5. Electronic Function
5.1 Abbreviation
T1: Indoor ambient temperature
T2: Middle indoor heat exchanger coil
temperature
T2B: Indoor heat exchanger exhaust coil
temperature (located on the outdoor unit)
T3: Outdoor heat exchanger pipe temperature
T4: Outdoor ambient temperature
T5: Compressor discharge temperature
5.2 Electric Control Working Environment.
5.2.1 Input voltage: 230V.
5.2.2 Input power frequency:
60Hz.
5.2.3 Indoor fan standard working amp.: <1A
5.2.4 Outdoor fan standard working amp.: <1.5A.
5.2.5 Four-way valve standard amp.: <1A.
5.3 Main Protection
5.3.1 Compressor Restart Delay
---- The compressor takes 1 minute to start up the
first time. Further restarts take 3 minutes.
5.3.2 Temperature Protection of Compressor
Discharge.
When the
discharge temperature of the
compressor rises, the running frequency is limited
according to the following rules:
----If 10
5
℃
(
221
℉
)
≦
T5<
110
℃
(230
℉
),
maintain the current frequency.
----If the temperature increase and
T5
≧
110
℃
(
230
℉
), decrease the frequency to a lower level
every 2 minutes till to F1.
---If T5
≧
115
℃
(
239
℉
) for 10 seconds, the
compressor stops and then restart untill T5<90
℃
(194
℉
).
5.3.3 Fan Speed Malfunction
---- If outdoor fan speed is lower than
100RPM
or
higher than 2400RPM for
6
0 seconds or more,
the unit stops and LED displays
E8
failure code.
5.3.4 Inverter Module Protection.
---- The inverter protection module ensures that
faults related to current, voltage, or temperature
does not damage the inverter.
If these protections are triggered, the A/C unit
stops and the LED displays the failure code.
The unit restarts 3 minutes after the protection
mechanism has turned off.
5.3.5 Low Voltage Protection
VOLTAGE
No limit
VOLT_LTM_FREQ1_ADD
VOLT_LTM_FREQ2_ADD
Note: If low voltage protection triggers and
voltage is not restored to normal within 3
minutes, the protection remains active even
after a machine restart.
5.3.6 Compressor Current Limit Protection
The temperature interval for the current limit is
the same as the range of the T4 frequency limit.
Cooling mode:
Summary of Contents for MMCUT18AS2
Page 3: ...3 MMCUT36AS4 WD30 metal plate 114 MMCUT48AS5 WE30 metal plate 121...
Page 10: ...10...
Page 23: ...23 6 Wiring Diagrams 6 1 Wiring diagram of 1 drive 2 outdoor MMCUT18AS2...
Page 24: ...24 6 2 Wiring diagram of 1 drive 3 outdoor MMCUT27AS3...
Page 25: ...25 6 3 Wiring diagram of 1 drive 4 outdoor MMCUT36AS4...
Page 29: ...29...
Page 43: ...43 Operating Standby Pic 2 IPM for 2 zone 3 zone...
Page 59: ...59 Operating Standby Pic 2 IPM board for 2 zone 3 zone...
Page 66: ...66 IPM board for 2 zone 3 zone...
Page 68: ...68 IPM board for 4 zone...
Page 71: ...71 Two ports of the inductance Inductance...
Page 74: ...74 Vs Vcc Vsp FG...
Page 77: ...77...
Page 80: ...80...
Page 83: ...83...
Page 94: ...94 6 EXV check Disconnect the connectors...
Page 96: ...96 Red Blue Red Yellow...
Page 97: ...97 Brown Orange...
Page 98: ...98 Brown White...
Page 108: ...108 Screws of right rear panel Screws of terminal board...