Sensor input wiring 18

5

Sensor input wiring 18 AWG, twisted, shielded pair.

External relay.  24 VAC coil.

6

Dry contact. Must not be powered.

4

2-wire, 4-20mA transmitter.
AWG, twisted, shielded pair.

3

24 VAC transformer. See powering instructions.

2

1

For communication wiring, use twisted, shielded 18
AWG. Must be run separately.

RS485

C

R

+P

IN1

DI1

DI2

T1

POWER

IN2

A

B

REF

COM

T2

T4

T3

T2

T1

T4

T3

NO

DATA

SZ1145

GENERAL
PURPOSE
MONITOR

ALARM

ALARM STATUS

OK

+

2

3

4

4

+

3

+

5

Black

Red

5

Black

Red

5

Black

Red

5

Black

Red

A

R

6

+-

2

B

7

Up to nominal 28 VAC from transformer.

7

1

REF

To

To

To

To

Wiring                                     

The SZ1145 uses terminal designations for wiring. See 
diagram below.

TRANSMITTER WIRING

The SZ1145 accepts two 2-wire, 4-20mA transmitters. 
Use TH Series for relative humidity sensing, TS/TX 
Series for temperature sensing, TD/TL Series for dif-
ferential air sensing. The SZ1145 also accepts four 
two-wire remote temperature sensors for general pur-
pose temperature monitoring.  Consult the TS Series 
Temperature Sensor Submittal Data sheet for a com-
plete listing of packaging and application styles.  When 
using TCS/Basys Controls three-wire sensors, use the 
black and red leads and either clip or twist off the white 
lead. Make sure that the dip switches are set for the 
sensors you are using.

POWERING THE SZ1145

The SZ1145 is powered from 24 VAC +/- 20 %. 

Caution:

  Do not connect to 120 VAC.  When multiple 

TCS/Basys Controls devices are using a single 
transformer, the polarity of the power wiring 
must be maintained because all TCS devices 
are half-wave rectified and have common return 
paths.

If wiring for communications, dedicated power must be 
used to power the SZ1145. Several “S” series controllers 
may be powered from the same transformer, provided 
that the transformer has sufficient power.  (Supertrols 
require 5 VA @ 24 VAC.) 

Summary of Contents for SZ1145

Page 1: ...F 6 7 to 48 9 C are suitable for monitoring temperatures in this range If any of these inputs exceed their high or low limits the alarm output relay is energized Features Stand alone or network opera...

Page 2: ...ity sensing TS TX Series for temperature sensing TD TL Series for dif ferential air sensing The SZ1145 also accepts four two wire remote temperature sensors for general pur pose temperature monitoring...

Page 3: ...on Temp2 Alarm Low Limit Screen Enter a low limit temperature setting When the Temp2 input temperature falls to this value an alarm will be generated This screen is not shown if the Temp2 alarm is not...

Page 4: ...his screen is not shown if the AI1 alarm is not enabled AI1 Alarm High Limit Screen Enter a high limit value When the AI1 input rises to this value an alarm will be gen erated This screen is not shown...

Page 5: ...the amount of time that an analog alarm condition Temp1 4 AI1 2 must be pres ent before actually generating the alarm The time is adjustable in 15 second incre ments from 0 minutes and 0 seconds to 6...

Page 6: ...oses based on your selection an Alarm Condition is generated Open refers to the input as being Open or Off and closed refers to the input as being Closed or On 15 SECOND DI DELAY If either of the two...

Page 7: ...the wires or terminal block from ter minals NO to COM Measure W from terminals NO to COM If the reading is 0W the mechanical relay is defective R 2800 LAURA LANE MIDDLETON WI 53562 800 288 9383 FAX 6...

Page 8: ...us Screen Shows the DI1 and DI2 status Alarm Relay Status Screen Shows alarm relay output status Override Status Screen Shows whether the override is active and if so how many minutes remaining This s...