R
2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com
5
Occupied Heat Setpoint Screen.
Set the heat setpoint for this occupied
period.
Occupied Heat Setpoint Screen.
Set the heat setpoint for this occupied
period.
Occupied Heat Setpoint Screen.
Set the heat setpoint for this occupied
period.
Unoccupied Heat Setpoint Screen.
Set the unoccupied heat setpoint.
Occupied Cool Setpoint Screen.
Set the cool setpoint for this Occupied
period.
Occupied Cool Setpoint Screen.
Set the cool setpoint for this Occupied
period.
Occupied Cool Setpoint Screen.
Set the cool setpoint for this Occupied
period.
Occupied Cool Setpoint Screen.
Set the cool setpoint for this Occupied
period.
Unoccupied Cool Setpoint Screen.
Set the unoccupied cool setpoint.
User Setpoint Limit Screen.
Enter the
number of degrees you want the user to
be allowed to change the preset occupied
setpoints up or down.
Override Time Screen.
Enter the number
of minutes (0 to 255) that the Superstat will
maintain occupied setpoints when over-
ridden.
Heat Stage 1 Differential Screen.
Enter a
differential value for heat stage 1.
Cool Stage 1 Differential Screen.
Enter
a differential value for cool stage 1.
Control Mode Screen.
Enter if you want
to control by temperature only (P) or add a
time factor (P+I).
Discharge Air Sensor Function Screen.
Choose whether or not you are using a
discharge air sensor function. To monitor
only, select NO. See setup instructions for
dipswitch settings which must also be set.
Discharge Air Low Limit Screen.
Enter a discharge air low limit value. This
screen will not appear if the discharge air
sensor function is disabled.
Discharge Air High Limit Screen.
Enter
a discharge air high limit value. This
screen will not appear if the discharge air
sensor function is disabled.
program
setup
SET OVERRIDE
TIME: 180 MINUTES
22.
program
setup
UNOCCUPIED COOL
SETPOINT:
80F
20.
program
setup
HEAT STAGE 1
DIFF:
1F
23.
program
setup
COOL STAGE 1
DIFF:
1F
24.
program
setup
SET CONTROL
MODE:
P
25.
program
setup
DISCHARGE AIR
LOW LIMIT: 045F
27.
program
setup
DISCHARGE AIR
HIGH LIMIT: 125F
28.
program
setup
ENABLE DISCHARGE
AIR SENSOR? NO
26.
program
setup
OCCUPIED HEAT
SETPOINT C: 70F
13.
program
setup
OCCUPIED HEAT
SETPOINT B: 70F
12.
program
setup
OCCUPIED HEAT
SETPOINT D: 70F
14.
OCCUPIED COOL
SETPOINT A: 75F
program
setup
16.
OCCUPIED COOL
SETPOINT C: 75F
program
setup
18.
OCCUPIED COOL
SETPOINT D: 75F
program
setup
19.
OCCUPIED COOL
SETPOINT B: 75F
program
setup
17.
program
setup
UNOCCUPIED HEAT
SETPOINT: 60F
15.
program
setup
LIMIT SETPOINT
/-: 05F
21.