

4. For all analog inputs which will be used to generate 

an alarm condition, go into programming mode and 
adjust the high and/or low limits below and/or above 
the current readings. For all digital inputs which will 
be used to generate and alarm condition, go into 
programming mode and change the setting from 
open to closed (or vice versa). Through the monitor-
ing screens, verify that the alarm condition(s) is (are) 
recognized.

5. If the relay output is not disabled, verify its operation 

when at least one alarm is present and also when no 
alarms are present. If using the alarm time-out fea-
ture, verify that once an alarm occurs the relay goes 
back to its non-alarm state after the programmed 
time.

6. If DI1 will be set to "Toggle Momentary" mode when 

there are no alarms present, momentarily short DI1 
to C. Through the monitoring screens, verify that the 
"Override" is on and that the "Time Remaining" num-
ber counts down.

7. Go back into programming mode and set up the 

SZ1145 with all of the desired settings.

TROUBLESHOOTING

No Display

Check for 24 VAC on terminals “R” and “C”.

Relay Output Does Not Come On

Check the High and Low Limits for analog inputs, and 
open or closed settings for digital inputs. Check to be 
sure that the relay output has been selected to be open 
or closed upon alarm. Verify through the monitoring 
screens that indeed there is an alarm present.

Relay Output Does Not Shut Off

Verify that the "Alarm Status" in the monitoring menu is 
"OK", signifying that there are no alarms present. If this 
is the case, verify that the relay output is set to normally 
closed for an alarm condition.  Remove power from the 
SZ1145. Remove the wires (or terminal block) from ter-
minals “NO” to “COM”.  Measure W from terminals “NO” 
to “COM”. If the reading is 0W, the mechanical relay is 
defective. 

R

2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

7

Alarm Status. 

Either check or ok.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp1 & Temp2 Alarm Screen. 

 Shows 

the Temp1 and/or Temp2 alarm condition if 
either is in alarm.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp3 & Temp4 Alarm Screen. 

Shows 

the Temp3 and/or Temp4 alarm condition if 
either is in alarm.

 

 

 

 

 

 

 

 

 

AI1 & AI Alarm Screen. 

Shows the AI1 

and/or AI2 alarm condition if either is in 
alarm.

Wrong Temperature Display

If either of the four temperature input readings is slightly 
high or low +/- 5°F, they can be adjusted. The "T1" input 
adjustment pot is labeled "T1" and so on. You should also 
remove the wires from (or terminal block) from terminals 
"T1" to "T1", etc., and measure 

Ω

 on the wires. The sen-

sor will read 1000 

Ω

 at 32°F (0°C). The sensor has a posi-

tive temperature coefficient and the reading will change 
2.16 

Ω

 per °F. If the actual temperature was 70°F the 

reading would be 1082 

Ω

. Using this knowledge, you can 

determine whether the problem is with the controller or 
sensor, or a wiring problem.

Wrong Analog Input Display

If either of the two analog input readings is slightly high 
or low, the respective Low and High scaling limits can 
be adjusted slightly. Let's say that the AI1 value is 5°F 
low and AI1 has a span from -40°F to 160°F. Change the 
scaling for the Low and High Limits to be -35°F to 165°F, 
instead of -40°F to 160°F. You can also measure DC volt-
age from "AI1" to "C" and "AI2" to "C". The 4 to 20mA 
inputs are represented as 1 to 5VDC signals here. Using 
this knowledge, you can determine whether the problem 
is with the controller or your input device, or a wiring prob-
lem.

MONITORING SCREENS

Continually pressing the scroll button allows more exten-
sive monitoring. The screens are shown below. 

ALARM STATUS

CHECK

*SZ1145*

TCS V2.0(C)

ALARM STATUS

CHECK

TEMP1 HIGH ALARM

TEMP2 LOW ALARM

TEMP3 LOW ALARM

TEMP4 LOW ALARM

2.

1.

AI1 HIGH ALARM

AI2 HIGH ALARM

3.

Summary of Contents for SZ1145

Page 1: ...F 6 7 to 48 9 C are suitable for monitoring temperatures in this range If any of these inputs exceed their high or low limits the alarm output relay is energized Features Stand alone or network opera...

Page 2: ...ity sensing TS TX Series for temperature sensing TD TL Series for dif ferential air sensing The SZ1145 also accepts four two wire remote temperature sensors for general pur pose temperature monitoring...

Page 3: ...on Temp2 Alarm Low Limit Screen Enter a low limit temperature setting When the Temp2 input temperature falls to this value an alarm will be generated This screen is not shown if the Temp2 alarm is not...

Page 4: ...his screen is not shown if the AI1 alarm is not enabled AI1 Alarm High Limit Screen Enter a high limit value When the AI1 input rises to this value an alarm will be gen erated This screen is not shown...

Page 5: ...the amount of time that an analog alarm condition Temp1 4 AI1 2 must be pres ent before actually generating the alarm The time is adjustable in 15 second incre ments from 0 minutes and 0 seconds to 6...

Page 6: ...oses based on your selection an Alarm Condition is generated Open refers to the input as being Open or Off and closed refers to the input as being Closed or On 15 SECOND DI DELAY If either of the two...

Page 7: ...the wires or terminal block from ter minals NO to COM Measure W from terminals NO to COM If the reading is 0W the mechanical relay is defective R 2800 LAURA LANE MIDDLETON WI 53562 800 288 9383 FAX 6...

Page 8: ...us Screen Shows the DI1 and DI2 status Alarm Relay Status Screen Shows alarm relay output status Override Status Screen Shows whether the override is active and if so how many minutes remaining This s...

Reviews: