TCS Basys Controls SZ1022 Product Manual Download Page 12

R

2800 LAURA LANE • MIDDLETON, WI 53562 •  (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

12

(SYSTEM SWITCH button), and the unoccupied fan 

mode in programming.  If the fan is off but the fan LED 

is on, check wiring. Short terminals “R” to “G” and see if 

the fan comes on. This is a check for a mechanical relay 

failure. 

Heating or Cooling Does Not Come On

At least one stage of heating is on whenever the heating 

LED is on, and at least one stage of cooling is on when-

ever the cooling LED is on.  If heating or cooling should 

be on but the heating or cooling LED is off:
1. Check the fan and system switch modes. 
2. Check the heating and cooling setpoints.
3. Check the room temperature to be sure heating or 

cooling should be on. 

4. Check the offsets and differentials.
5. If using outdoor air or discharge air high and low lim-

its, check their values to be sure heating or cooling is 

allowed. 

If heating or cooling is off, but the corresponding SED is 

on, check the wiring.  Short terminals “R” to “W1”, “W2” 

“Y1”,Y2”, or “G” and see if the heating, cooling, or fan 

comes on. This is a check for a mechanical relay failure. 

Wrong Temperature Display

Initially, verify the wiring connections to check for prob-

lems (poor connections, opens, or shorts). If the tem-

perature is at a minimum or maximum reading, check 

that the sensor dipswitch positions are correct as shown 

in the Setup section of this document. Also, verify the 

resistance reading for the sensor in question. A remote 

sensor should read 1080 to 1090 ohms at room temper-

ature. The built-in sensor should read 108 to 109 ohms 

at room temperature. If any of the temperatures are still 

reading slightly high or low, you can add in a tempera-

ture offset (calibration) using Ubiquity or TCS Insight. 

In Ubiquity, you can edit the calibration offset for each 

temperature input (room, discharge, outdoor air, etc.) on 

the controller's programming page. For example, if the 

room temperature is reading 2 degrees high, you would 

subtract 2 from the existing offset in the room tempera-

ture calibration offset field and submit the page. In TCS 

Insight, the process is similar. Refer to the Calibrate 

Using TCS Insight Tech Bulletin # 1019 for details. As 

a last resort and only when directed to do so by TCS 

technical support, you may be able to use the on-

board adjustment pots. Refer to the Thermostat Sensor 

Calibration Tech Bulletin # 1005 for details.

setpoint adjustment limits.  Change this to +/-20 °F 

(11.1 °C).  Press the PROGRAM SETUP button once 

more to store the change.  Then press the SERVICE 

STATUS button once to exit the programming. 

4. Press the FAN SWITCH button to access the fan 

mode and change the mode to AUTO.  Press the 

FAN SWITCH button once more to store the change.   

Press the SYSTEM SWITCH button to access the 

system mode and change the mode to AUTO.  Press 

the SYSTEM SWITCH button once more to store the 

change.  

5. Verify that the thermostat is operating in the occupied 

mode by making sure that the top LED is lit.  If not, 

press the OVERRIDE button.  The LED should light 

up. 

6. Take note of the current temperature reading.  Press 

the WARMER (up) button.  The setpoint adjustment 

screen should now be showing.  Press the WARMER 

button until the heating setpoint is greater than the 

current temperature by at least five degrees.  The fan 

will come on.  The heating stage(s) will sequence on 

after 30 seconds. 

7. Press the cooler (down) button until the heating set-

point is one degree less than the current temperature.  

The heating stage(s) will sequence off.  The fan will 

turn off 2 minutes after the last heating stage. 

8. Press the cooler button until the cooling setpoint is 

less than the current temperature by at least five 

degrees.  The fan will come on. The cooling stage(s) 

will sequence on after 30 seconds. 

9. Press the warmer button until the cooling setpoint is 

greater than the current temperature by one degree.  

The cooling stage(s) will sequence off. The fan will 

turn off 2 minutes after the last cooling stage.

