Occupied Heat Setpoint Screen.   

Set the heat setpoint for this occupied 

period. 

Occupied Heat Setpoint Screen.   

Set the heat setpoint for this occupied 

period. 

Occupied Heat Setpoint Screen.   

Set the heat setpoint for this occupied 

period. 

Unoccupied Heat Setpoint Screen.  

Set the unoccupied heat setpoint. 

Occupied Cool Setpoint  Screen.   

Set the cool setpoint for this Occupied 

period. 

    

    

Occupied Cool Setpoint  Screen.   

Set the cool setpoint for this Occupied 

period.

Occupied Cool Setpoint  Screen.   

Set the cool setpoint for this Occupied 

period.

Occupied Cool Setpoint  Screen.   

Set the cool setpoint for this Occupied 

period.

Unoccupied Cool Setpoint Screen.  

Set the unoccupied cool setpoint.

User Setpoint Limit Screen.  

Enter the 

number of degrees you want the user to 

be allowed to change the preset occupied 

setpoints up or down.  

Override Time Screen.  

Enter the number 

of minutes (0 to 255) that the Superstat will 

maintain occupied setpoints when over-

ridden.  

Heat Stage 1 Differential Screen.  

Enter a 

differential value for heat stage 1.  

Cool Stage 1 Differential Screen.  

Enter 

a differential value for cool stage 1.  

    

Control Mode Screen.  

Enter if you want 

to control by temperature only (P) or add a 

time factor (P+I).

Discharge Air Sensor Function Screen.  

Choose whether or not you are using a 

discharge air sensor function. To monitor 

only, select NO. See setup instructions for 

dipswitch settings which must also be set.  

Discharge Air Low Limit Screen.  

Enter a discharge air low limit value.  This 

screen will not appear if the discharge air 

sensor function is disabled. 

 

 

Discharge Air High Limit Screen.  

Enter 

a discharge air high limit value.  This 

screen will not appear if the discharge air 

sensor function is disabled.  

program

setup

SET OVERRIDE

TIME:    180 MINUTES

22.

program

setup

UNOCCUPIED COOL

SETPOINT: 

80F

20.

program

setup

HEAT STAGE 1

DIFF: 

1F

23.

program

setup

COOL STAGE 1

DIFF: 

 

 

 

1F

24.

program

setup

SET CONTROL

MODE: 

P

25.

program

setup

DISCHARGE AIR

LOW LIMIT:        045F

27.

program

setup

DISCHARGE AIR

HIGH LIMIT:        125F

28.

program

setup

ENABLE DISCHARGE

AIR SENSOR?      NO

26.

program

setup

OCCUPIED HEAT

SETPOINT  C:          70F

13.

program

setup

OCCUPIED HEAT

SETPOINT  B:          70F

12.

program

setup

OCCUPIED HEAT

SETPOINT  D:          70F

14.

OCCUPIED COOL

SETPOINT  A:          75F

program

setup

16.

OCCUPIED COOL

SETPOINT  C:          75F

program

setup

18.

OCCUPIED COOL

SETPOINT  D:          75F

program

setup

19.

OCCUPIED COOL

SETPOINT  B:          75F

program

setup

17.

program

setup

UNOCCUPIED HEAT

SETPOINT:          60F

15.

program

setup

LIMIT SETPOINT

/-:        05F

21.

Summary of Contents for SZ1009

Page 1: ...ing or schedule may be locked out or limited with the use of an access code Fahrenheit or Celsius temperature display Convertible to heat pump mode in programming Contents Description 1 Features 1 Mou...

Page 2: ...designations for wir ing See diagram below REMOTE TEMPERATURE SENSOR WIRING Use 18 AWG shielded twisted pair grounded at the sen sor mounting location Sensor wiring runs of up to 250 feet are attainab...

Page 3: ...outdoor air sensor only Using remote room sensor with both discharge and outdoor air sensors KEYPAD ACCESS The dipswitches in the thermostat cover shown above must be set in order to lock the user out...

Page 4: ...K 9 6K and 19 2K Display Type Screen Choose between FAHRENHEIT and CELSIUS for tem perature indication Controller Type Screen Choose Conventional or Heat Pump mode Unit will reset the screen will mome...

Page 5: ...cool stage 1 Control Mode Screen Enter if you want to control by temperature only P or add a time factor P I Discharge Air Sensor Function Screen Choose whether or not you are using a discharge air s...

Page 6: ...n on programming through the PC consult your TCS soft ware manual SETTING CLOCK SCHEDULE THROUGH THE KEYPAD To access the clock and schedule screens press the clock setup button To make changes use th...

Page 7: ...xternal time clock OVERRIDE A timed override is available using the button on the face of the thermostat or through momentary contacts wired into the OVR terminal The amount of time the unit will be o...

Page 8: ...G LOCKOUT TEMP all cooling stages will be locked out and will remain locked out until the outdoor air temperature rises 2 above the lockout temperature If the outdoor temperature rises above the HEATI...

Page 9: ...HECK DI2 NO Dry contact switch Any type DI2 SERVICE OFF or ON for monitoring and indication DI2 Monitor with NO OK YES shifts setpoint by Dry contact switch setpoint shift DI2 OPEN or CLOSED programme...

Page 10: ...e warmer button until the cooling setpoint is greater than the current temperature by one degree The cooling stage s will sequence off The fan will turn off 2 minutes after the last cooling stage 10 G...

Page 11: ...the service status button simultaneously Service LED is On If the service LED is on it may be for monitoring purposes or it may indicate a critical problem The first monitoring screen which is used t...

Page 12: ...put are closed PROGRAM DATA This LED will be lit when the thermostat is within the pro gramming or clock setup menus It will blink when the unit is being accessed by a PC Additional monitoring is avai...