10. Go back to programming step #14 and set the set-

point adjust limit back to the desired value. Make any 

other changes in programming, clock, and schedule.  

Set the fan and system modes to their desired set-

tings. 

11. If using remote sensors, verify that the reading is 

correct. If not, see 

Wrong Temperature Display 

in the 

Troubleshooting

 section.

TROUBLESHOOTING
No Display

Check for 24 VAC on terminals “+24” and “-24”.  Check 

ribbon cable connecting the cover to the base for a good 

connection.

Fan Does Not Come On

The fan is on whenever the fan LED is on. If the 

fan should be on, but the fan LED is off, check 

the fan (FAN SWITCH button) and system modes 

T1

T2
T3

1  2

1  2  3  4  5

adjust display contrast

LIMIT SETPOINT

ADJUST  +/-:              5F

Summary of Contents for SZ1022

Page 1: ...or limited with the use of an access code Fahrenheit or Celsius temperature display Uses ZigBee protocol IEEE 802 15 4 compliant Self healing plug play mesh network 100mW output at 2 4 GHz 150 to 500...

Page 2: ...install a jumper between the R and 24 terminals The 24 terminal must then be connected to the common side of the unit transformer Wiring The SZ1022 SZ1031 and SZ1035 use standard terminal designation...

Page 3: ...sensor only Using remote room sensor with both discharge and outdoor air sensors SZ1031 and SZ1035 only KEYPAD ACCESS The dipswitches in the thermostat cover shown above must be set in order to lock...

Page 4: ...aud Rate Screen If using a PC to do programming all controllers on a network must be set to the same baud rate Choose between 2 4K 4 8K 9 6K and 19 2K Display Type Screen Choose between FAHRENHEIT and...

Page 5: ...4TH STAGE AS COOL 25 program setup ENABLE THIRD STAGE AS DISABLE 26 program setup HEAT STAGE 1 OFFSET 0F 27 program setup OCCUPIED COOL SETPOINT B 75F 16 program setup OCCUPIED COOL SETPOINT C 75F 17...

Page 6: ...etup ENABLE OUTDOOR AIR FUNCT YES 44 DISCHARGE AIR LOW LIMIT 45F ENABLE DISCHARGE AIR FUNCT YES program setup 41 program setup TIMECLOCK OUTPUT OCCUPIED CLOSED program setup 40 DISCHARGE AIR HIGH LIMI...

Page 7: ...CONDS DI3 USED FOR FILTER SERVICE program setup 50 program setup SET DI2 SETPOINT SHIFT 00F program setup 49 ENABLE SMART RECOVERY NO 52 program setup 51 program setup SET ACCESS CODE 248 55 MON 11 19...

Page 8: ...ed Times Screen Set hours and minutes of start and end times for up to two occupied periods Schedule Announcement Screen Announces the next screen Copy Schedule Screen Indicate whether or not to use t...

Page 9: ...such as with a switch or wind up timer If each occupancy period is about the same theaters meetings another option is to set the DI3 to external override and use the timed override button to put the...

Page 10: ...ment to the building load The offset value is the amount away from the setpoint a stage will turn off By assign ing a stage a value other than zero you anticipate that the residual heat or cooling in...

Page 11: ...35 also have a P I option Without enabling this option stages turn on and off based on temperature vs setpoint alone as described above By enabling this option you allow a time factor to be added This...

Page 12: ...support you may be able to use the on board adjustment pots Refer to the Thermostat Sensor Calibration Tech Bulletin 1005 for details setpoint adjustment limits Change this to 20 F 11 1 C Press the P...

Page 13: ...the override is active and if so how many minutes remain ing service status MON 11 19 01 12 00 AM 72F service status SERVICE STATUS OK 1 service status OUTDOOR AIR TEMP 75F 3 service status DISCHARGE...

Page 14: ...allow the occupant to change the system mode is allowed by factory default To lock out access to system switching see programming step 5 SETTING CLOCK SCHEDULE The ability to set the clock and schedul...

Reviews: